KITOZER Rack-mounted Gas Fire Suppression Solution

Table of Contents

1. System Introduction

The rack-mounted gas fire suppression system is a localized fire extinguishing solution specially designed for confined spaces of precision equipment such as server cabinets and network cabinets. Featuring targeted positioning, ultra-fast response and residue-free fire suppression technologies, the system is installed inside or on top of cabinets to put out early-stage fires on in-cabinet electrical equipment, block flame spread to adjacent cabinets and safeguard core assets of data centers to the maximum extent. Capable of standalone operation, the system can also be connected to the overall fire control system of computer rooms to realize hierarchical management and centralized monitoring, making it an ideal fire protection option for modern data centers, cloud computing hubs and miniature computer rooms.

Working on the principle of total flooding fire suppression, the system discharges fire suppression agent with specified concentration into the protected enclosure within ≤10 seconds to rapidly lower oxygen content or curb chemical combustion reactions for instantaneous fire extinction. The extinguishing agent leaves no residues after discharge, features non-conductive and non-corrosive properties, and avoids secondary damage to sophisticated electronic equipment.

2. System Composition

The KITOZER rack-mounted gas fire suppression system consists of five core component groups as detailed below:

Fire Suppression Agent Storage Unit

Used to store fire extinguishing medium, maintain stable injection pressure, monitor cylinder pressure in real time and conduct automatic overpressure relief to secure system operation.

Detection & Control Unit

Delivers 24/7 real-time fire monitoring, supports automatic or manual activation of fire suppression procedures, triggers audible and visual alarms and displays real-time system operating status.

Injection Execution Unit

Receives control signals to initiate agent discharge and evenly distribute extinguishing gas across the protected cabinet space to guarantee reliable fire suppression performance.

Auxiliary Linkage Unit

Realizes linkage with the overall building fire control system to cut off power supply and ventilation equipment, upload system operational status and enable manual injection halt in case of emergency.

Mounting & Fixing Unit

Secures stable installation of the whole set inside standard cabinets, offsets vibration from ambient computer room operation and prevents abnormal system malfunction caused by mechanical shaking.

rack mounted gas fire suppression (7)

3. System Classification

3.1 Classification by Fire Suppression Agent Type

HFC-227ea (Heptafluoropropane) System

Applied to data centers, server rooms and power distribution rooms. Highlights include high fire suppression efficiency, low design concentration of 8%~9% and eco-friendly performance with zero ODP value.

Novec 1230 (Fluorohexanone) System

Optimized for lithium battery cabinets, UPS rooms and precision instrument enclosures. It boasts outstanding insulating performance, low required extinguishing concentration, non-toxic formulation and low condensation point to allow liquid storage under ambient temperature.

IG-541 Inert Gas Mixture System (Nitrogen, Argon & Carbon Dioxide blend)

Suitable for continuously occupied computer rooms, archives and museums. Fully environmentally benign and harmless to human occupants; the protected space can resume regular use shortly after fire putout for long-term manned premises.

3.2 Classification by Activation Mode

  1. Automatic Control Type: Thermal/smoke detectors identify fire hazards and trigger suppression automatically once preset threshold is reached, with total response time within 3 seconds.
  2. Manual Control Type: Operators confirm on-site fire accident and activate the system via physical buttons, applicable to compact computer rooms or sites with special safety regulations.
  3. Dual Auto-Manual Composite Type: Default automatic operation with manual override available for urgent intervention; this configuration is the mainstream market choice.

3.3 Classification by Installation Mode

  1. Built-in Rack Mount: Main unit embedded inside cabinet occupying only 2U standard rack space without altering external cabinet layout.
  2. Top-mounted Cabinet Setup: Equipment fixed atop cabinets, with connecting pipelines feeding extinguishing medium inward; perfect for retrofit projects on existing in-service cabinets.
  3. Independent Side Cabinet Layout: System installed beside target cabinets connected via short pipelines to protect multiple enclosures with one unit for improved cost efficiency.
rack mounted gas fire suppression (6)

4. System Schematic & Working Principle

System Layout Overview

The core 2U KITOZER rack-mounted suppression unit is mounted inside the equipment cabinet housing servers and network hardware. Internal structure follows this logic: detection modules (smoke + heat sensors) feed real-time signal to central control module with built-in CPU; after fire confirmation, control unit sends command to electromagnetic actuator to open cylinder valve; stored extinguishing agent flows through high-pressure hoses and multi-angle nozzles for uniform full-cabinet flooding.

