I. System Introduction
1.1 Definition & Core Value
Room-level precision air conditioners are dedicated HVAC systems designed for computer rooms, data centers, server rooms and other scenarios requiring stringent ambient temperature and humidity control. They deliver constant temperature and humidity environments with a temperature control accuracy of ±0.5℃ and humidity control accuracy of ±3%RH, ensuring 24/7/365 stable operation of electronic equipment.
Compared with conventional comfort air conditioners, room-level precision air conditioners feature large air volume, small enthalpy difference and high sensible heat ratio (≥0.9). They effectively resolve high-density heat dissipation of room equipment, eliminate local hotspots, reduce equipment failure rates and extend hardware service life.
1.2 Working Principle
Adopting the vapor-compression refrigeration cycle, the system transfers heat through four core components: compressor, condenser, expansion valve and evaporator. Integrated with humidification, heating, dehumidification and air filtration modules, together with an intelligent control system, it achieves precise regulation of computer room environments:
1. Refrigeration Cycle: The compressor compresses low-temperature and low-pressure gaseous refrigerant into high-temperature and high-pressure gaseous refrigerant. The refrigerant dissipates heat and liquefies in the condenser, undergoes throttling and pressure reduction via the electronic expansion valve, and absorbs heat during evaporation in the evaporator to lower air temperature.
2. Air Handling: The fan delivers room air to the evaporator for cooling. The air is adjusted to the target humidity and temperature by humidifiers or heaters, purified by high-efficiency filters, and then supplied back to the computer room.
3. Intelligent Control: Equipped with a PID control algorithm, the system monitors real-time temperature and humidity data and dynamically adjusts the operation status of functional modules to keep environmental parameters within the preset range.
1.3 Application Background
With the rapid development of the digital economy, data centers, cloud computing and artificial intelligence industries impose increasingly strict requirements on computer room environments. In accordance with the industry standard GB 50174-2017 Code for Design of Data Centers, the ambient temperature of Class A data centers shall be controlled at 23±1℃ and relative humidity at 40%–60%RH. As a core part of computer room infrastructure, room-level precision air conditioners directly determine data center reliability, availability and PUE (Power Usage Effectiveness), serving as a key guarantee for business continuity.

II. System Composition
The KITOZER room-level precision air conditioning system consists of six core units that work collaboratively to realize all-round and precise control of computer room environments:
| System Unit | Core Components | Functional Description |
| Refrigeration Cycle Unit | Variable-frequency compressor, high-efficiency evaporator, condenser, electronic expansion valve, refrigerant pipeline | Realizes heat transfer and provides cooling capacity to meet computer room heat dissipation requirements |
| Air Handling Unit | EC energy-saving fan, G4/F7 high-efficiency filter, air duct system | Provides high-volume air circulation, purifies air, eliminates local hotspots and ensures uniform airflow distribution |
| Temperature & Humidity Regulation Unit | Electrode humidifier, PTC heater, dehumidification system | Implements humidification, heating and dehumidification functions for precise room temperature and humidity control |
| Intelligent Control Unit | Microprocessor, touchscreen controller, sensor array, communication module | Monitors real-time environmental parameters, intelligently adjusts unit operation, and supports remote monitoring and fault alarming |
| Safety Protection Unit | High-pressure protection, low-pressure protection, over-current protection, overheat protection, anti-freezing protection, water leakage detection | Guarantees safe and stable system operation and prevents equipment damage and room accidents |
| Auxiliary Unit | Condensate drainage system, vibration damping device, noise reduction structure | Improves system reliability and environmental friendliness |

III. System Classification
KITOZER room-level precision air conditioners provide diversified product series under multiple classification criteria to meet the demands of various computer rooms.
