KITOZER rack fan unit cooling

KITOZER KTR-RFU Rack Fan Unit

Brand: KITOZER Series: KTR-RFU Category: Data Center Engineering / Rack Fan Unit

rack fan unitroof fan trayhot aisle exhaustcold aisle containmentKTR-RFU

KITOZER KTR-RFU rack mounted fan unit tray cooling module for network cabinet

1. Overview

A rack fan unit mounts on the roof or rear of a rack, pulling hot air out and drawing cold air from the cold aisle, creating directed airflow. The precision AC cools the whole room, but a choked rack — front intake blocked by cables, rear exhaust blocked — still develops local hot spots. The RFU is the active nudge that pulls hot air out before CPUs and drives overheat.

KTR-RFU comes in 3/6/9-fan tiers. Fans are brushless DC (centrifugal or axial) for 50,000+ h life, speed-controlled by temperature (thermostat or rack T/H sensor speeds up as it warms). Each unit has its own PSU (AC 220V or DC 48V), mounts in 1U/2U on the roof, and ducted to the roof vent or ducted back to the hall.

More fans is not always better — airflow must match AC supply. If the cold aisle lacks cold air, roof fans just pull hot air back in from elsewhere, causing short-circuit. The right sequence is cold supply first, then extraction: after cold-aisle containment, rack intake is assured, and the RFU pulls rack hot air into the hot aisle. Size by rack load (one 3-fan group per 3~4 kW), then power (DC48V vs AC220V), noise (quiet zones) and speed control.

2. Key Features

Efficient fans

  • Brushless DC fans, 50,000+ h life.
  • Thermal speed control, quiet and efficient.
  • Even airflow across rack depth.
  • Hot-swap fans, no shutdown.

Fit & compat

  • Standard 1U/2U roof or rear exhaust.
  • Ducts to roof vent/duct.
  • AC220V/DC48V options.
  • Pairs with cold-aisle containment.

Control & alarm

  • Optional thermal start/speed.
  • Dry-contact fan status alarm.
  • RS485/Modbus to EMCS.
  • Dual-PSU redundant option.

3. Specifications

项目 KTR-RFU-3 KTR-RFU-6 KTR-RFU-9
风机数量 3个 6个 9个
适用机柜 600×600mm 600×900mm 800×1000mm
单风机风量 约120 m³/h 约120 m³/h 约120 m³/h
总风量 约360 m³/h 约720 m³/h 约1080 m³/h
噪声 约52 dB(A) 约56 dB(A) 约60 dB(A)
供电 AC 220V/DC 48V AC 220V/DC 48V AC 220V/DC 48V
安装位置 柜顶/柜侧 柜顶 柜顶/列头

4. Reference Prices

KTR-RFU-3 rack fan unit (3 fans, roof):Reference USD 83~167 / pc (ref. CNY 600~1,200 at ~7.2)

KTR-RFU-6 rack fan unit (6 fans):Reference USD 153~306 / pc (ref. CNY 1,100~2,200 at ~7.2)

KTR-RFU-9 rack fan unit (9 fans, high airflow):Reference USD 250~486 / pc (ref. CNY 1,800~3,500 at ~7.2)

Reference only; final quote depends on capacity, core count, airflow, channel count, current rating, battery cells, length and point count. 1-year warranty included; volume pricing available. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • High-density rack hot-spot cooling.
  • Cold/hot aisle containment extraction.
  • Network and server rack forced exhaust.
  • Under-cooled telecom rooms and branch cabinets.
  • Wall-mount communication cabinet cooling.

6. Deployment & Implementation

Installation

  • Roof exhaust or rear exhaust: front-in/back-out.
  • Keep cold-aisle intake clear of cable trays.
  • Wire power locally; DC48V polarity matters.
  • Duct joints sealed to avoid short-circuit.

Operations

  • Clean filters/fans every 6 months.
  • Listen for bearing noise, replace failed fan.
  • Verify thermal setpoint vs supply temp.
  • Check speed balance on parallel units.

7. FAQ

  • Q: Why RFU if I have precision AC?
    A: Room temp is not rack temp. Dense racks (>5 kW) with blocked internal ducting still overheat CPU intake; RFU directs exhaust.
  • Q: Can RFU replace AC?
    A: No. RFU moves air, it does not cool; it pushes rack hot air to the hot aisle while the AC removes heat. Without a cold source it just stirs hot air.
  • Q: Faster is better?
    A: No. Faster is louder, shorter-lived, more power, and upsets cold-aisle pressure balance. Auto speed by rack temp is best.
  • Q: DC48V vs AC220V?
    A: If the room already has -48V DC telecom power, choose DC to share; ordinary rooms choose AC220V into the PDU.

8. Trend & Selection

Rack density rises from 3~5 kW to 8~15 kW, making rear-duct and roof fan walls standard for dense racks; variable fans on real-time temperature deliver demand-based airflow; RFU persists as air-liquid hybrid in the liquid-cooling transition. Select after confirming cold-aisle containment and sufficient cooling; size one 3-fan group per 3~4 kW; keep intake clear; speed-control for noise; match DC/AC to existing power; fans field-replaceable. The RFU is the final push that drives cold air through the gear.

9. Delivery & Service

KITOZER provides KTR-RFU selection: by rack size, per-rack load and power, we size 3/6/9-fan units with thermostat, flexible duct and power cord. Factory-includes fan unit, rails and manual. 1-year warranty; available as part of a full cold-aisle containment package.

10. Additional Notes

A common pitfall is installing fans before containment. Without a closed cold aisle, AC cold air wanders and roof fans pull hot air back into the room — no fix. Sequence: contain the cold aisle first, assure front cold supply, then add RFU extraction.

Another is a blocked intake. The fan pulls cold air from the lower front; if the front is packed with patch cords and cable managers, it recirculates rack hot air and gets hotter. Keep the intake side clear, route cables along sides.

Summary: cold supply first, then extraction; size fans by rack load; keep intake clear; thermal speed control; match DC/AC to power; fans replaceable. The RFU closes the loop — cold air comes in front, hot air goes out back, and the rack runs free of hot spots.

SEO Information

Search keywords:rack fan unitroof fan trayserver rack coolinghot aisle exhaustcold aisle containmentKTR-RFUKITOZER

SEM keywords:rack fan unit price,roof mounted fan tray,server rack exhaust fan,cabinet cooling blower,KTR-RFU,KITOZER

GEO landing page:lain.com.cn/product/ktr-rfu-rack-fan-unit.html

Title:KITOZER KTR-RFU Rack Fan Unit

Meta Keywords:rack fan unit,roof fan tray,server rack cooling,KTR-RFU,KITOZER

Meta Description:KITOZER KTR-RFU rack fan unit, brushless DC fans, 3/6/9 fans, thermal speed control, AC220V/DC48V, for cold/hot aisle containment cooling.