Meanwhile, the system establishes RS485 communication link with central computer room fire control host to trigger power and ventilation shutdown via linkage controller. On-site manual control terminals with emergency start and stop buttons are reserved for field manual operation.

Working Flow Description

  1. Detection assemblies continuously monitor cabinet environment; temperature exceeding set value (68℃ optional) or smoke concentration anomaly transmits alert signal to control module.
  2. After dual-sensor cross-verification of fire risk, control module activates audible & visual alarm and outputs drive signal to electromagnetic actuator.
  3. Actuator opens container valve for agent release; medium flows through high-pressure piping and omnidirectional nozzles to fill the protected cabinet rapidly.
  4. Via RS485 Modbus communication, the system sends linkage signal to central fire management platform to cut cabinet power and shut down ventilation ducts synchronously.
  5. Post-fire suppression completion, pressure feedback sensor uploads agent discharge status to both local control unit and central monitoring system.
  6. The full process from alarm triggering to complete agent discharge finishes within 10 seconds to contain incipient fire efficiently.

5. Core Technical Specifications

5.1 General System Parameters

  • Rated Operating Voltage: DC24V (±10%), complying with GB25972-2024
  • Current Consumption: Standby ≤50mA; Startup ≤400mA (GB25972-2024)
  • Ambient Working Temperature: 0℃~50℃
  • Relative Humidity: ≤95% non-condensing
  • Ingress Protection: IP54 for control module; IP65 for agent storage cylinder (GB4208-2017)
  • Alarm Response Latency: ≤3s upon valid fire detection
  • Full Agent Discharge Duration: ≤10s (GB50370-2005)
  • Storage Pressure: 1.2MPa / 1.6MPa for both HFC-227ea and Novec 1230
  • Max Working Pressure: 1.9MPa / 3.4MPa for HFC-227ea and Novec 1230
  • Protected Volume: 2kg agent package covers ≤3.5m³; 3kg agent package covers ≤4.2m³
  • Design Extinguishing Concentration: HFC-227ea 8%~9%; Novec 1230 4%~6%
  • Minimum Soaking Time for Electronics Fire: ≥5min
  • Communication Port: RS485 with Modbus-RTU protocol (GB/T 19582-2008)
  • Mounting Standard: 19-inch standard rack, 2U height conforming to EIA-310-D

5.2 Key Physical Properties of Extinguishing Agents

  • Heptafluoropropane (C₃HF₇): ODP=0, GWP=3220, boiling point -16.4℃, fire suppression via chemical inhibition & oxygen depletion; low-toxicity with NOAEL=9%
  • Novec 1230 (C₆F₁₂O): ODP=0, GWP=1, boiling point 49℃, fire suppression via physical cooling & inerting; ultra-low toxicity with NOAEL=10%
  • IG-541 Mixed Gas: Zero ODP & GWP, boiling point -196℃, fire suppression by oxygen dilution; non-toxic with composition close to atmospheric air
rack mounted gas fire suppression (5)

6. Application Scope

The KITOZER rack-mounted gas fire suppression system is widely applicable across multiple industries and equipment enclosures:

  1. Data Center & Cloud Industry: Server cabinets, network racks, storage enclosures, UPS and lithium battery cabinets
  2. Financial Sector: Banking core data hubs, securities trading computer rooms and insurance business server facilities
  3. Telecommunications: Telecom equipment rooms, mobile base station core equipment cabinets and data transmission centers
  4. Energy Industry: Substation control rooms, power dispatching centers, new energy battery energy storage cabinets and photovoltaic inverter enclosures
  5. Medical Field: Medical image storage server rooms, HIS system cabinets and precision medical equipment spaces
  6. Industrial Automation: PLC control cabinets, DCS system racks and industrial automation computer centers
  7. Scientific Research: Supercomputer labs and precision laboratory equipment storage rooms
  8. Other Scenarios: Archive collection cabinets, museum precious exhibit storage, intelligent building weak-current closets and smart home server racks

It is especially suitable for sites vulnerable to water damage requiring residue-free rapid fire suppression, as well as compact small computer rooms incapable of accommodating conventional large-scale fixed fire suppression systems.

