KITOZER Precision AC Refrigerant Piping Connection Guide

This guide covers refrigerant piping between KITOZER indoor and outdoor units. Copper piping must be sized according to the manufacturer table, with insulation thickness at least 15 mm on suction lines and full NBR closed-cell foam on both lines to prevent sweating. Slope the pipe toward the outdoor unit for oil return, and minimize bends using long-radius elbows. Every brazed joint must be pressure tested with dry nitrogen at 40 bar for 24 hours, then evacuated below 500 microns before charging refrigerant. Never vent refrigerant to atmosphere; recover it with a machine during service.

Test Values

Pressure test 40 bar, vacuum 500 microns. Installation labor from $600.