The KITOZER point heat detector rate-of-rise responds to both a fixed temperature threshold and a rapid rise in ambient temperature, providing reliable fire detection in environments where smoke detectors would cause false alarms. The rate-of-rise element triggers when temperature climbs faster than a set slope, while the fixed-temperature element triggers when the ceiling reaches a threshold such as 57 or 70 degrees Celsius. This dual-element design catches fast-flaming fires that produce little smoke and is suitable for kitchens, garages, boiler rooms, and dusty workshops.
Table of Contents
ToggleProduct Overview
The detector is a compact ceiling-mounted unit with a thermistor and bimetal or fusible element. It mounts on a standard base wired to the fire alarm loop. An LED indicates normal and alarm status. The unit is available in conventional and addressable versions and is rated for higher ambient temperatures than smoke detectors.
Technical Specifications
Fixed temperature options are 57 degrees Celsius or 70 degrees Celsius. Rate-of-rise trigger is 8 degrees Celsius per minute. Operating voltage is 12 to 24 volts DC. Standby current is less than 50 microamps. Alarm current is 20 to 50 milliamps. Operating temperature range is -10 to 60 degrees Celsius for standard, or up to 80 degrees for high-temperature models. Weight is approximately 110 grams.
Application Scenarios
Heat detectors are used in kitchens, boiler rooms, garages, warehouses, dusty workshops, loading docks, and other areas where smoke, steam, dust, or cooking fumes would falsely trigger smoke detectors. They are also used in unheated spaces where condensation affects optical detectors. They are not a substitute for smoke detectors in occupied sleeping areas but provide robust secondary detection.
Advantages
Rate-of-rise detection catches fast-flaming fires that smoke detectors may miss. Fixed-temperature backup ensures alarm even if temperature rises slowly. Heat detectors are immune to dust, steam, and insects, reducing false alarms. They are low-cost and low-maintenance. The dual-element design gives broad coverage across fire growth rates.
Installation and Maintenance
Mount on the ceiling at code-specified spacing, at least 300 millimeters from walls. Avoid locations directly above ovens, radiators, or duct outlets where normal temperature swings could cause false alarms. Test annually with a heat gun or test wand. Inspect for dust or insect nests. Replace every 10 years. Keep the sensing chamber unobstructed.
Engineering Notes
Install heat detectors in kitchens, garages, and dusty areas where smoke detectors false alarm. Avoid mounting directly above heat sources. Test annually with a heat gun. Keep the sensing chamber clear. Choose high-temperature versions for boiler rooms.
Code and Compliance
Heat detectors must comply with local heat detector standards. Verify the fixed temperature and rate-of-rise settings match the environment. Annual testing includes heat response checks. Keep a detector schedule on the as-built drawing.
Warranty and Accessories
From $38 per rate-of-rise heat detector. The detector carries a five-year warranty. KITOZER supplies fixed temperature and rate-of-rise versions, plus high-temperature models. Spare bases are available. Contact +86 13922289957 for high-temperature versions.
Detailed Application Examples
Ten rate-of-rise heat detectors cover a kitchen and boiler room where smoke detectors false alarm from cooking fumes. The 57 degree Celsius fixed element and rate-of-rise element catch both slow and fast fires. Heat gun tests confirm operation annually. Detectors are replaced at 10 years.
Long-term Operational Benefits
Heat detectors have no optical chamber to clean and no sensitivity drift, making them the most maintenance-free detection device. They are immune to dust, steam, and insects, which reduces nuisance calls and replacement. The 10 year service life means they rarely need replacement. Because they are standardized, replacement units are cheap. Annual testing is fast with a heat gun.
System Integration
Heat detectors share the same loop and base as smoke detectors, so the same wiring infrastructure supports both types. In kitchens, heat detectors replace smoke detectors to avoid cooking nuisance alarms. The panel can be programmed to treat heat detector alarms as a separate class, triggering a different response. Remote indicators allow alarm location from outside the room.
Why Choose KITOZER
KITOZER heat detectors are built for harsh environments and backed by a five-year warranty. Each detector is heat-tested before shipment. KITOZER supplies matching bases and high-temperature models as a complete package, ensuring reliable detection in kitchens and boiler rooms.
Summary
In summary, the point heat detector provides dependable fire detection in environments where smoke detectors would false alarm. Its rate-of-rise and fixed temperature elements cover both fast and slow fires. KITOZER supplies the detector with a five-year warranty and supports high-temperature and industrial versions.
KITOZER supports project quantities and fast delivery for retrofit and new build sites.
Each unit is backed by local technical support and a global spares network.
For high-temperature locations, KITOZER offers a 90 degree Celsius model.
Price
From $38 per rate-of-rise heat detector. Contact +86 13922289957 for high-temperature versions.