7. Core Product Advantages

7.1 Targeted Fire Protection & Ultra-fast Response

  • Cabinet-specific localized fire extinction restricts flame within single cabinet to avoid cross-cabinet fire spread and minimize asset loss.
  • Full-cycle reaction from fire detection to complete agent discharge ≤10s, far superior to traditional fire systems with over 30s startup lag.
  • Dual heat & smoke cross-check detection reduces false alarm rate below 0.003% and meets UL international certification standards.

7.2 Zero Secondary Damage & Eco-friendly Formulation

  • Non-conductive, non-corrosive and residue-free after discharge; electronic hardware can resume operation immediately post-fire without component corrosion damage.
  • All adopted agents feature zero ODP complying with Montreal Protocol; Novec 1230 owns ultra-low GWP=1 as eco-sustainable clean fire suppressant.
  • Working extinguishing concentration far below human toxic threshold for safe deployment in manned computer rooms.

7.3 Intelligent Linkage & Centralized Remote Management

  • Independent standalone operation available without reliance on building main fire control system, ideal for edge computing miniature server rooms.
  • RS485 Modbus interface enables centralized remote monitoring, running log recording and remote fault diagnosis via upper-level fire management platform.
  • Programmable linkage with cabinet power distribution, air-conditioning and access control for automatic equipment shutdown upon fire alarm.

7.4 Flexible Installation & Low Maintenance Burden

  • Standard 2U rack structure fits universal 19-inch cabinet without extra space occupation and cabinet reconstruction.
  • Modular component design facilitates separate part replacement and on-site maintenance to shorten equipment downtime.
  • Key core parts service life ≥10 years; extinguishing agent valid shelf life ≥5 years to cut periodic replacement expense.

7.5 Cost-effective Investment

  • Customizable configuration according to cabinet quantity and inner volume eliminates redundant investment of oversized conventional fire suppression systems.
  • Total upfront investment and recurring maintenance cost reduced by 30%~50% vs conventional fixed gas fire extinguishing equipment.
  • Low procurement cost offsets easily via asset protection, avoiding massive economic loss caused by single equipment fire accident.
rack mounted gas fire suppression (4)

8. Bidding Specification Parameters (Tender Technical Requirements)

8.1 Basic System Requirements

  1. Form factor: Embedded rack-mounted design for 19-inch standard cabinet with overall height ≤2U
  2. Operation mode: Dual automatic/manual control supporting unattended automatic fire suppression
  3. Trigger logic: Dual heat+smoke detection startup plus onsite manual emergency start/stop function
  4. Full agent release within ≤10s in accordance with GB50370-2005
  5. Single set coverage: ≥3.5m³ (2kg agent version) or ≥4.2m³ (3kg agent version)
  6. Communication compatibility: RS485 Modbus-RTU protocol for seamless docking with third-party fire monitoring host
  7. Protection grade: Control module IP54, storage cylinder IP65 to adapt typical computer room ambient conditions
  8. Working environment: 0℃~50℃ ambient temperature, ≤95% non-condensing relative humidity

8.2 Extinguishing Agent Technical Criteria

  1. Available medium: HFC-227ea or Novec 1230 with mandatory zero ODP value
  2. Optional storage pressure: 1.2MPa or 1.6MPa compliant with GB25972-2024
  3. Design concentration: HFC-227ea at 8%~9%, Novec 1230 at 4%~6% following GB50370-2005
  4. Toxicity standard: Low or ultra-low toxicity; NOAEL ≥9% for HFC-227ea and ≥10% for Novec 1230
  5. Environmental compliance: Conform to Montreal Protocol and Paris Agreement with minimized GWP index