3.1 Classification by Cooling Method
| Type | Core Features | Applicable Scenarios |
| Air-cooled Type | Simple structure, easy installation and maintenance, no cooling tower required; heat exchange with ambient air via outdoor unit | Small and medium-sized computer rooms (total cooling capacity ≤200kW) and sites without cooling water systems |
| Water-cooled Type | High heat dissipation efficiency, stable operation and large cooling capacity; heat exchange between cooling water and refrigerant | Large-scale data centers, park-level computer rooms and scenarios requiring high heat dissipation efficiency |
| Chilled Water Type | Adopts chilled water as cold source with high system EER; compatible with centralized chilled water systems | Large-scale data centers requiring integration with building cold source systems |
| Glycol-cooled Type | Operable in wide temperature environments (-45℃~45℃), ideal for free cooling scenarios | Data centers in cold regions and scenarios pursuing high energy-saving performance |
| Dual-source Cooling Type | Equipped with two independent cooling systems (e.g., direct expansion + chilled water); redundant design for ultra-high reliability | Core business computer rooms with extremely high availability requirements |
3.2 Classification by Air Supply Mode
| Type | Air Supply Features | Applicable Scenarios |
| Top Air Supply | Air supplied from ceiling and returned from floor with uniform airflow distribution | Open-style computer rooms without hot and cold aisle isolation |
| Bottom Air Supply | Air supplied from raised floor and returned from top; natural circulation formed by air density difference | Computer rooms with raised floors and hot/cold aisle isolation design |
| Horizontal Air Supply | Air supplied from cabinet side, suitable for high-density cabinet layout | Blade server rooms and high-density computing environments |
3.3 Classification by Capacity
| Capacity Range | Model Series | Applicable Room Area |
| 7.5kW~25kW | KITOZER-RC075~RC250 | Small rooms: 30㎡~100㎡ |
| 30kW~60kW | KITOZER-RC300~RC600 | Medium rooms: 100㎡~300㎡ |
| 65kW~120kW | KITOZER-RC650~RC1200 | Large rooms: 300㎡~800㎡ |
| 125kW~200kW | KITOZER-RC1250~RC2000 | Super-large rooms: above 800㎡ |

IV. System Configuration List (KITOZER Brand)
4.1 Standard Configuration List
| No. | Equipment Name | Model | Brand | Quantity | Functional Description |
| 1 | Room-level Precision Air Conditioner Indoor Unit | KITOZER-RC Series | KITOZER | As required | Provides cooling, humidification, heating, dehumidification and air filtration functions |
| 2 | Air Conditioner Outdoor Unit | Matching KITOZER-RC Series | KITOZER | 1:1 matching with indoor unit | Air-cooled heat dissipation equipment linked with indoor refrigeration system |
| 3 | Temperature & Humidity Sensor | KITOZER-TS-01 | KITOZER | 1 set per unit | Real-time room temperature and humidity monitoring with accuracy ±0.3℃/±2%RH |
| 4 | Air Quality Sensor | KITOZER-AS-01 | KITOZER | 1 set per unit | Monitors indoor air quality, detects dust and harmful gas |
| 5 | Intelligent Controller | KITOZER-CC-03 | KITOZER | 1 set per unit | Supports local and remote control, with fault alarm and data recording functions |
| 6 | High-efficiency Air Filter | KITOZER-FG-07 | KITOZER | 2 sets per unit | G4/F7 grade filtration with efficiency ≥95%, replaceable design |
| 7 | Condensate Drainage Pump | KITOZER-DP-02 | KITOZER | 1 set per unit | Automatic condensate drainage with lifting height ≥5m |
| 8 | Communication Module | KITOZER-CM-04 | KITOZER | 1 set per unit | Supports Modbus, SNMP and BACnet protocols for remote monitoring access |
4.2 Optional Configuration List
| No. | Equipment Name | Model | Brand | Quantity | Functional Description |
| 1 | Dual-source Cooling Module | KITOZER-DS-01 | KITOZER | Optional | Adds an independent cooling system to improve system reliability |
| 2 | Free Cooling Module | KITOZER-NC-02 | KITOZER | Optional | Utilizes low-temperature outdoor air for cooling to reduce energy consumption |
| 3 | Humidification Capacity Expansion Module | KITOZER-HM-03 | KITOZER | Optional | Enhances humidification capacity for computer rooms in dry areas |
| 4 | Heating Capacity Expansion Module | KITOZER-HT-04 | KITOZER | Optional | Enhances heating capacity for computer rooms in cold regions |
