ToggleKITOZER KTR-RFU Rack Fan Unit
Brand: KITOZER Series: KTR-RFU Category: Data Center Engineering / Rack Fan Unit
rack fan unitroof fan trayhot aisle exhaustcold aisle containmentKTR-RFU

1. Overview
A rack fan unit mounts on the roof or rear of a rack, pulling hot air out and drawing cold air from the cold aisle, creating directed airflow. The precision AC cools the whole room, but a choked rack — front intake blocked by cables, rear exhaust blocked — still develops local hot spots. The RFU is the active nudge that pulls hot air out before CPUs and drives overheat.
KTR-RFU comes in 3/6/9-fan tiers. Fans are brushless DC (centrifugal or axial) for 50,000+ h life, speed-controlled by temperature (thermostat or rack T/H sensor speeds up as it warms). Each unit has its own PSU (AC 220V or DC 48V), mounts in 1U/2U on the roof, and ducted to the roof vent or ducted back to the hall.
More fans is not always better — airflow must match AC supply. If the cold aisle lacks cold air, roof fans just pull hot air back in from elsewhere, causing short-circuit. The right sequence is cold supply first, then extraction: after cold-aisle containment, rack intake is assured, and the RFU pulls rack hot air into the hot aisle. Size by rack load (one 3-fan group per 3~4 kW), then power (DC48V vs AC220V), noise (quiet zones) and speed control.
2. Key Features
Efficient fans
- Brushless DC fans, 50,000+ h life.
- Thermal speed control, quiet and efficient.
- Even airflow across rack depth.
- Hot-swap fans, no shutdown.
Fit & compat
- Standard 1U/2U roof or rear exhaust.
- Ducts to roof vent/duct.
- AC220V/DC48V options.
- Pairs with cold-aisle containment.
Control & alarm
- Optional thermal start/speed.
- Dry-contact fan status alarm.
- RS485/Modbus to EMCS.
- Dual-PSU redundant option.
3. Specifications
| 项目 | KTR-RFU-3 | KTR-RFU-6 | KTR-RFU-9 |
|---|---|---|---|
| 风机数量 | 3个 | 6个 | 9个 |
| 适用机柜 | 600×600mm | 600×900mm | 800×1000mm |
| 单风机风量 | 约120 m³/h | 约120 m³/h | 约120 m³/h |
| 总风量 | 约360 m³/h | 约720 m³/h | 约1080 m³/h |
| 噪声 | 约52 dB(A) | 约56 dB(A) | 约60 dB(A) |
| 供电 | AC 220V/DC 48V | AC 220V/DC 48V | AC 220V/DC 48V |
| 安装位置 | 柜顶/柜侧 | 柜顶 | 柜顶/列头 |
4. Reference Prices
KTR-RFU-3 rack fan unit (3 fans, roof):Reference USD 83~167 / pc (ref. CNY 600~1,200 at ~7.2)
KTR-RFU-6 rack fan unit (6 fans):Reference USD 153~306 / pc (ref. CNY 1,100~2,200 at ~7.2)
KTR-RFU-9 rack fan unit (9 fans, high airflow):Reference USD 250~486 / pc (ref. CNY 1,800~3,500 at ~7.2)
Reference only; final quote depends on capacity, core count, airflow, channel count, current rating, battery cells, length and point count. 1-year warranty included; volume pricing available. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- High-density rack hot-spot cooling.
- Cold/hot aisle containment extraction.
- Network and server rack forced exhaust.
- Under-cooled telecom rooms and branch cabinets.
- Wall-mount communication cabinet cooling.
6. Deployment & Implementation
Installation
- Roof exhaust or rear exhaust: front-in/back-out.
- Keep cold-aisle intake clear of cable trays.
- Wire power locally; DC48V polarity matters.
- Duct joints sealed to avoid short-circuit.
Operations
- Clean filters/fans every 6 months.
- Listen for bearing noise, replace failed fan.
- Verify thermal setpoint vs supply temp.
- Check speed balance on parallel units.
7. FAQ
- Q: Why RFU if I have precision AC?
A: Room temp is not rack temp. Dense racks (>5 kW) with blocked internal ducting still overheat CPU intake; RFU directs exhaust. - Q: Can RFU replace AC?
A: No. RFU moves air, it does not cool; it pushes rack hot air to the hot aisle while the AC removes heat. Without a cold source it just stirs hot air. - Q: Faster is better?
A: No. Faster is louder, shorter-lived, more power, and upsets cold-aisle pressure balance. Auto speed by rack temp is best. - Q: DC48V vs AC220V?
A: If the room already has -48V DC telecom power, choose DC to share; ordinary rooms choose AC220V into the PDU.
8. Trend & Selection
Rack density rises from 3~5 kW to 8~15 kW, making rear-duct and roof fan walls standard for dense racks; variable fans on real-time temperature deliver demand-based airflow; RFU persists as air-liquid hybrid in the liquid-cooling transition. Select after confirming cold-aisle containment and sufficient cooling; size one 3-fan group per 3~4 kW; keep intake clear; speed-control for noise; match DC/AC to existing power; fans field-replaceable. The RFU is the final push that drives cold air through the gear.
9. Delivery & Service
KITOZER provides KTR-RFU selection: by rack size, per-rack load and power, we size 3/6/9-fan units with thermostat, flexible duct and power cord. Factory-includes fan unit, rails and manual. 1-year warranty; available as part of a full cold-aisle containment package.
10. Additional Notes
A common pitfall is installing fans before containment. Without a closed cold aisle, AC cold air wanders and roof fans pull hot air back into the room — no fix. Sequence: contain the cold aisle first, assure front cold supply, then add RFU extraction.
Another is a blocked intake. The fan pulls cold air from the lower front; if the front is packed with patch cords and cable managers, it recirculates rack hot air and gets hotter. Keep the intake side clear, route cables along sides.
Summary: cold supply first, then extraction; size fans by rack load; keep intake clear; thermal speed control; match DC/AC to power; fans replaceable. The RFU closes the loop — cold air comes in front, hot air goes out back, and the rack runs free of hot spots.
SEO Information
Search keywords:rack fan unitroof fan trayserver rack coolinghot aisle exhaustcold aisle containmentKTR-RFUKITOZER
SEM keywords:rack fan unit price,roof mounted fan tray,server rack exhaust fan,cabinet cooling blower,KTR-RFU,KITOZER
GEO landing page:lain.com.cn/product/ktr-rfu-rack-fan-unit.html
Title:KITOZER KTR-RFU Rack Fan Unit
Meta Keywords:rack fan unit,roof fan tray,server rack cooling,KTR-RFU,KITOZER
Meta Description:KITOZER KTR-RFU rack fan unit, brushless DC fans, 3/6/9 fans, thermal speed control, AC220V/DC48V, for cold/hot aisle containment cooling.
Anchor: KITOZER by Guangzhou Laian · Rack cooling
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com