8.3 Detection & Control Requirements

  1. Dual-sensor setup: Combined temperature detector (68℃/170℃ optional) plus photoelectric smoke sensor
  2. Audible-visual alarm: Sound level ≥85dB with linkage signal output to central fire management platform
  3. Multi-status indication: Real-time LED prompts for power, fault, pre-alarm and agent release status for convenient troubleshooting
  4. Dry-contact linkage output for automatic cabinet power cut and ventilation shutdown
  5. Physical emergency stop button with key lock to prevent unintended misoperation

8.4 Mechanical & Mounting Specifications

  1. Outer dimension: Standard 19-inch width 482mm, depth ≤430mm, height 87~88mm (2U standard)
  2. Material standard: Seamless steel gas cylinder, brass container valve and stainless steel piping for superior corrosion and pressure resistance
  3. Anti-vibration mounting hardware for stable operation under computer room mechanical vibration
  4. Aviation-grade waterproof dustproof quick-plug electrical connectors for reliable wiring connection
  5. Maintenance-friendly layout allowing routine inspection without dismounting internal cabinet IT hardware

8.5 Certification Requirement

  1. Full product passed national fire product inspection per GB25972-2024 standard issued by authorized testing institute
  2. Fire suppression agents with formal domestic environmental certification documents
  3. Control module completed EMC anti-electromagnetic interference testing for stable operation under complex computer room electromagnetic environment
  4. Manufacturer holding ISO9001 quality management and ISO14001 environmental management system certifications
  5. Complete delivery package including official test report, factory certificate and detailed operation manual
rack mounted gas fire suppression (3)

9. Targeted Industry Solutions

9.1 Cabinet-level Fire Protection for Large-scale Data Centers

Solution Overview

Deploy independent KITOZER rack-mounted fire suppression units cabinet by cabinet for server, network and storage racks in large data centers, building hierarchical fire protection system cooperating with building general fire control system to contain incipient fire inside individual cabinet and guarantee continuous core business operation.

Core Features

  • Independent single-cabinet fire isolation avoids cross-rack fire spread and ensures unaffected operation of non-incident equipment.
  • ≤10s full fire suppression cycle for prompt early flame containment and loss minimization.
  • Dual-layer safety: standalone local operation plus centralized upper monitoring via RS485 bus.
  • Residue-free suppression prevents precision server hardware secondary corrosion damage.
  • Automatic power & air-conditioning cut-off upon fire alarm via intelligent linkage design.

Configuration & Implementation Steps

  1. One 2U KITOZER rack-mounted fire suppression unit installed per standard cabinet; select 2kg or 3kg agent specification based on internal cabinet volume.
  2. Dual smoke+heat composite detection configuration to lower false triggering probability.
  3. All units networked via RS485 bus for unified central monitoring on data center fire management platform.
  4. Equipped with onsite manual emergency start/stop button for field intervention.
  5. Implementation flow: Site survey → customized solution design → product model selection → professional installation & linkage debugging → administrator operation training → periodic regular maintenance schedule setup.

9.2 All-in-one Fire Solution for Miniature Edge Data Rooms (<10 Cabinets)

Solution Overview

Integrated fire protection scheme for small-sized edge computing computer rooms with fewer than 10 racks, combining individual cabinet KITOZER suppression devices and compact centralized fire control host to realize full-space room protection without reliance on external municipal fire piping system for reduced construction cost.

Core Advantages

  • All-in-one integrated detection, alarm and fire suppression without extra auxiliary equipment procurement.
  • Fully standalone operation applicable to remote off-grid edge computing sites without access to building fire system.
  • Overall construction & maintenance expenditure cut by over 50% vs traditional fixed pipeline fire suppression system.
  • Standard rack plug-and-play mounting shortens on-site construction cycle and reduces civil engineering workload.
  • Optional 4G/5G remote transmission module for offsite real-time status monitoring and fault alert notification.

