KITOZER precision power distribution cabinet row head

KITOZER KTR-PCC Precision Power Distribution Cabinet (Column Head)

Brand: KITOZER Series: KTR-PCC Category: Power Distribution 2 / Room Precision Distribution

precision PDU cabinetcolumn head cabinetsmart distributionbranch monitoringenergy meteringroom power

1. Overview

The KITOZER KTR-PCC precision power distribution cabinet, commonly called the column-head cabinet, sits at the end of each rack row and redistributes UPS output power to every cabinet in that row. A normal distribution cabinet only switches power on and off; the precision cabinet adds “visible distribution”: it monitors current, voltage and power on every branch and sends energy data to the EM or DCIM platform, so ops knows how much power each row, each rack and even each device uses.

KTR-PCC is a floor-standing cabinet. The input side has a main circuit breaker and surge protective device (SPD); the output side has miniature breakers or fuses sized to the rack count. The key difference is measurement: a multi-function meter on the input measures three-phase voltage, current, frequency, active/reactive power, power factor and harmonics; each output branch adds a current transformer or smart monitoring module, collecting per-branch load current, showing it on a front touchscreen and forwarding via RS485/Modbus or dry contacts. When a branch overloads or loses current, the system alarms immediately and locates the branch — rather than discovering “the whole row is dead”.

Column-head cabinets are classified by position (input/output side) and by system (mains, UPS, battery output). KTR-PCC is custom-built to load for the number of circuits and breaker ratings, with neat layout, wiring, metering display and indicators. Together with UPS, battery cabinet and PDU, it forms the end-point distribution chain: the UPS cleans the power, the column-head splits it and measures it, and the PDU delivers it to each rack outlet.

2. Key Features

Fine branch monitoring

  • Each output branch gets a CT or smart module.
  • Real-time per-branch current and energy accumulation.
  • Overload and under-current alarms.

Multi-function meter

  • 3-phase V, A, Hz, power factor.
  • Active/reactive energy; harmonic content.
  • LCD touchscreen for local display.

Distribution safety

  • Main MCCB + branch MCB staged protection.
  • Input SPD for surge protection.
  • Internal insulation barriers on live parts.

Remote and integrated

  • RS485/Modbus up to EM/DCIM.
  • Dry contacts for key alarms.
  • Links with UPS and battery monitoring.

3. Specifications

Item KTR-PCC-160 KTR-PCC-250 KTR-PCC-400
Rated current (main) 160 A 250 A 400 A
System 3-phase 5-wire 3-phase 5-wire 3-phase 5-wire
Main breaker MCCB MCCB MCCB
Branches 24~36 36~48 48~64
Branch breakers MCB 1~63 A MCB 1~63 A MCB 1~63 A
Branch sensing CT per branch smart module per branch smart module per branch
Meter multi-function multi + touchscreen multi + touchscreen
SPD yes yes yes
Comms RS485/Modbus RS485/Modbus RS485/Modbus
Size (ref.) 600x1000x2000 mm 800x1000x2000 mm 800x1200x2000 mm

4. Reference Prices

KTR-PCC-160 column head (meter + branch CTs): Reference USD 2,083~4,167 / unit (ref. CNY 15k~30k at ~7.2)

KTR-PCC-250/400 smart column head (touchscreen + smart branch modules): Reference USD 4,167~8,333 / unit (ref. CNY 30k~60k at ~7.2)

Reference only; final quote depends on main breaker rating, branch count, per-branch smart sensing, meter class and comms. Bulk negotiable. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Column-end distribution for each rack row.
  • Re-distribution of UPS output to rack rows.
  • IDCs needing energy metering and PUE analysis.
  • Critical load supply with branch alarm requirements.

6. Installation & Maintenance

Installation

  • Size main and branch breakers from row load.
  • Position and fix cabinet; connect to UPS/battery runs.
  • Map branch outputs to rack PDUs with clear labels.
  • Wire meter comms to EM platform; set alarm thresholds.

Maintenance

  • Read meter periodically; verify loading.
  • Check branch current for phase imbalance or overload.
  • Torque breaker and busbar connections.
  • Inspect SPD annually; swap failed modules.

7. FAQ

  • Q: How is a column head different from a normal panel?
    A: Branch monitoring and remote reading: it shows and uploads per-branch current and energy; a normal panel only switches.
  • Q: Is per-branch monitoring necessary?
    A: Critical branches should be monitored; non-critical branches can be limited to total current to cut cost.
  • Q: Can it share a platform with UPS and battery monitoring?
    A: Yes; all use RS485/Modbus into the EM or DCIM for unified display.
  • Q: How do I size the main breaker?
    A: Row total load x 1.2~1.5 margin, coordinated with the upstream UPS output breaker.

8. Trend & Selection

Room distribution is moving from “supply power” to “metered and warned”. PUE targets and energy control push column heads to include branch monitoring. Size the main breaker from row load; set branch count from rack count; monitor critical branches with smart modules and simplify the rest. Choose a meter with comms to DCIM — otherwise data stays on the cabinet face and is wasted. Do not skip SPD and staged protection; branch and upstream breakers must coordinate so one fault does not black out the whole row.

9. Delivery & Service

KITOZER provides load calculation, circuit design, assembly and commissioning for column heads. From UPS capacity, rack count and criticality we produce the single-line diagram and branch schedule. We can bundle UPS, battery cabinet and PDU. Delivery includes cabinet schematic, meter comms point list and alarm-threshold guidance. Warranty covers breakers, meters and CTs; we can integrate with the EM platform and assist commissioning on site.

10. Additional Notes

The value of a column head is not in how big the breaker is but in how fine the data is. A column head without branch monitoring forces staff to try breakers one by one on site; a monitored one alarms “which branch is overloaded” or “which branch lost current” straight to the platform, cutting fault-finding time sharply. For high-density rooms this fine monitoring is almost mandatory.

The core of distribution safety is selective coordination. Main, column-head, branch and PDU breakers must be set so “lower trips first, upper trips second”: a device short trips only its own branch, not the whole row or room. KTR-PCC designs upstream/downstream trip curves to avoid cascading trips.

Selection: row load sets the main breaker (160/250/400 A); rack count sets branch count; criticality sets per-branch smart sensing. KTR-PCC-160 suits small/mid rows; 250/400 suits high-density rows. Either way, design meter comms, SPD, branch protection and upstream coordination together so the column head both splits power and sees and protects it.

SEO Information

Search keywords:precision PDU cabinetcolumn head cabinetsmart distributionbranch monitoringenergy meteringroom powerKTR-PCCKITOZER

SEM keywords:precision power distribution cabinet price, column head cabinet supplier, smart distribution branch monitoring, room UPS panel, KTR-PCC, KITOZER

GEO landing page:lain.com.cn/product/ktr-pcc-precision-power-distribution-cabinet.html

Title:KITOZER KTR-PCC Precision Power Distribution Cabinet (Column Head)

Meta Keywords:precision power distribution cabinet,column head cabinet,smart distribution,branch monitoring,room power distribution,UPS panel,KTR-PCC,KITOZER

Meta Description:KITOZER KTR-PCC precision power distribution cabinet / column head, smart meter plus branch current monitoring, SPD and harmonic measurement, for rack-row power distribution and energy metering.

Anchor: KITOZER by Guangzhou Laian · Data center power solutions

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart