Table of Contents
ToggleKITOZER KTR-SPDB Type 1 Power Surge Protection Box
Brand: KITOZER Series: KTR-SPDB Category: Power Distribution / Type 1 SPD
type 1 SPDpower surge box10/350μslightning protectionKTR-SPDB

1. Overview
A power surge protective device (SPD) mounts after the mains incoming cabinet and before the UPS, diverting transient overvoltages from lightning or switching to ground so the UPS and servers survive. Lightning surges riding the power feed can reach thousands of volts — more than UPS and servers can withstand. The SPD is the floodgate that dumps surge energy into the earth grid.
Protection is staged: Type 1 (T1) at the building main entry diverts 10/350μs direct-lightning induced current (Iimp 12.5~35 kA); Type 2 (T2) at floor panels diverts 8/20μs surges; Type 3 (T3) fine-protects at the device. KTR-SPDB is a Type 1 box, modular plug-in so failed modules swap individually, with remote dry contacts that alarm the EMCS on degradation, and a digital-display model showing leakage current.
Selection hinges on Iimp (10/350μs): high-rises and high-thunderstorm areas choose 80~120 kA; general rooms start at 40 kA. More important is coordination — T1 must be followed by T2 and T3 in stages; no single box takes all surges. SPDs are consumables: each strike degrades them, modules replaced every 3~5 years; the remote alarm tells you when.
2. Key Features
Diversion
- Type 1, 10/350μs direct-strike current.
- Iimp 12.5~35 kA options.
- In 20~60 kA (8/20μs).
- L-N/L-PE/N-PE full-mode.
Status monitoring
- Remote dry contacts to EMCS.
- Window: green normal / red failed.
- Digital display shows leakage current.
- Modular plug-in, single-swap.
Safety
- Back-up breaker/fuse coordinated.
- Thermal + current disconnection.
- Flame-retardant enclosure, IP30.
- Terminals to 70 mm².
3. Specifications
| 项目 | KTR-SPDB-40 | KTR-SPDB-80 | KTR-SPDB-120 |
|---|---|---|---|
| 防雷等级 | 一级(T1) | 一级(T1) | 一级(T1) |
| 标称放电电流In | 20 kA(8/20μs) | 40 kA(8/20μs) | 60 kA(8/20μs) |
| 冲击电流Iimp | 12.5 kA(10/350μs) | 25 kA(10/350μs) | 35 kA(10/350μs) |
| 最大持续电压 | ~385V | ~385V | ~385V |
| 保护模式 | L-N/L-PE/N-PE | L-N/L-PE/N-PE | L-N/L-PE/N-PE |
| 遥信告警 | 接点输出 | 接点输出 | 接点输出+数显 |
| 接入线径 | ≤35mm² | ≤50mm² | ≤70mm² |
4. Reference Prices
KTR-SPDB-40 type-1 SPD box (40kA, wall):Reference USD 111~250 / pc (ref. CNY 800~1,800 at ~7.2)
KTR-SPDB-80 type-1 SPD box (80kA, floor):Reference USD 208~444 / pc (ref. CNY 1,500~3,200 at ~7.2)
KTR-SPDB-120 type-1 SPD box (120kA, high):Reference USD 389~764 / pc (ref. CNY 2,800~5,500 at ~7.2)
Reference only; final quote depends on capacity, core count, airflow, channel count, current rating, battery cells, length and point count. 1-year warranty included; volume pricing available. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room mains incoming Type-1 protection.
- Data center and building main distribution.
- Outdoor base stations and pump stations.
- Factory, hospital, school distribution.
- Weak-current system incoming protection.
6. Deployment & Implementation
Installation
- Wire in series after main entry, before UPS.
- Ground lead short and thick (≤0.5 m, ≥16 mm²).
- ≥10 m or de-couple from T2.
- Phase order correct, Rg ≤4 Ω.
Operations
- Check window indicator before storm season.
- Replace degraded modules on remote alarm.
- Whole-module swap every 3~5 years.
- Tighten terminals; watch overheating.
7. FAQ
- Q: Can T1 and T2 merge?
A: Not advised. They need de-coupling distance (≥10 m) for energy coordination; merging overloads T2. Staged install is what works. - Q: SPD window red — still usable?
A: Red means the module has degraded/failed; protection is reduced — replace soon, and gear can still be damaged meanwhile. - Q: Does poor grounding make the SPD useless?
A: Mostly. The SPD dumps surge through the ground lead; Rg >10 Ω leaves high residual voltage. Fix the earth grid first (≤4 Ω). - Q: Is SPD absolutely safe?
A: No. SPD clamps surge to within device limits and degrades over strikes; critical gear still needs UPS + good grounding, multi-layered.
8. Trend & Selection
SPDs go modular and smart: built-in monitoring (leakage current, remote upload to cloud) so BMS sees each SPD health; T1+T2 combo units (10/350 + 8/20) save space. Select Iimp by local storm intensity (coastal/high ground 80~120 kA); stage T1/T2/T3 with spacing; keep ground lead short and thick; wire remote alarm to EMCS; swap modules every 3~5 years. Surge protection is peace-of-mind spending — invisible daily, worth its weight when lightning hits.
9. Delivery & Service
KITOZER provides KTR-SPDB Type-1 selection: by incoming capacity and local storm grade, we size 40/80/120 kA with back-up breaker, links and ground bar. Factory-includes box, modules and remote wire. 1-year warranty; staged protection scheme design available.
10. Additional Notes
A common pitfall is a thin, long ground lead. The SPD dumps surge through the earth wire; thin and long means high impedance and residual voltage still reaches gear. Keep it short (≤0.5 m), thick (≥16 mm²), straight to the room ground bar.
Another is installing only T1 and skipping T2/T3. T1 diverts big current but residual is still kV-level; the UPS and gear need T2/T3 to clamp fine. A complete defense is staged — not one box.
Summary: size by storm intensity; stage T1/T2/T3; ground ≤4 Ω with short thick lead; wire remote alarm to EMCS; swap modules every 3~5 years. The SPD is the room’s second lightning rod — quiet year-round, earning its keep on the day it matters.
SEO Information
Search keywords:type 1 SPDpower surge protective device10/350μs surge boxdata center lightning protectionSPD boxKTR-SPDBKITOZER
SEM keywords:type 1 power SPD price,surge protection box,10/350μs lightning arrester,data center SPD,KTR-SPDB,KITOZER
GEO landing page:lain.com.cn/product/ktr-spdb-surge-protection-box.html
Title:KITOZER KTR-SPDB Type 1 Power Surge Protection Box
Meta Keywords:type 1 power surge protective device,10/350μs SPD box,lightning protection,KTR-SPDB,KITOZER
Meta Description:KITOZER KTR-SPDB type-1 power surge box, 10/350μs, 40/80/120kA, modular plug-in, remote alarm, for mains incoming protection.
Anchor: KITOZER by Guangzhou Laian · Power SPD
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com