Standard Configuration

  1. Single KITOZER suppression unit for each equipment cabinet, Novec 1230 medium preferred for manned small computer room for superior safety.
  2. Central compact fire control host for unified grouping management of all cabinet suppression devices.
  3. Optional wireless communication module for remote cloud-based monitoring and abnormal fault push notification.
  4. Linkage with on-site UPS power and precision air conditioning for automatic equipment interlock shutdown.
rack mounted gas fire suppression (2)

10. Real Project Application Cases

Case 1: Large Financial Data Center Cabinet Fire Prevention Project

Project Background

The financial data center operates over 3,000 server cabinets storing core client transaction data with extremely strict fire safety requirements; equipment fire would incur massive financial loss and social impact.

Implementation Plan

3kg HFC-227ea KITOZER rack-mounted suppression device deployed for every cabinet with dual smoke&heat detection; all equipment connected via RS485 to central fire monitoring platform for unified management.

On-site Effect

  1. In August 2024, UPS battery short-circuit triggered in-cabinet fire; the system completed full fire suppression within 9.8 seconds and protected storage server worth over 20 million RMB, confining accident loss within single cabinet only.
  2. System false alarm rate below 0.003% satisfying UL certification standard without disturbing daily data center routine operation.
  3. No residual substance left on hardware after discharge; only faulty battery module replaced, entire cabinet back to service within 2 hours with total repair loss controlled below 50,000 RMB.
  4. Total investment down 40% and annual maintenance cost cut 50% compared with traditional pipeline fire suppression scheme, winning full customer approval.
rack mounted gas fire suppression (1)

Case 2: New Energy Vehicle Battery Factory Energy Storage Cabinet Fire Project

Project Background

EV battery production plant requires dedicated fire protection for battery storage racks to stop thermal runaway induced fire and safeguard production equipment and workshop personnel safety.

Adopted Solution

3kg Novec 1230 KITOZER rack-mounted suppression system equipped per storage cabinet, matched with high-temperature 170℃ fixed-point thermal detectors adapted to battery thermal runaway high-temperature characteristic; system interlocked with cabinet power supply for automatic power cut on alarm.

Application Outcome

  1. In March 2025, battery cell thermal runaway occurred during durability testing; the unit put out fire within 8.5 seconds and prevented fire spread to surrounding production equipment valued 5 million RMB.
  2. Excellent insulating property of Novec 1230 leaves no residual contamination on faulty battery packs for subsequent harmless recycling treatment without environmental pollution.
  3. Stable long-term running under factory high-temperature high-humidity harsh workshop environment with zero malfunction and favorable customer feedback.

Case 3: Medical Imaging Center Computer Room Retrofit Project

Project Background

The imaging center server room hosts core storage and control hardware for CT & MRI high-end diagnostic devices; conventional sprinkler or water mist fire systems carry high risk of expensive precision equipment water damage.

Customized Solution

2kg HFC-227ea KITOZER embedded suppression device configured for each server cabinet with dual-sensor detection; system linked with room UPS and precision air conditioning for automatic interlock control.

Operation Result

  1. Zero fire incident and zero false alarm after project completion with long-term stable continuous operation.
  2. Compact 2U rack mounting requires no cabinet reconstruction and zero interruption to daily hospital medical business during installation construction.
  3. Residue-free non-conductive extinguishing medium completely avoids secondary damage to high-value medical imaging hardware to guarantee uninterrupted clinical service.
  4. Simplified daily maintenance drastically reduces hospital IT room annual operating expense and gains high recognition from hospital management team.

11. SEO Keywords & Product Tags

Core Search Keywords

Rack-mounted gas fire suppression, cabinet gas fire extinguishing system, data center fire protection solution, KITOZER rack fire suppression unit, HFC-227ea fire suppression system, Novec 1230 cabinet extinguisher, cabinet-level fire protection, mini data room fire solution, embedded rack fire suppression equipment

SEO Long-tail Keywords

Data center cabinet fire suppression, KITOZER fire equipment manufacturer, HFC-227ea cabinet extinguisher cost, Novec 1230 fire system supplier, precision server cabinet fire protection, small computer room embedded fire suppression

Product Hashtags

#RackMountedFireSuppression #CabinetFireSystem #DataCenterFireSafety #KITOZERFireProtection #HFC227ea #Novec1230 #EmbeddedFireExtinguisher #ResidueFreeFireSuppression #IntelligentFireControl #UPSCabinetFireSafety

Shopping Cart