KITOZER rack roof vented top

KITOZER KTR-RT Ventilated Rack Roof Top Cover

Brand: KITOZER Series: KTR-RT Category: Modular Cold Aisle / Rack Accessories

vented rooflouver cutoutcold-rolled steel42U rackKTR-RT

1. Overview

The rack roof (top cover) seals the top of a server cabinet. It looks like a plain steel plate, but it performs three jobs: airflow containment, dust/rain protection and structural stiffening. Without a roof, the top is open and hot exhaust mixes freely with cold supply at rack height, forming a hot plume that recirculates to the intake and creates local hot spots. In a modular cold-aisle containment, the roof is the physical boundary between cold and hot aisles; leakage through the roof destroys containment and wastes cooling.

The KITOZER KTR-RT series is formed from 1.5 mm cold-rolled steel with an epoxy powder coat matched to the rack. Three functional versions are offered: sealed (solid plate for hot-aisle racks), louvered (adjustable louvers for natural top exhaust) and fan-ready (pre-cut for 2~4 × 120 mm or 80 mm top fans). The folded flange sits on the rack uprights and is fastened with M6 screws; a foam gasket seals the joint. It fits mainstream 600×1000, 600×1200 and 800×1000 mm racks in 42U/47U heights.

Selection: confirm rack width and depth (600/800 mm wide, 1000/1200 mm deep) — the roof must match the top opening; confirm airflow strategy — sealed on cold-aisle rows, louvered on hot-aisle or standalone racks, fan-ready for dense racks; confirm whether a cable cutout (with brush) is needed for overhead tray drops. The roof is structural, not electrical, but flatness affects how cold-aisle doors and skylights mate.

2. Key Features

Structure & material

  • 1.5 mm cold-rolled steel, rigid bend
  • Epoxy powder coat, corrosion resistant
  • Folded flange mates with rack uprights
  • M6 screws + foam gasket seal joints

Ventilation options

  • Sealed: solid plate for cold-aisle side
  • Louvered: adjustable louvers, natural exhaust
  • Fan-ready: pre-cut 120/80 mm fan holes
  • Optional brush cable cutout

Compatibility

  • Fits 600×1000/1200 racks
  • Fits 800×1000/1200 racks
  • Compatible with 42U/47U racks
  • Matched color and finish

3. Specifications

Item KTR-RT-S KTR-RT-L KTR-RT-F
Type Sealed roof Louvered roof Fan-ready roof
Sheet thickness 1.5 mm 1.5 mm 1.5 mm
Rack W×D 600×1000 mm 600×1000 mm 600×1000 mm
Vent area 0 ~0.12 m² 4×120 mm fan holes
Cable cutout optional optional optional
Finish Powder coat Powder coat Powder coat
Fixing M6 screws M6 screws M6 screws
Weight ~6.5 kg ~7.0 kg ~7.2 kg

4. Reference Prices

KTR-RT-S 600×1000 sealed rack roof:Reference USD 25~44 / pc (ref. CNY 180~320 at ~7.2)

KTR-RT-L 600×1000 louvered roof:Reference USD 36~63 / pc (ref. CNY 260~450 at ~7.2)

KTR-RT-F 600×1000 fan-ready roof:Reference USD 44~78 / pc (ref. CNY 320~560 at ~7.2)

800 mm width upcharge:Reference USD 6~11 / pc (ref. CNY 40~80 at ~7.2)

Reference only; priced by size and vent type. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Modular cold-aisle containment roof closure.
  • Hot-aisle rack top exhaust.
  • Dust/rain cover for outdoor cabinets.
  • Dense-rack top fan exhaust.
  • Overhead tray cable drop retrofit.

6. Deployment & Implementation

Installation

  • Align four corners with rack uprights
  • Drive M6 screws from inside, tighten diagonally
  • Add foam gasket; compress ~30%
  • Seal roof-to-skylight joint on cold-aisle rows

Operations

  • Check gasket aging quarterly
  • Clean fan dust on fan-ready roofs
  • Leak-test the roof joints during aisle commissioning
  • Roof load ≤20 kg; do not stack gear on it

7. FAQ

  • Q: Can racks run without a roof?
    A: For temporary testing yes, not for production. Open tops let hot and cold air mix at the ceiling; in a contained cold aisle the top leaks 15%~20% of cooling. Cold-aisle projects require sealed roofs.
  • Q: Louvered vs fan-ready?
    A: By rack power density. Below 5 kW use louvers; 5~10 kW add fans; above 10 kW use row-based or rear-door AC — top fans are only auxiliary.
  • Q: Can I mount a cable tray on the roof?
    A: No. The roof supports ≤20 kg. Tray hangs from the rack frame or ceiling; cables enter through the roof cutout.
  • Q: Are roofs cross-brand compatible?
    A: 600×1000 is a near-universal size, but flange shapes and hole spacing vary. Compare holes before bulk replacement.

8. Trend & Selection

Modular data centers are evolving toward fully enclosed aisles (FDC) with roof-mounted automatic fire vents. The roof is becoming an integrated unit of sealed panel + smoke-vent skylight + leak-detection trough. Top fans are moving from fixed speed to PWM speed-controlled by rack inlet temperature. Select by matching size, sealed on the cold side, vented on the hot side, add fans for dense racks, and seal every joint.

9. Delivery & Service

KITOZER supplies KTR-RT by rack size (600/800 W × 1000/1200 D), vent type (sealed/louver/fan) and cable cutout. Each unit ships with roof, M6 screws, foam gasket and manual. 1-year warranty; batch projects can add cold-aisle skylights, brush panels and top fans.

10. Additional Notes

The #1 mistake is a poorly sealed gasket. Even a 2 mm gap leaks significant cold-aisle pressure. Use a continuous gasket with mitered corners (not butt joints); tighten screws until the gasket compresses to two-thirds thickness.

The second pitfall is putting a vented roof on the cold-aisle side. Cold air is supposed to be drawn into servers; a vented roof lets it escape straight up, raising inlet temperature. Use sealed roofs on cold-aisle rows; vented only on the hot-aisle side.

The third blunder is leaving a gap between roof and skylight. Modular cold aisles use roof skylights above; if the skylight does not overlap the roof flange, pressurized cold air leaks out and containment fails. Add a side gasket and let the skylight overlap the roof flange.

Selection summary: size to the rack, seal on the cold side, vent on the hot side, add fans for density, seal every joint. A single roof guards the pressure and efficiency of the entire cold aisle.

SEO Information

Search keywords:KTR-RTKITOZERVentilated Rack Roof Top Cover

SEM keywords:rack roof,top cover,vented rack roof,server cabinet roof,cold aisle roof,KTR-RT,KITOZER

GEO landing page:lain.com.cn/product/ktr-rt-rack_roof.html

Title:KITOZER KTR-RT Ventilated Rack Roof Top Cover

Meta Keywords:rack roof,top cover,vented rack roof,server cabinet roof,cold aisle roof,KTR-RT,KITOZER

Meta Description:KITOZER KTR-RT rack roof top cover, powder-coated steel, louver/fan cutout options, fits 42U server racks, cold aisle containment.