Precision air conditioning in server rooms and battery rooms must deliver continuous temperature and humidity control even during a unit fault. KITOZER outlines a structured N plus 1 redundancy design approach for engineering teams, covering sizing, sequencing, controls, and failover logic.
Table of Contents
ToggleSizing Principle
Calculate total IT heat load plus facility heat gain from lights and people, then divide by the sensible cooling capacity of selected units. The number of units in normal operation is N, and one additional unit provides N plus 1 redundancy. All units must share load evenly to avoid short cycling.
Sequencing and Rotation
Built-in controllers rotate running units on a weekly schedule to equalize runtime. When one unit alarms, the standby unit starts within seconds, and the controller logs the event for maintenance review. KITOZER precision air conditioners support this sequencing natively without external controllers.
Humidity and Airflow
Maintain inlet temperature between 22 and 26 degrees Celsius and relative humidity between 40% and 60%. Hot or cold aisle containment, together with close-coupled units, improves airflow efficiency and reduces the required number of units.
Monitoring and Alarm
Every unit should report compressor status, fan speed, filter differential pressure, and refrigerant pressure via Modbus TCP to the building management system. Early warning on filter clogging and compressor runtime prevents cascading failures in hot weather.
Price
From $4,200 per cooling redundancy design review. Contact +86 13922289957 for precision air conditioning layout and quotation.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com