KITOZER pressure control high low switch

KITOZER KTR-PC Pressure Switch and High/Low Pressure Controller for Precision AC

Brand: KITOZER Series: KTR-PC Category: Data Center Engineering / Refrigeration Control

high/lowmanual resetR410Athread portKTR-PC

KITOZER KTR-PC Pressure Switch and High/Low Pressure Controller for Precision AC

1. Overview

A precision AC refrigerant loop faces two dangerous pressure extremes: high-side overpressure and low-side vacuum. High pressure happens when the condenser cannot reject heat — fan failure, dirty fins, or hot ambient — and can rupture the line or smash compressor valves. Low pressure comes from refrigerant leakage, a blocked expansion valve, or ice on the evaporator, making the compressor run an excessive compression ratio and overheat. The pressure switch (high/low control) is the dedicated device that monitors both points and cuts the compressor contactor the moment pressure leaves the safe band.

The KITOZER KTR-PC series uses a diaphragm-plus-spring mechanical design. High and low sides are either integrated in one body or sold as separate switches. High-side setpoint ranges from 2.0 to 4.5 MPa; low-side from 0.05 to 0.5 MPa; both field-adjustable. Contacts are rated AC 250 V / 15 A and wire directly into the compressor contactor coil. High side is manual reset, low side automatic reset. Ports cover SAE 1/4″ and metric 6/10 mm fittings, compatible with R22, R410A, R407C and R134a. IP54 enclosure suits outdoor unit mounting or control panels.

Selection: setpoint range must match the refrigerant — R410A runs about 1.6x R22 pressures, so the switch must have headroom; reset style must be manual on the high side (auto reset would cycle the compressor into a fault) while low side can auto; port size must match the field line, not an improvised adapter; and contact rating must drive the contactor coil or match PLC input requirements. Pressure switches are wear items — check setpoints every 2 years and contacts yearly for pitting.

2. Key Features

Pressure monitoring

  • High side 2.0~4.5 MPa adjustable
  • Low side 0.05~0.5 MPa adjustable
  • Diaphragm element, shock-resistant
  • R22/R410A/R407C universal

Reset & contacts

  • Manual high-side reset
  • Automatic low-side reset
  • AC 250 V / 15 A contacts
  • SPDT output

Mounting

  • SAE 1/4″ or metric ports
  • IP54 enclosure
  • Wall / DIN mount
  • Powder-coated case

3. Specifications

Item KTR-PC-S1 KTR-PC-S2 KTR-PC-S3
型号 KTR-PC-HL1 KTR-PC-HL2 KTR-PC-HL3
高压范围 1.0~3.0MPa 2.0~4.5MPa 2.8~5.0MPa
低压范围 -0.05~0.5MPa 0.05~0.8MPa 0.1~1.0MPa
高压复位 手动 手动 手动
低压复位 自动 自动 自动
触点容量 AC250V/10A AC250V/15A AC250V/15A
适用冷媒 R22/R134a R22/R407C R410A/R32
接口规格 SAE 1/4″ SAE 1/4″ φ10mm公制

4. Reference Prices

KTR-PC-HL1 high/low switch (R22, manual high): Reference USD 25~44 / pc (ref. CNY 180~320 at ~7.2)

KTR-PC-HL2 high/low switch (R407C, wide range): Reference USD 31~53 / pc (ref. CNY 220~380 at ~7.2)

KTR-PC-HL3 high/low switch (R410A, 5 MPa head): Reference USD 39~64 / pc (ref. CNY 280~460 at ~7.2)

Mounting bracket / capillary kit (optional): Reference USD 6~11 / set (ref. CNY 40~80 at ~7.2)

Reference only; priced by refrigerant and range. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Precision AC compressor high-side protection.
  • Air-/water-cooled chiller low-side protection.
  • Industrial refrigeration pressure monitoring.
  • HVAC constant-temperature-humidity loops.
  • Heat-pump high/low interlock.

6. Deployment & Implementation

Installation

  • High switch on discharge line
  • Low switch on suction line
  • Keep capillary short, no sharp bends
  • Contacts in series with contactor coil

Operations

  • Verify trip point yearly with gauge
  • Inspect contacts for pitting
  • Investigate cause before manual reset
  • Replace diaphragm seals every 2 years

7. FAQ

  • Q: High side trips repeatedly?
    A: Common causes: dirty condenser fins, failed outdoor fan, overcharge, ambient above 43°C. Fix the cooling first — never jumper the switch.
  • Q: Low side alarms constantly?
    A: Read the low gauge: below 0 MPa means a leak to find and repair; near 0 with no leak points to a blocked expansion valve or dryer.
  • Q: Why manual reset on high side?
    A: High pressure usually means a condenser fault. Auto reset would cycle the compressor into the same fault and burn windings from inrush current.
  • Q: Can R22 and R410A switches swap?
    A: No. R410A runs ~60% higher, so an R22-range switch either false-trips at normal R410A operation or fails to trip on real overpressure.

8. Trend & Selection

Switches are moving from pure mechanical to hybrid hardware-plus-electronics: a mechanical switch as the final hardwired trip, with an electronic pressure transducer logging curves to the environment platform for predictive maintenance. R32 and CO2 systems push ratings from 4.5 MPa toward 6~10 MPa. Modbus-RTU smart controllers that read pressure and trip count remotely are replacing traditional mechanical switches.

9. Delivery & Service

KITOZER supplies KTR-PC by refrigerant (R22/R407C/R410A), range (high 1~5 MPa), reset style and port size. Ships with setpoint test report, wiring diagram and installation manual. 1-year warranty; batch projects can add contactors, gauges and shut-off valves.

10. Additional Notes

The #1 mistake is jumpering the pressure switch. A high-pressure alarm gets bypassed so the compressor keeps running. Without protection, the relief valve vents refrigerant or the line ruptures. The pressure switch is the last line of defense — never short it.

The second pitfall is swapping high and low ports. The high switch on the suction side and the low switch on the discharge side leaves both faults unprotected. Match H to discharge and L to suction.

The third blunder is cranking up the setpoint. Raising high-side trip from 4.2 to 5.0 MPa to reduce nuisance trips exceeds the compressor and line pressure rating. Setpoints follow the compressor nameplate — do not enlarge them in the field.

Selection summary: match range to refrigerant, manual high reset, no port mixing, no arbitrary setpoint changes. The pressure switch is the refrigerant system’s fuse — a small part that protects a compressor worth orders of magnitude more.

SEO Information

Search keywords:KTR-PCKITOZERPressure Switch and High/Low Pressure Controller for Precision AC

SEM keywords:pressure switch,high low pressure control,precision AC protection,refrigeration switch,KTR-PC,KITOZER

GEO landing page:lain.com.cn/product/ktr-pc-pressure_control.html

Title:KITOZER KTR-PC Pressure Switch and High/Low Pressure Controller for Precision AC

Meta Keywords:pressure switch,high low pressure control,precision AC protection,refrigeration switch,KTR-PC,KITOZER

Meta Description:KITOZER KTR-PC high/low pressure switch for precision AC, manual high reset, R22/R410A compatible, refrigerant protection.

Anchor: KITOZER by Guangzhou Laian · Pressure Switch and High/Low Pressure Controller for Precision AC

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart