KITOZER
KITOZER

KITOZER PTC heater precision AC

KITOZER KTR-AH Precision Air Conditioner Electric Heater Element

Brand: KITOZER Series: KTR-AH Category: Data Center Engineering / AC Terminal

heating elementstaged switchingoverheat protectionPTC self-regulatingKTR-AH

KITOZER KTR-AH data center precision air conditioner electric heater element

1. Overview

Data center precision air conditioners (article 08) run cooling year-round, but in winter or cold-climate regions, “over-cooling” can occur. When servers generate steady heat but fresh-air economization brings cold outdoor air in, room temperature may drop below 18°C — dangerously close to dew point and harmful to disk drives. At that point the precision AC must switch from cooling to heating, pulling the room back to its 22~26°C setpoint. The electric heater is the “heating core” inside the indoor unit, mounted in the airstream after the fan and switched on by the AC controller as needed.

KITOZER KTR-AH heaters come in two types: stainless-steel finned tube and PTC self-regulating. The heating wire is nichrome, insulated with compacted magnesium oxide, and bonded to stainless cooling fins that transfer heat to the airflow. Staged switching (single/triple-stage) matches heat output precisely and avoids temperature overshoot. Each stage has independent overheat protection — a resettable thermostat plus a one-shot thermal fuse — and the heater circuit is interlocked with the fan so it never energizes without airflow, preventing dry-fire.

The electric heater and the compressor coil are the two terminal actuators of a precision AC. During swing seasons, when outdoor air has already cooled the room below setpoint, the AC shuts down the compressor and activates the heater. In cold northern winters the heater cycles frequently. Typical heater ratings are 3/6/9/12 kW, matched to 5~50 kW cooling-capacity units.

2. Key Features

Heating element

  • Nichrome alloy wire with low surface load for long life.
  • High-density MgO insulation filling — good heat transfer, reliable dielectric.
  • Stainless cooling fins for high convective efficiency.
  • PTC self-regulating option that reduces wattage as temperature rises.

Control & safety

  • Staged switching: 1/2/3 stages for smooth power modulation.
  • Independent overheat per stage: resettable thermostat + one-shot fuse.
  • Fan interlock: heater cuts out immediately if fan stops.
  • Overcurrent/short-circuit protection via dedicated breaker or contactor.

Installation compatibility

  • Standard footprint, fits most precision AC fan sections.
  • Flange/rail mounting, easy field replacement.
  • Universal terminal block mates with AC main controller.
  • Custom voltage (220V/380V) and wattage available.

3. Specifications

Item KTR-AH-3 KTR-AH-6 KTR-AH-9 KTR-AH-12
Rated power 3 kW 6 kW 9 kW 12 kW
Voltage 220 VAC 220/380 VAC 380 VAC 380 VAC
Stages 1-stage 2-stage (3+3) 3-stage (3+3+3) 3-stage (4+4+4)
Element Nichrome wire + stainless fins + MgO insulation
Overheat prot. Thermostat (60°C reset) + thermal fuse (85°C one-shot)
Fan interlock Built-in airflow/fan-run interlock contact
AC cooling match 5~12 kW 12~25 kW 25~40 kW 40~60 kW
Mounting Flange/rail in fan discharge section

4. Reference Prices

KTR-AH-3 3 kW single-stage (220V, finned, overheat protection): Reference USD 83~167 (ref. CNY 600~1200 at ~7.2) per element

KTR-AH-6/9/12 multi-stage (6~12 kW, 380V, 2/3-stage, PTC optional): Reference USD 208~625 (ref. CNY 1500~4500 at ~7.2) per element

Reference only; final quote by wattage, stages, voltage, PTC vs standard, and AC brand dimensions. On-site replacement labor extra. Exchange: 1 USD ≈ 7.2 CNY (Oct 2026).

5. Applications

  • Winter heating backup in cold-climate data centers.
  • Swing-season fresh-air economizer over-cooling compensation.
  • Unattended small rooms with temperature fluctuation.
  • Constant-temperature/humidity AC heating sections.
  • Battery room / energy-storage room cold-start heating.