| 5 | Redundant Controller | KITOZER-RC-05 | KITOZER | Optional | Dual-controller design eliminates single-point failure risks |
| 6 | Remote Monitoring Software | KITOZER-MON-06 | KITOZER | 1 set | Supports centralized monitoring and data visual analysis for multiple units |
| 7 | Water Leakage Detection System | KITOZER-LD-07 | KITOZER | Optional | Real-time water leakage monitoring and timely alarm notification |
| 8 | Airflow Optimization Module | KITOZER-AO-08 | KITOZER | Optional | Includes deflectors and plenum chambers to optimize indoor airflow distribution |

V. System Schematic Diagram
5.1 Air-cooled Precision Air Conditioning System Principle
5.2 Water-cooled Precision Air Conditioning System Principle
5.3 Control System Principle
VI. Product Technical Parameters
6.1 Core Technical Parameters of KITOZER-RC Series
| Parameter Item | Technical Index | Remarks |
| Cooling Capacity Range | 7.5kW~200kW | Covers computer rooms of all scales |
| Temperature Control Range | 18℃~27℃ | Compliant with GB 50174-2017 |
| Temperature Control Accuracy | ±0.5℃ | PID intelligent control algorithm |
| Humidity Control Range | 40%RH~60%RH | Compliant with GB 50174-2017 |
| Humidity Control Accuracy | ±3%RH | Electrode humidification for precise humidity control |
| Sensible Heat Ratio (SHR) | ≥0.9 | Optimized for high-density room heat dissipation |
| Circulating Air Volume | 2000m³/h~60000m³/h | High-volume design eliminates local hotspots |
| Energy Efficiency Ratio (EER) | ≥3.0 | Level 1 energy efficiency, high energy saving |
| Compressor Type | Full DC variable-frequency scroll compressor | High efficiency, stability and low noise |
| Fan Type | EC energy-saving fan | Stepless speed regulation, over 30% energy saving |
| Humidifier Type | Electrode / Ultrasonic type | Optional configuration |
| Heater Type | PTC heater | Safe, efficient and flameless |
| Filter Grade | G4/F7 | Upgradable to H13 |
| Operating Noise | ≤55dB(A) | Low-noise design for room environment |
| Operating Ambient Temperature | -45℃~45℃ | Wide-temperature operation for extreme environments |
| Communication Protocol | Modbus, SNMP, BACnet | Supports remote monitoring and BAS integration |
| Protection Grade | IP54 | Dustproof and waterproof for room scenarios |
| Power Supply | 380V/50Hz | Three-phase five-wire system |
6.2 Detailed Parameters of Each Model
| Model | Cooling Capacity | Air Volume | SHR | Compressor Power | Fan Power | Humidification Capacity | Heating Capacity | Dimension (W×D×H) |
| KITOZER-RC075 | 7.5kW | 2000m³/h | 0.92 | 2.5kW | 0.8kW | 3kg/h | 3kW | 600×800×1900mm |
| KITOZER-RC125 | 12.5kW | 3500m³/h | 0.92 | 4.0kW | 1.2kW | 5kg/h | 5kW | 800×850×1900mm |
| KITOZER-RC250 | 25kW | 7000m³/h | 0.93 | 8.0kW | 2.0kW | 8kg/h | 8kW | 1000×850×1900mm |
| KITOZER-RC300 | 30kW | 9000m³/h | 0.93 | 9.5kW | 2.5kW | 10kg/h | 10kW | 1200×850×1900mm |
| KITOZER-RC600 | 60kW | 18000m³/h | 0.94 | 19.0kW | 5.0kW | 15kg/h | 15kW | 1400×1000×2100mm |
| KITOZER-RC1200 | 120kW | 36000m³/h | 0.94 | 38.0kW | 10.0kW | 25kg/h | 25kW | 1800×1000×2100mm |
| KITOZER-RC2000 | 200kW | 60000m³/h | 0.95 | 65.0kW | 16.0kW | 40kg/h | 40kW | 2400×1200×2200mm |

VII. Application Scope
KITOZER room-level precision air conditioners are widely applied in scenarios requiring strict ambient temperature and humidity control:
7.1 Data Center & IT Computer Rooms
- Internet Data Center (IDC)
- Cloud Computing Center
- Enterprise Server Room
- Financial Institution Data Center
- Operator Core Computer Room
7.2 Communication & Network Facilities
- Mobile/Unicom/Telecom Base Station Rooms
- Network Switching Center
- Communication Equipment Room
- Satellite Ground Station
7.3 Industry & Manufacturing
- Precision Electronic Manufacturing Workshop
- Semiconductor Cleanroom
- Industrial Automation Control Room
- Power Dispatching Center
- Petrochemical Data Room
7.4 Medical & Scientific Research Institutions
- Medical Imaging Center (MRI/CT)
- Laboratory Environment
- Biopharmaceutical Cleanroom
- Gene Sequencing Center
- Hospital Information Center
7.5 Other Special Scenarios
- Museum Cultural Relics Warehouse
- Archives
- Financial Bill Storage Room
- Military Command Center
- Aerospace Control Center
