Loose busbar joints and cable lugs are the root cause of most electrical fires in low-voltage distribution panels. KITOZER recommends torqueing all main and branch lugs annually to the manufacturer spec listed on the breaker or busbar nameplate. After de-energizing the panel, use a calibrated torque wrench and follow the diagonal tightening sequence for multi-bolt joints. Apply a thin layer of antioxidant contact grease to aluminum lugs to prevent oxide buildup, but never use grease on copper-to-copper connections, which can insulate and cause heating. Re-torque after the first 3 months of operation on a new installation, then once a year thereafter. Record the torque value and inspector name on the panel door label.