KITOZER
KITOZER

KITOZER Oil Transformer: 2000kVA 10kV/0.4kV Distribution

KITOZER 2000kVA oil immersed distribution transformer converts 10kV utility voltage to 400V for industrial plants, commercial parks, and rural substations. Mineral oil provides both insulation and cooling, allowing high overload capability and long service life in outdoor environments. This model is designed for pole pad mount or ground mount installation with low total owning cost. Oil cooled transformers remain the workhorse of outdoor distribution because they tolerate overload, heat, and vibration better than dry type alternatives at the same power rating.

Product Overview

The transformer has a laminated silicon steel core wound with copper or aluminium conductors, immersed in mineral oil inside a corrugated or finned steel tank. A conservator tank with silica gel breather accommodates oil expansion and contraction. Off circuit tap changers on the high voltage side allow voltage adjustment of plus or minus 2 times 2.5 percent. Buchholz relay, pressure relief valve, and thermometer provide protection and remote alarm. Cooling is by natural oil circulation (ONAN). The tank is fitted with lifting lugs, oil drain valve, and earthing bolts. A thermometer with mercury or capillary bulb measures top oil temperature and provides alarm and trip contacts.

Technical Specifications

Rated power 2000kVA, primary 10kV plus or minus 2 times 2.5 percent, secondary 400V, Dyn11 connection, impedance 6 percent, frequency 50/60Hz. No-load loss 2680W, load loss 14300W at 75 degrees Celsius. Oil volume approximately 600kg, weight approximately 4200kg. Cooling ONAN, temperature rise 65K winding, 60K oil. Ambient temperature minus 25 to plus 40 degrees Celsius. The transformer can be overload by 30 percent for 2 hours under ONAN cooling without damage. Buchholz relay alarm on gas accumulation, trip on internal surge. Pressure relief valve operates at 0.05MPa. Compliance with IEC 60076 and GB/T 6451. Noise level is 62dB, suitable for outdoor installation away from noise sensitive areas.

Applications

This transformer is used as the main supply transformer in industrial plants, manufacturing workshops, logistics parks, and agricultural processing facilities. It is also used in utility distribution substations feeding residential communities and in outdoor kiosk substations. Oil cooled transformers are preferred where outdoor installation, high ambient temperature, and overload duty are expected. They are less suitable for indoor occupied buildings where fire codes prefer dry type. In mining and quarry sites, the rugged tank withstands vibration and dust. In rural electrification, the transformer sits on a concrete plinth or pole platform and feeds several villages through low voltage lines.

Advantages

Oil cooling handles temporary overloads well and tolerates high ambient temperature. The tank is rugged and suitable for outdoor installation without extra enclosure. Low cost per kVA compared with dry type. Off circuit tap changer allows compensation for long cable voltage drops. Mineral oil can be filtered and reused, lowering maintenance cost. The transformer has a typical service life of 30 years or more with proper oil maintenance. Buchholz and pressure protection give early warning of internal faults. Because oil is also a diagnostic medium, regular dissolved gas analysis can detect incipient faults such as partial discharge or overheating years before they cause failure.

Installation and Maintenance

Place the transformer on a concrete plinth with oil spill bund, connect high and low voltage cables without stress, and check oil level before energization. Commissioning includes insulation resistance, ratio, no-load, and oil dielectric test. Maintenance annually includes oil sample for dielectric and dissolved gas analysis, silica gel replacement, terminal tightening, and buchholz relay check. Every five years, filter or replace oil if breakdown voltage drops below 30kV. Keep the radiators free of dust and vegetation. Ensure the earthing system connects both tank and neutral properly. After a trip on Buchholz, investigate the gas sample before re-energizing, because accumulation of acetylene indicates an internal arc that requires major inspection.

Ordering and Support

Ordering requires the kVA rating, primary and secondary voltage, impedance, tap changer range, and oil type. KITOZER supplies the transformer filled with mineral oil, complete with buchholz and thermometer calibration certificates and a routine test report. Recommended spares include silica gel, gasket kit, and drain valve. Technical support covers oil sampling schedule, protection relay settings, and foundation design. The transformer is backed by a two year on site warranty and a ten year warranty on the tank against oil leakage.

Price

From $13,800/pc. Contact +86 13922289957 for oil transformer pricing.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com

Shopping Cart