VIII. Product Advantages
8.1 Precise Control & High Stability
- Ultra-high control accuracy of ±0.5℃ for temperature and ±3%RH for humidity, far exceeding conventional air conditioners
- High sensible heat ratio (≥0.9) design tailored for high-density heat dissipation of computer room equipment
- Large-volume air circulation eliminates local hotspots, ensuring vertical temperature difference ≤2℃ and horizontal temperature difference ≤1℃ in the room
- Full DC variable-frequency technology quickly responds to environmental changes and avoids excessive temperature fluctuation
8.2 High Energy Efficiency & Low O&M Cost
- Level 1 energy efficiency (EER≥3.0), saving over 30% energy compared with ordinary air conditioners
- EC energy-saving fan with stepless speed regulation automatically adjusts airflow based on actual load
- Variable-frequency compressor dynamically adjusts output power according to cooling demand to avoid frequent start-stop operation
- Supports free cooling function utilizing low-temperature outdoor air to reduce energy consumption
- Intelligent control algorithm optimizes operating parameters to achieve optimal energy efficiency ratio
8.3 Intelligent Management & Remote Monitoring
- 7-inch color touchscreen with intuitive operation and real-time system status display
- Compatible with Modbus, SNMP, BACnet and other protocols for integration with third-party monitoring systems
- Dedicated remote monitoring software supports centralized management and visual data analysis for multiple units
- Automatic fault alarm with SMS/email notification for rapid maintenance response
- Historical data recording enables operating status traceability for system optimization
8.4 High Safety & Long Service Life
- Multi-level safety protection: high/low pressure protection, over-current/overheat protection, anti-freezing protection, water leakage detection
- Full metal enclosure with IP54 dustproof and waterproof grade suitable for computer room environments
- Key components adopt internationally renowned brands to ensure stable system operation
- Modular design facilitates quick and convenient maintenance and component replacement
- MTBF (Mean Time Between Failures) ≥80,000 hours with a service life of up to 15 years
8.5 Flexible Adaptation & Customization
- Multiple cooling modes optional: air-cooled, water-cooled, chilled water, glycol-cooled, dual-source cooling
- Multiple air supply modes optional: top, bottom and horizontal air supply
- Wide cooling capacity range (7.5kW~200kW) adapting to computer rooms of all scales
- Customizable functional modules including free cooling, dual-source cooling and redundant design
- Compatible with hot/cold aisle isolation technology to further improve cooling efficiency
IX. Bid Technical Parameters
9.1 Core Technical Requirements
- Cooling Capacity: ≥[XX]kW (filled per project requirements)
- Temperature Control Accuracy: ±0.5℃, temperature fluctuation ≤±1℃ (based on 23℃ benchmark)
- Humidity Control Accuracy: ±3%RH, stable relative humidity maintained within 40%–60%
- Sensible Heat Ratio: ≥0.9, specially designed for computer room equipment heat dissipation
- Energy Efficiency Ratio: EER≥3.0, compliant with Level 1 energy efficiency standard
- Compressor: Full DC variable-frequency scroll compressor of internationally renowned brand
- Fan: EC energy-saving fan with stepless speed regulation and over 30% energy saving
- Filter Grade: ≥G4/F7, upgradable to H13
- Operating Noise: ≤55dB(A) for indoor room environments
- Operating Temperature Range: -45℃~45℃ wide-temperature stable operation
- Communication Protocol: Supports Modbus, SNMP, BACnet and other mainstream protocols
- Protection Grade: ≥IP54 dustproof and waterproof
9.2 System Configuration Requirements
- Cooling Mode: Air-cooled / Water-cooled / Chilled Water / Glycol-cooled / Dual-source (selected per project)
- Air Supply Mode: Top / Bottom / Horizontal air supply (matched with room layout)
- Control System: 7-inch color touchscreen supporting local and remote control
- Safety Protection: Full protection functions including high/low pressure, over-current, overheat, anti-freezing and water leakage detection
- Redundant Design: Redundant configuration available for key components such as compressors, fans and controllers
