ToggleProduct Overview
The KITOZER pneumatic tube fire detection and suppression device is a fully self-contained linear fire detection unit designed for small, enclosed, or hard-to-reach electrical compartments where point detectors cannot provide adequate coverage. A temperature-sensitive polymer tube is routed through the protected volume, taped or clipped to cable trays, bus bars, and equipment interiors. When a fire raises local temperature above the rated threshold, the tube bursts at the hottest point, dropping pressure inside the tube. That pressure drop is sensed at the manifold, which immediately opens the agent cylinder and sends extinguishing agent back through the same tube to the burst point. Because the tube itself is both detector and nozzle, the system reacts in seconds with no electronics, no power, and no commissioning software. KITOZER offers the device in a range of cylinder sizes and agents including HFC-227ea, Novec 1230, and dry powder, making it ideal for electrical cabinets, wind turbine nacelles, marine switchboards, rail signaling cabinets, and industrial control enclosures.
Technical Specifications
The detection tube is a single-layer EVA copolymer with a bursting temperature of 68 degrees Celsius or 90 degrees Celsius depending on selection, and a minimum bend radius of 50 mm. Tube length per zone is typically 6 to 30 meters, and the tube is rated for continuous ambient temperatures up to 60 degrees Celsius. Cylinders are offered in 1.5 kg, 3 kg, 6 kg, and 12 kg nominal agent capacities, pressurized with nitrogen to 6 MPa. The manifold includes a pressure switch, manual release, gauge, and solenoid interface for optional remote alarm signaling. Discharge time is less than 10 seconds, and the burst point acts as the nozzle, delivering agent directly onto the hottest spot. Operating voltage for the optional alarm circuit is 24 VDC, and the device is certified to EN 12094 and ISO 14520 standards. The complete unit mounts on a DIN rail or steel bracket inside the protected cabinet, occupying roughly 200 by 150 by 300 mm of space.
Applications
KITOZER pneumatic tube systems are installed inside low-voltage switchgear, motor control centers, PLC cabinets, UPS modules, battery racks, frequency drives, railway signaling cubicles, wind turbine nacelles, marine electrical panels, telecommunications base stations, and server rack enclosures. They are also used in elevator machine rooms, cash counting cabinets, and small archive lockers where a standalone detection and release path is preferred. Because the system is intrinsically safe and requires no external power, it is suitable for explosion-hazard zones where electronic detectors must be intrinsically safe certified.
Advantages and Features
The KITOZER device has four practical strengths. First, the linear tube detects fire at the exact location of overheating, eliminating the delay that occurs when smoke must travel to a point detector. Second, because the burst point is the nozzle, agent concentration is highest exactly where the fire starts, minimizing collateral discharge. Third, the system operates without external power, so it protects cabinets that are de-energized or during main-power outages. Fourth, installation is fast: a technician clips the tube, bolts the cylinder, and wires the optional alarm contact, typically completing a single cabinet in under an hour. The tube is also translucent, so inspectors can visually check for aging, cracking, or discoloration during routine visits.
Installation and Maintenance Recommendations
Route the tube at least 50 mm away from hot surfaces such as transformer resistor banks and exhaust ducts, and avoid sharp bends that could create premature burst points. Secure the tube with nylon clips every 300 mm, leaving enough slack to accommodate thermal expansion. Do not paint the tube, because paint can soften the polymer and alter the burst temperature. After any discharge, replace the entire tube segment and the cylinder, then weigh the cylinder and record the serial number in the maintenance log. Inspect the gauge monthly for pressure drop, and perform a visual tube inspection quarterly. Every five years, replace the tube regardless of condition, because polymer aging reduces burst accuracy. Keep a spare cylinder and tube kit on site for rapid restoration. Price starts from $480 per 1.5 kg HFC-227ea unit.
Ordering and Factory Support
When ordering, KITOZER requires the protected cabinet volume, the heat load inside the cabinet, and the preferred tube routing length. The factory supplies a matched cylinder, manifold, tube, and initiator cable as one kit, so installers do not need to source components separately. Each kit is labeled with a unique serial number and includes a wiring diagram, a tube installation guide, and a one-year warranty. For large projects, KITOZER can pre-cut and pre-label the tube to the measured length, reducing on-site work and ensuring consistent bend radii. Spare initiators and pressure switches are stocked locally for fast replacement. For projects that require remote monitoring, KITOZER can add a supervisory module that transmits tube pressure, cylinder presence, and discharge events to the building management system, giving operators continuous visibility into cabinet-level fire protection.