KITOZER
KITOZER

KITOZER Reactive Compensation Cabinet: 400V 300kvar LV PFC

The KITOZER 400V reactive compensation cabinet is a low-voltage power factor correction assembly installed on the secondary side of distribution transformers to improve power factor, reduce line losses, and avoid penalty tariffs. The cabinet contains stepped capacitor banks switched by contactors or thyristor switches, a power factor controller, and protection devices. KITOZER supplies standard and detuned versions depending on the harmonic environment, and the cabinet can be built with automatic or manual stepping. It is a standard feature of commercial building substations, industrial plants, and data center low-voltage switchboards.

Technical Specifications

Rated voltage 400V three phase, rated frequency 50Hz, total reactive power 300kvar in steps of 50kvar, dry-type self-healing capacitors with overpressure disconnector, detuning reactor at 7% or 14% for harmonics, switching by AC contactor or thyristor switch for fast response. Power factor controller measures power factor and switches stages. Protection: main circuit breaker, branch fuses or MCBs, surge protection device. IP30 or IP42 cabinet, forced ventilation optional. Conforms to IEC 60831 and GB standards. Communication: RS485 Modbus optional.

Applications

The KITOZER 400V compensation cabinet is connected to the low-voltage main switchboard of industrial plants, shopping malls, office towers, hospitals, and data centers. It compensates reactive power drawn by induction motors, HVAC chillers, welders, and discharge lighting. Where the utility imposes power factor penalties, the cabinet raises the power factor to 0.95 or above, eliminating penalty charges and releasing transformer capacity. In plants with many VFDs and UPS systems, the detuned version prevents resonance and protects the capacitors from harmonic overcurrent.

Thyristor-switched versions are used where load changes rapidly, such as welding shops or elevator banks, because contactor-switched banks cannot respond fast enough. The cabinet is often split into several smaller banks distributed across the low-voltage switchboard to reduce cable runs. In data centers, compensation cabinets work together with UPS systems and active filters to maintain clean power at the transformer secondary.

Key Advantages

Self-healing capacitors isolate internal breakdown and restore operation automatically, improving reliability compared with old oil-filled units. The overpressure disconnector permanently disconnects a faulty capacitor in case of severe internal fault, preventing cabinet fire. The power factor controller automates stepping based on real demand, so the cabinet matches compensation to load without manual adjustment. Detuned reactors block harmonic resonance and extend capacitor life in nonlinear-load environments.

KITOZER builds the cabinet as a factory-tested assembly with prewired controllers, contactors, and protection, reducing site commissioning time. Standard dimensions allow integration into existing switchroom layouts. Modular capacitor blocks allow replacement without disconnecting the main busbar. Remote monitoring via Modbus integrates the cabinet into energy management and DCIM platforms.

Installation and Maintenance

Locate the cabinet close to the main LV switchboard to minimize cable length, because long cables add inductance and reduce compensation effectiveness. Connect the earthing conductor to the cabinet earth bar and verify tightness of main busbar connections. Set the controller target power factor (typically 0.98) and step delay, and verify that each stage switches in and out correctly during commissioning.

After switching off, wait for the capacitor discharge time before opening the door. Inspect capacitors annually for bulging or leakage, check contactor contacts, and measure capacitor capacitance. Clean filters and fans in ventilated cabinets. If the controller shows repeated overcompensation or stage hunting, recalibrate current transformer connections and controller settings. Keep spare capacitor blocks of the same rating on site for quick replacement.

Price

From $4,200/pc. Contact +86 13922289957 for LV compensation cabinet sizing.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com

Scroll to Top