When base stations, roadside equipment, rooftop telemetry and remote power gear have to survive rain, dust, heat and overnight freeze cycles, a standard indoor rack simply will not hold up. The KITOZER outdoor telecom cabinet is a purpose-built weatherproof enclosure engineered for rooftop, pole-mount and ground-pad deployment, with a dedicated 1500W cabinet air conditioner, double-wall thermal insulation, and a pre-wired power and alarm chain — ready to accept your active equipment with minimum on-site work.
Table of Contents
ToggleTypical application scenarios
This enclosure class is specified when active electronics have no shelter to live in. Common fits include:
- 4G/5G rooftop and street-base-site extension cabinets hosting radio units, baseband boxes and power modules
- Outdoor CCTV, traffic and ITS equipment housings beside junctions, tunnels and toll plazas
- Remote environmental monitoring stations for water, gas and pipeline SCADA
- Edge computing and mini-DCIM nodes at unmanned substations and pumping stations
- Outdoor energy storage and battery cabinets requiring climate-controlled compartments
The reference configuration below targets a two-tier equipment load with about 3000W total heat dissipation on a rooftop, where sunlight load, wind uplift and condensation all have to be designed out of the cabinet rather than tolerated.
Mechanical construction
The standard cabinet measures 800 mm wide × 1000 mm deep × 1500 mm tall, fabricated from welded steel sheet with a matte light-gray powder coat rated for outdoor UV exposure. The shell is not a single skin: a 30 mm rock-wool insulation sandwich sits between an inner galvanized liner and the outer skin, sealed along every edge to block condensation and moisture vapor transmission. A sloped sunshade roof sheds rain and cuts direct solar load on the door.
A 150 mm reinforced welded base with four extended press-plates gives the cabinet a rigid footing. Anchor weight, down-hold straps and uplift calculation are sized separately against local wind-load, anti-overturning and anti-slip requirements — the cabinet itself does not ship with concrete ballast or roof-anchor engineering.
Cooling design — why a 1500W unit on a 3000W load

A common mistake is to size the cabinet air conditioner to the nameplate heat load. A 1500W rated unit is selected here because it is run below its maximum continuous rating, and the cabinet is designed around a measured heat balance rather than a nominal figure. Real-world checks include:
- Solar load on the sun-facing door and roof is offset by the double-wall insulation and reflective roof coating
- The cooling unit is sized so it cycles rather than runs flat out, which keeps humidity under control and lengthens compressor life
- Hot exhaust is ducted away from the fresh-air intake so the unit does not short-cycle on its own exhaust
- Drainage for condensed water is routed through a heated trace or drain heater so it does not freeze in winter
If the active load genuinely needs to sustain 3000W of continuous dissipation, a second cooling unit or a larger 2000–3000W cabinet AC should be quoted rather than overloading a 1500W unit.
Power distribution and protection
Inside, a 19-inch 1U six-way PDU distributes AC mains to the equipment, with a 16A input and per-socket rating matched to the plugs actually used. A separate distribution box provides a main breaker plus independent branch circuits for the active gear, the cooling unit and the monitoring circuit, each with over-current and residual-current protection as required by the installation. The reference cabinet uses a 32A frame as a pre-selection placeholder; the actual breaker rating is set after the field supply and load are confirmed.
Door bonding, grounding terminals, shielded cable glands and a labeled wiring kit are factory-assembled so the on-site electrician only lands the external feed.
Monitoring and alarm
A compact 4G SMS alarm kit watches cabinet temperature, humidity and mains failure. It uses a built-in rechargeable backup battery so it still sends a warning when AC power drops, and reports over SMS to designated site engineers. The SIM and airtime are arranged on the customer side. The alarm kit is a standalone unit — it does not require a licensed monitoring platform to function.
Reference configuration and indicative pricing (EXW Guangzhou, USD)
The list below is a technical reference budget for a single cabinet built to the rooftop scenario described above. Prices are indicative market reference figures in US dollars, EXW Guangzhou, excluding tax, freight and on-site installation. Final pricing depends on exact dimensions, equipment list, cooling capacity and finish requirements.
| # | Item | Specification | Qty | Unit Price (USD) | Amount |
|---|---|---|---|---|---|
| 1 | Outdoor custom cabinet | 800×1000×1500 mm, double-wall insulated | 1 | $828 | $828 |
| 1-1 | Double-wall insulated sunshade roof | 30 mm rock-wool sandwich, sealed edges | 1 | $97 | $97 |
| 1-2 | Reinforced welded base with press plates | 150 mm high, four extended anchor plates | 1 | $97 | $97 |
| 2 | Cabinet air conditioner | AC220V, rated cooling 1500W | 1 | $467 | $467 |
| 3 | 19-inch PDU | 1U, six outlets, 16A input | 1 | $42 | $42 |
| 4 | Reinforced equipment shelf | 2 mm steel, folded edge, four-point fixed | 1 | $33 | $33 |
| 4-1 | Lower heavy-duty shelf | Support ≥500×700 mm, frame-bolted | 1 | $33 | $33 |
| 5 | Cable gland kit | Bottom entry, IP68 glands, 4 entries | 1 | $19 | $19 |
| 6 | Installation hardware kit | Bonding, grounding, clamps, labels | 1 | $22 | $22 |
| 6-1 | Distribution and branch protection | Main breaker + equipment/AC/alarm branches | 1 | $78 | $78 |
| 7 | 4G SMS temperature/power alarm kit | Temp/humidity probe, backup battery, antenna | 1 | $181 | $181 |
| 8 | Factory integration and test | AC cutout, wiring, alarm config, heat-balance check | 1 | $69 | $69 |
| Subtotal (EXW Guangzhou, before tax) | $1,966 |
Lead time is typically 15–25 working days after technical confirmation and deposit. MOQ is one cabinet. Warranty is 12 months from shipment. Freight, customs, roof fastening, concrete ballast and structural wind-load certification are not included.
Why specify KITOZER outdoor cabinets
KITOZER builds outdoor enclosures as an integrated product rather than a repackaged indoor rack. Every cabinet leaves the factory with the cooling cutout, rack mounting, PDU, distribution and alarm chain already fitted and tested together, so the on-site crew lands power and equipment rather than assembling a climate-controlled room. Dimensions, cutouts and mounting points are adjusted to your exact equipment list before fabrication starts.
Frequently asked questions
Can you build non-standard sizes? Yes. Width, depth, height, door configuration, cable entries and cutouts are all adjustable. Send your equipment outline drawing and we return a dimensional layout for confirmation before production.
What protection rating does the cabinet achieve? The base cabinet is designed to IP55 with properly sealed glands and a closed door. Overall rating depends on gland selection and door-seal condition; it is not a rating a single component can guarantee on its own.
Is the cooling unit always 1500W? No. 800W, 1500W, 2000W and 3000W cabinet AC units are available. The right size is chosen from the measured heat balance, not the nameplate.
Do you supply the battery and SIM card? No. The alarm kit ships ready for a local SIM; battery backup is internal. The customer arranges the SIM and airtime plan.
Contact KITOZER
KITOZER / Guangzhou Laian Intelligent System Development Co., Ltd.
Tel / WeChat: +86 13922289957 · +86 18520668845
WhatsApp: +86 19068534140
Web: www.gdlain.com · www.lain.com.cn
Address: Chaotian Park, Zhongrun Industrial Zone, No.5 Huashan Road, Shilou, Panyu, Guangzhou, China
This article is a technical reference and indicative budget compiled from publicly available industry practice; figures are market reference prices for planning purposes and are not a formal quotation.