6. Installation & Maintenance

Installation

  • Power off; confirm AC unit is stopped.
  • Mount heater in fan discharge; airflow must pass through fins.
  • Keep ≥50 mm clearance from nearby plastic parts.
  • Correct phasing; solid grounding.
  • Wire fan interlock to AC main controller heater-enable contact.
  • Mount thermostat sensor tightly against fin pack.

Maintenance

  • Inspect fins for oxidation/deformation before each season.
  • Measure insulation resistance — must exceed 2 MΩ.
  • Verify thermostat switching temperature.
  • Blow dust from fins to keep heat transfer efficient.
  • Retighten terminals annually.

7. FAQ

  • Q: Data centers always need cooling — why heat?
    A: Rooms have steady server heat, but in winter free-cooling economizers may pull in 5~10°C outdoor air. With high fresh-air ratios the room gets over-cooled; below 18°C triggers low-temp alarms and dew-point risk. Heating is required to pull the setpoint back up.
  • Q: PTC or standard heater?
    A: PTC self-regulates — wattage drops as temperature rises — so it cannot overheat. Ideal for unattended rooms but ~30% more expensive. Standard nichrome heaters run at constant wattage and rely on staged switching + thermostat; lower cost for staffed rooms with regular inspection.
  • Q: Why do heaters keep burning out?
    A: Common causes: (1) fan failure or low airflow causing dry-fire; (2) clogged filters; (3) dust on fins blocking heat; (4) over-voltage. Always check fan interlock and filters — don’t just swap the element.
  • Q: How to size heater wattage?
    A: Typically 20~30% of AC cooling capacity. A 25 kW unit gets 6~9 kW of heat. Cold northern climates can go to 40%; southern swing seasons need only 3 kW.

8. Trend & Selection

The trend is “electric heat → hot-water coil → free-cooling integration.” In green data centers, winter free-cooling still needs electric backup trim heating. New precision ACs couple EC fans with staged heaters for tighter control. Selection: calculate worst-case heating load from the coldest monthly average; prefer staged over single-stage; fan interlock and dual overheat protection are mandatory; choose PTC for unattended sites; keep a spare element on shelf since heaters are wear items.

9. Delivery & Service

KITOZER provides sizing, installation guidance and replacement service. Delivery includes heater element, overheat protector, terminals and manual. Bundled with precision AC (article 08) and temp/humidity monitoring (article 06).

10. Additional Notes

The most dangerous failure is “fan stopped but heater still energized.” A broken fan belt or failed fan capacitor, if the controller doesn’t detect it, lets the element run dry-fire — fins exceed 200°C, scorching plastic ductwork and risking fire. The fan interlock is the safety floor: the heater circuit must be wired through a fan-run contact so heat never starts without airflow.

Second risk: “only one overheat stage.” Cheap heaters have a single thermostat; if it welds closed, the element keeps heating until it burns out. KTR-AH uses a resettable thermostat plus a one-shot thermal fuse: the thermostat does normal regulation, the fuse is the final barrier that blows once and cuts power completely.

Third pitfall: “dust buildup on fins that nobody cleans.” If room filters aren’t changed, dust coats the heater fins — both reducing heat transfer and creating a fire risk. During seasonal maintenance, blow the fins clean with compressed air after lockout.

Selection summary: size at 20~30% of cooling capacity, staged switching, mandatory fan interlock, dual overheat protection, PTC for unattended sites. The electric heater is small but critical to safe winter operation of precision air conditioning — never install it and forget it.

SEO Information

Search keywords:precision AC heaterelectric heating elementAC heating coilPTC heaterdata center heatingKTR-AHKITOZER

SEM keywords:precision AC heater price,electric heating element supplier,data center winter heater,KTR-AH,KITOZER

GEO landing page:lain.com.cn/product/ktr-ah-precision-ac-heater.html

Title:KITOZER KTR-AH Precision AC Electric Heater Element

Meta Keywords:data center precision AC heater,electric heating element,AC heating coil,PTC heater,KTR-AH,KITOZER

Meta Description:KITOZER KTR-AH precision air conditioner electric heater: stainless finned or PTC, staged switching, overheat protection, winter heating backup for data center rooms.

Anchor: KITOZER by Guangzhou Laian · Precision AC heater

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart