KITOZER 10kV voltage transformer (PT or VT) steps primary voltage down to 100V or 100 over 3V for metering, protection, and synchronizing. It provides a scaled, isolated voltage reference so that relays and meters can operate safely at low voltage. This model is a fully cast resin insulated indoor PT used in 10kV switchgear for bus voltage measurement, feeder protection, and auto-reclosing schemes. Without a reliable PT reference, directional relays, synchronism check, and voltage controlled capacitor switching cannot function correctly.
Table of Contents
ToggleProduct Overview
The PT is a single-phase double-wound electromagnetic unit encapsulated in cast resin. Primary and secondary windings are wound on a silicon steel core, with a residual voltage winding for earth fault detection in ungrounded or resistance grounded systems. The epoxy housing is sealed against dust and moisture. Primary terminals are fitted with fuses for short circuit protection, and secondary terminals have automatic air break switches to prevent back feed. The unit mounts on a withdrawable truck or fixed panel inside the switchgear. A terminal block at the rear provides easy wiring to the protection and metering circuits.
Technical Specifications
Rated voltage 12kV, rated frequency 50/60Hz, primary voltage 10000V, secondary voltage 100V, residual winding 100 over 3V, accuracy class 0.5 for metering and 3P for protection, rated output 30VA to 100VA, thermal output 200VA. Power frequency withstand 42kV for 1 minute primary to earth, 2kV for 1 minute secondary to earth, lightning impulse withstand 75kV peak. Short-time thermal current on secondary limited by fuses. The three PTs connected in broken delta produce 3 times residual voltage during earth faults, allowing sensitive earth fault detection in unearthed networks. Compliance with IEC 61869-3 and GB 20840. The no-load current is low, so the PT itself does not meaningfully disturb the measured voltage.
Applications
This PT is used on 10kV bus PT panels in KYN28A and XGN switchgear, supplying voltage signals to multifunction meters, protection relays, power quality recorders, and synchronizing check relays. It is also used on capacitor bank panels for voltage controlled switching, on motor feeder panels for undervoltage protection, and on incoming panels for over/under voltage and frequency monitoring. The residual winding supports earth fault detection in unearthed networks, directing maintenance crews to faulted feeders. In generator incoming panels, the PT supplies the synchronism relay that checks phase and voltage match before closing the breaker between two sources.
Advantages
Cast resin insulation eliminates oil handling and fire risk, making the PT suitable for indoor occupied switchrooms. Dual secondary windings allow independent metering and protection circuits. Residual winding enables sensitive earth fault detection without extra sensors. Withdrawable truck allows safe replacement without de-energizing the bus. Accurate 0.5 class supports revenue metering and precise power control. Long service life and low maintenance reduce total cost over decades of operation. Because the PT is a voltage source with very low burden, its accuracy is stable across the connected instrument range, and the fuses isolate internal faults quickly.
Installation and Maintenance
Insert the PT truck into the switchgear compartment, verify primary and secondary fuse ratings, and rack in until the secondary plug engages. Commissioning includes ratio test, polarity test, insulation resistance, and secondary wiring continuity. Ensure the secondary neutral is grounded at one point only to avoid circulating currents. Never short circuit the secondary winding. Inspect annually for resin cracks, fuse integrity, and terminal tightness. Calibrate metering windings every four years. Replace the PT if the core noise increases significantly or if insulation resistance drops below the manufacturer threshold. When replacing primary fuses, use only the same rated current and breaking capacity, and verify that the secondary burden has not grown beyond the PT rated output.
Ordering and Support
Ordering requires the primary and secondary voltage, residual winding requirement, accuracy class, burden, and whether the unit is fixed or truck mounted. KITOZER supplies PTs with ratio test reports, polarity certificates, and primary fuse ratings. Recommended spares include primary fuses and secondary terminal blocks. Technical support covers earth fault detection scheme design and synchronizing relay wiring. Each PT is backed by a five year warranty, and cast resin units carry a long term spare parts commitment.