KITOZER 30kW rear-door heat exchanger mounts in place of the standard rear door on a server rack, capturing hot exhaust air before it enters the hot aisle. Water flows through a coil behind the perforated door, removing up to 30kW of heat directly from rack exhaust with no added fans or noise. This passive design is the most efficient way to cool dense racks because IT server fans push air through the coil, eliminating the need for facility-side fans. The unit uses a water or glycol loop connected to a dry cooler or building chilled water system, and it leaves the rack footprint unchanged.
Technical Specifications
Heat rejection 30kW sensible, water flow 5.4 cubic meters per hour at 18/23 degrees C supply/return, water connection DN20 quick coupling, coil aluminum fins with copper tubes, rack dimensions 600 millimeters wide by 1,200 millimeters deep by 2,000 millimeters high, weight about 85kg, pressure rating 10 bar, differential pressure across coil below 100 Pa at design airflow, leak detection sensor included, supply voltage 230V for leak detector, color status LED, CE certified.
Application Scenarios
Rear-door heat exchangers are used in high-density compute clusters, GPU racks, storage arrays, and edge colocation halls where rack density reaches 15 to 30kW. They are ideal for retrofit projects where raising overall cooling capacity would require a full plant upgrade. Multiple rear-door units connect to a common water loop, and they work equally well in hot-aisle or cold-aisle containment.
Advantages and Features
Passive operation means zero added fan energy and zero added noise. Warm water supply enables free cooling for most of the year in temperate climates. Quick-disconnect couplings allow door removal for rack maintenance without draining the loop. Integrated leak sensing protects rack contents. The door fits standard 19-inch rack frames, so no rack replacement is needed.
Installation and Maintenance Recommendations
Install supply and return hoses with isolation valves near the rack. Use a glycol mix appropriate to the site winter temperature. Balance water flow across all doors. Confirm rack server fans can overcome coil static pressure. Maintenance is minimal: inspect hoses annually, clean coil fins with low-pressure air, and test the leak sensor. Keep spare hoses and couplings on site.
Price
From $4,980 per door. Contact KITOZER for water loop design and quick coupling selection.