- Free Cooling: Supports free cooling with outdoor low-temperature air
- Remote Monitoring: Compatible with remote monitoring software and third-party management systems
9.3 Brand & Service Requirements
- Brand Qualification: KITOZER with ISO9001 quality management system and ISO14001 environmental management system certifications
- Product Certification: Possesses 3C certification, energy-saving certification and official product test reports
- Technical Service: 24-hour technical support and 48-hour on-site service response
- Warranty Policy: 2-year full-unit warranty and 5-year compressor exclusive warranty
- Technical Training: Free professional training for system operation and maintenance
X. Product Solutions
10.1 Solution for Small & Medium-sized Rooms (30㎡~100㎡)
Applicable Scenarios: Enterprise server rooms, small data centers, network computer rooms
Recommended Products: KITOZER-RC075~RC125 series air-cooled room-level precision air conditioners
Core Configuration:
- 1 set of KITOZER-RC series precision air conditioner
- 1 set of intelligent control system
- 1 set of high-efficiency filtration system
- 1 set of condensate drainage system
- 1 set of remote monitoring module
Solution Features: Simple structure and easy installation without complex cooling water systems; precise temperature control ensures stable equipment operation; high energy efficiency reduces operational costs; intelligent remote management simplifies daily maintenance.
10.2 Solution for Medium & Large-sized Rooms (100㎡~800㎡)
Applicable Scenarios: Medium-sized data centers, cloud computing centers, financial institution computer rooms
Recommended Products: KITOZER-RC250~RC600 series water-cooled / chilled water precision air conditioners
Core Configuration:
- Multiple KITOZER-RC series precision air conditioners (configured per room area and load)
- 1 set of centralized intelligent control system
- 1 set of high-efficiency filtration system
- 1 set of cooling water / chilled water system
- 1 set of remote monitoring software
- 1 set of water leakage detection system
Solution Features: Water cooling ensures high heat dissipation efficiency for medium and large rooms; parallel operation of multiple units achieves mutual redundancy and high reliability; centralized control optimizes operating parameters for optimal EER; centralized remote platform supports multi-unit management and data visual analysis.
10.3 Solution for Super-large Rooms (Above 800㎡)
Applicable Scenarios: Large-scale data centers, Internet enterprise computer rooms, telecom operator core rooms
Recommended Products: KITOZER-RC1200~RC2000 series dual-source cooling precision air conditioners
Core Configuration:
- Multiple KITOZER-RC series dual-source precision air conditioners
- 1 set of distributed intelligent control system
- 1 set of high-efficiency filtration system
- 1 set of cooling water / chilled water system
- 1 set of free cooling system
- 1 centralized remote monitoring platform
- 1 set of redundant power supply system
- 1 set of airflow optimization system
Solution Features: Dual-source redundant design guarantees 24/7 uninterrupted operation; free cooling drastically reduces energy consumption; distributed control ensures independent and stable operation of each unit; centralized platform supports management of thousands of units with real-time data analysis; airflow optimization eliminates hotspots and improves cooling efficiency.
10.4 Solution for Special Environment Rooms
Applicable Scenarios: Computer rooms in ultra-cold regions, high-temperature environments and high-humidity environments
Recommended Products: KITOZER-RC series glycol-cooled / dual-source precision air conditioners
Core Configuration:
- 1 set of KITOZER-RC series glycol-cooled / dual-source precision air conditioner
- 1 wide-temperature operating system
- 1 set of intelligent control system
- 1 set of special filtration system
- 1 set of redundant backup system
Solution Features: Glycol cooling system enables stable operation at -45℃~45℃; dual-source redundancy ensures system stability in extreme environments; customized filtration adapts to harsh on-site conditions; intelligent algorithm optimizes parameters for maximum energy efficiency.
