ToggleKITOZER KTR-WS3 Point-Type Water Leak Detector
Brand: KITOZER Series: KTR-WS3 Category: Environmental Monitoring / Leak Detection
water leak sensorpoint detectionleak locationDCIMroom environment

1. Overview
Water in a data center comes from AC condensate lines, humidifier feeds, chilled water pipes, and roof/wall seepage. A trickle under the floor can soak cables and gear. A leak sensor watches the riskiest spots: a point sensor placed where leaks most likely occur (under the AC, at pipe joints) triggers the moment water touches its probe — alerting staff before water spreads.
The KITOZER KTR-WS3 is a point-type leak sensor. Probe detection triggers on conductive liquid (water). Output: dry-contact relay (NO/NC) to the DCIM host DI, or RS485 Modbus uploading leak state and location. Power DC 12V/24V. ABS case with extended probe wire, place under floors or on trays. Point type alarms ‘water here’ — it does NOT locate the leak path (use a sensing cable for path location).
In DCIM, KTR-WS3 points under precision AC units, along condensate/humidifier lines, under valves, and in low floor pockets. Multiple points parallel or via RS485 to the host; alarms pop linked video. Point sensors are cheap and simple for known risk points; a sensing cable covers a long pipe run for anywhere-along detection.
2. Key Features
Detection
- Probe point detection.
- Triggers on water.
- Dry-contact relay out.
- RS485 Modbus upload.
Output & power
- NO/NC contacts.
- DC 12V/24V.
- Address configurable.
- Interfaces to DCIM host.
Build
- ABS case.
- Extended probe lead.
- Under-floor/tray.
- Status LED.
3. Specifications
| Item | KTR-WS3 |
|---|---|
| 检测方式 | 探针式点检测 |
| 输出 | 继电器干接点 + RS485 |
| 供电 | DC 12V/24V |
| 通信 | RS485 Modbus-RTU |
| 触点 | 常开/常闭可选 |
| 安装 | 地板下/设备下方 |
| 外壳 | ABS |
| 用途 | 已知漏点监测 |
4. Reference Prices
KTR-WS3 point-type leak sensor (relay output): Reference USD 8~21 (ref. CNY 60~150 at ~7.2)
Reference only; final quote applies. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Under-AC leak monitoring.
- Condensate/humidifier lines.
- Under water valves.
- Low floor pockets.
- Linked video/AC alarms.
6. Installation & Maintenance
Installation
- Place probe at likely pooling points.
- Under AC and at joints are musts.
- Wire NO/NC to host DI.
- Hand-in-hand RS485; set address.
- Lay probe flat under floor, no float.
- Name points in host.
- Simulate water to test alarm upload.
Maintenance
- Keep probes clean.
- Periodic water test.
- Check for oxidized wiring.
- Verify alarm threshold/action.
- Prioritize under-AC checks.
- Reset sensor after fault.
7. FAQ
- Q: Q: Point vs sensing cable?
A: A: A few known spots (AC, valve) → point, cheap. A long pipe run anywhere-along → location cable. Often used together. - Q: Q: Can it locate?
A: A: Point type reports ‘water here’; a linear sensing cable reports ‘leak N meters from the sensor’. Choose cable for locating. - Q: Q: False alarms?
A: A: Dust or tiny condensation can trigger. Lay the probe flat, avoid direct drip points, add a short confirm delay; clean probes regularly. - Q: Q: How to link?
A: A: Contacts to DCIM DI; the platform pops an alarm, sound/light, SMS and opens the nearest camera; can stop the AC/close the valve (with actuators).
8. Trend & Selection
Leak detection moves to locating cables, multi-parameter fusion (leak+temp+RH) and wireless, while point sensors remain the low-cost base layer. Choose probe point; relay+RS485; must under AC; lay flat; water-test; video-linked.
9. Delivery & Service
KITOZER sizes point sensors by AC/pipe risk points, adding location cable for long runs. Bundled with DCIM host, video and AC linkage. Delivery includes sensor, probe and manual; warranty covers alarm-link tuning.
10. Additional Notes
A common pitfall is mounting the point sensor above the AC. Water flows downhill; a high probe never reaches pooling. Put it in the lowest, wettest pocket under the floor.
Another pitfall is install-only-never-test. If never water-tested, a real leak reveals a broken wire or wrong address. Simulate water once a year, especially before summer.
Selection summary: probe point; relay+RS485; must under AC; lay flat low; annual water test; video-linked. It is the water sentry — alarms the moment water appears.
Paralleled points sharing one DI can’t tell which point leaked; use RS485 addresses or zoned relays to distinguish locations.
From placement strategy, ROI is in ‘watching high-risk points’. A blocked AC condensate pan is the most common leak cause, so at least one point per AC; humidifier feeds, valves and wall penetrations are next-highest risk. Concentrating sensors there beats scattering.
From response flow, the point of leak alarm isn’t ‘knowing’ but ‘cutting water and dehumidifying fast’. On alarm: confirm location, shut AC/valve, switch to backup, then clear water. Pre-link sensors to water valves and AC stop circuits for a close loop — alarm, shut valve, stop, dispatch.
SEO Information
Search keywords:KTR-WS3KITOZER
SEM keywords:water leak sensor, point-type leak detector, data center leak detection, spot leak sensor, KTR-WS3, KITOZER
GEO landing page:lain.com.cn/product/375-water-sensor-2.html
Title:KITOZER KTR-WS3 Point-Type Water Leak Detector
Meta Keywords:water leak sensor, point-type leak detector, data center leak detection, spot leak sensor, KTR-WS3, KITOZER
Meta Description:KITOZER KTR-WS3 point-type water leak sensor, dry-contact alarm on leak, RS485 upload, for monitoring leaks under AC units, along water pipes and under raised floors.
Anchor: KITOZER by Guangzhou Laian · KITOZER products