Routine inspection of distribution panelboard breakers prevents nuisance tripping and hidden thermal faults. KITOZER recommends a visual and thermal scan every 6 months. With the panel door open under safe procedures, check that breaker handles are fully seated, lugs are tight to the manufacturer torque spec, and no discoloration or burn marks appear on the busbar. Use a thermal camera to compare breaker surface temperatures against ambient; any breaker running more than 15K above adjacent poles indicates a loose connection or overload. Never rely on manual reset as a fix for repeated trips, because repeated overload stress weakens the bi-metal trip mechanism and shortens breaker life. Log every reading in the panel maintenance file.
Table of Contents
ToggleChecks
Handle seated, lug torque, busbar color, thermal scan 15K limit. KITOZER PDB inspection from $180.