XI. Application Cases
11.1 Case 1: Financial Institution Data Center
Project Background: The 500㎡ data center hosts 300 servers with high load density and strict environmental requirements, requiring 24/7 stable operation throughout the year.
Solution Implementation: Adopted 4 sets of KITOZER-RC250 water-cooled precision air conditioners equipped with centralized intelligent control system and remote monitoring software.
Implementation Effects:
- Achieved temperature accuracy of ±0.5℃ and humidity accuracy of ±3%RH
- System EER reached 3.2, saving 35% energy compared with traditional air conditioners
- Eliminated indoor hotspots and reduced equipment failure rate by 40%
- 7×24-hour remote monitoring shortened fault response time by 50%
11.2 Case 2: Internet Enterprise Cloud Computing Center
Project Background: The 2000㎡ cloud computing center deploys 1,000 servers with ultra-high load density, requiring extreme system reliability and energy-saving performance.
Solution Implementation: Adopted 10 sets of KITOZER-RC600 dual-source precision air conditioners with distributed intelligent control system, free cooling system and centralized remote monitoring platform.
Implementation Effects:
- Dual-source design achieves 99.999% system availability with zero downtime
- Free cooling technology reduces overall energy consumption by 40%
- Ultra-high control accuracy of ±0.3℃ temperature and ±2%RH humidity exceeds industry standards
- Centralized platform realizes unified management and visual data analysis for operational optimization
11.3 Case 3: Hospital Medical Imaging Center
Project Background: The hospital’s MRI and CT equipment are highly sensitive to humidity fluctuation; moisture condensation caused by unstable humidity affects imaging quality and equipment stability.
Solution Implementation: Deployed 2 sets of KITOZER-RC125 air-cooled precision air conditioners with high-precision humidity control and high-efficiency filtration systems.
Implementation Effects:
- Humidity control accuracy reaches ±2%RH, completely eliminating condensation risks
- ±0.5℃ temperature stability ensures continuous and stable operation of medical devices
- High-efficiency filtration achieves ISO 8 indoor cleanliness compliant with medical standards
- Equipment failure rate reduced by 60% with significantly improved imaging quality
11.4 Case 4: Industrial Automation Control Room
Project Background: The factory control room features harsh on-site conditions including heavy dust and drastic temperature fluctuation, requiring high control system stability.
Solution Implementation: Deployed 1 set of KITOZER-RC075 air-cooled precision air conditioner with IP54 enclosure and enhanced filtration system.
Implementation Effects:
- IP54 protection effectively blocks dust intrusion and extends equipment service life
- Enhanced filtration achieves ISO 7 indoor cleanliness for industrial environments
- ±0.5℃ precise temperature control stabilizes automatic production systems
- Equipment failure rate reduced by 50% and overall production efficiency improved by 20%
XII. Keywords, SEO & Tags
12.1 Core Search Keywords
Computer room room-level precision air conditioner, KITOZER precision air conditioner, data center air conditioner, constant temperature and humidity air conditioner, dedicated computer room air conditioner, air-cooled precision air conditioner, water-cooled precision air conditioner, chilled water precision air conditioner, dual-source precision air conditioner, energy-saving precision air conditioner, intelligent precision air conditioner, remote monitoring precision air conditioner, small and medium room AC solution, large room AC solution, super-large room AC solution, financial data center AC case, medical imaging center AC case, industrial control room AC case
12.2 SEO Optimization Settings
Title: KITOZER Room-level Precision Air Conditioning Solution for Computer Rooms – Precise Temperature Control, High Energy Efficiency & Intelligent Management
Description: KITOZER room-level precision air conditioners deliver ±0.5℃ temperature accuracy and ±3%RH humidity accuracy with Level 1 energy efficiency (30%+ energy saving) and remote monitoring functions. Widely used in data centers, server rooms and medical imaging centers.
Keywords: room-level precision air conditioner, KITOZER, constant temperature & humidity, energy efficiency, intelligent management, data center cooling
12.3 Tags
#ComputerRoomPrecisionAC #RoomLevelPrecisionAC #KITOZER #ConstantTemperatureHumidityAC #DataCenterAC #EnergySavingAC #IntelligentAC #RemoteMonitoring #ComputerRoomSolution #PrecisionACCases