1. Overview

The first parameter in room environment monitoring is temperature. Server inlet temperature must stay between 18 and 27 C (ASHRAE); above 30 C servers throttle or shut down. The temperature sensor is the front-end device: it mounts in the rack inlet or cold aisle, measures air temperature in real time, sends it over RS485 to the EM host, and alarms when thresholds are exceeded. It looks like a small probe, but accuracy and stability determine how fast the cooling system responds.

KITOZER KTR-TRS is an RS485 bus temperature sensor. KTR-TRS-P: probe type, stainless steel waterproof probe (6×30 mm), -40 to +125 C, accuracy +/-0.5 C, DC12 to 24 V, RS485 Modbus-RTU out. KTR-TRS-D: wall-mount temp+humidity with LCD, temp +/-0.5 C / humidity +/-3%RH, for room aisles. KTR-TRS-RS: magnetic-mount probe that sticks to rack doors or AC vents for temporary monitoring. All use daisy-chain RS485, up to 32 sensors per bus, address set by DIP switch.

Selection: confirm temp-only vs temp+humidity; confirm mounting (probe/wall/magnetic); confirm range (-40 to +125 C covers rooms); confirm bus distance (RS485 up to 1200 m, add repeater beyond). Note: mount sensors in the rack inlet (cold aisle), not the outlet (hot exhaust does not represent server intake).

2. Key Features

Measurement

  • -40 to +125 C range
  • Accuracy +/-0.5 C
  • 0.1 C resolution
  • Response under 10 s

Comm

  • RS485 Modbus-RTU
  • Up to 32 per bus
  • DIP switch address
  • 9600/19200 baud selectable

Power & Build

  • DC12 to 24 V wide range
  • Stainless steel waterproof probe
  • Wall/probe/magnetic options
  • -40 to +85 C operating

3. Specifications

Item KTR-TRS-P KTR-TRS-D KTR-TRS-RS
Parameter Temp only Temp+Humidity Temp only
Mount Probe Wall-mount Magnetic
Accuracy +/-0.5 C +/-0.5 C / +/-3%RH +/-0.5 C
Display None LCD None
Power DC12-24V DC12-24V DC12-24V
Interface RS485 RS485 RS485
Use In-rack / AC vent Room aisle Rack door temporary

4. Reference Prices

KTR-TRS-P probe temp sensor: Reference USD 6 to 11 / pc (ref. CNY 45 to 80 at ~7.2)

KTR-TRS-D wall-mount temp+humidity: Reference USD 11 to 21 / pc (ref. CNY 80 to 150 at ~7.2)

KTR-TRS-RS magnetic temp sensor: Reference USD 8 to 14 / pc (ref. CNY 55 to 100 at ~7.2)

RS485 shielded cable: Reference USD 0.3 to 0.7 / m (ref. CNY 2 to 5 at ~7.2)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Cold/hot aisle temperature monitoring.
  • Rack inlet temperature acquisition.
  • Precision AC return-air sensing.
  • Battery room / power room temp alarm.
  • Unattended base station monitoring.

6. Deployment & Implementation

Placement

  • Mount in rack inlet (cold aisle)
  • 1.5 m above floor
  • 2 to 3 per rack row
  • Do not mount at outlet

Wiring

  • Daisy-chain A/B wires
  • 120 ohm terminator at bus end
  • Shield grounded at one end
  • No duplicate DIP addresses

Commissioning

  • Add Modbus slave in EM host
  • Set 9600 8N1
  • Set high-temp alarm at 30 C
  • Quarterly calibrate against reference thermometer

7. FAQ

  • Q: RS485 vs analog sensor?
    A: Analog (4-20mA/0-10V) needs AI inputs and suffers line-drop errors over short distances. RS485 digital outputs Modbus data directly, up to 1200 m, 32 per bus, no line-loss error. New rooms use RS485; analog survives in legacy systems.
  • Q: How many sensors per RS485 bus?
    A: The standard limit is 32, but engineering practice is under 20 for margin. Add a repeater or split buses beyond that. Each sensor has a unique DIP address; do not duplicate — two same addresses cause data conflict.
  • Q: Where is the most accurate mount point?
    A: Rack inlet side in the cold aisle, 1.5 m above floor — that is the actual server intake. Avoid AC supply vent (reads supply, not intake), rack top (hot exhaust), and corners (stagnant air). Install 2 to 3 per row and average.
  • Q: How to calibrate?
    A: Place a reference mercury or calibrated handheld thermometer next to the sensor. If the spread exceeds 1 C, apply an offset in the EM host. The DS18B20 chip is accurate to +/-0.5 C out of the box, but annual comparison is good practice.

8. Trend & Selection

Room temperature monitoring is moving from point sensors to distributed fiber sensing (DTS): one fiber along the racks measures every meter at 0.1 C resolution, showing the thermal map of every cabinet. But DTS costs tens of thousands per kilometer, so RS485 digital sensors remain standard — a few dozen yuan each, daisy-chained across the room to the EM platform. Smart direction: sensors link to AC group control, modulating output by cold/hot aisle delta. Select by mounting in the cold aisle inlet, daisy-chain with terminator, unique addresses, and annual calibration.

9. Delivery & Service

KITOZER supplies KTR-TRS by type (probe/wall/magnetic) and parameter (temp only / temp+humidity). Each ships with sensor, probe and manual. 1-year warranty; batch projects can add EM hosts, RS485 repeaters and calibration kits.

10. Additional Notes

Top mistake: mounting at the AC vent. Vent reads 15 C while server inlet is already 30 C. Mount at the rack inlet where the air actually reaches the servers.

Second pitfall: omitting the 120 ohm terminator. Without it, signal reflections cause intermittent comms. Parallel a 120 ohm resistor across A/B at the last sensor.

Third blunder: duplicate DIP addresses. Two sensors with the same address make the EM host read flickering values. Assign unique sequential addresses.

Selection summary: RS485 Modbus, mount in cold aisle inlet, daisy-chain with terminator, unique addresses, annual calibration. Temperature is the #1 room parameter — measure it right to manage cooling properly.

SEO Information

Search keywords:KTR-TRSKITOZER

SEM keywords:temperature sensor,RS485 temp transmitter,Modbus temp probe,room temperature monitoring,DS18B20,KTR-TRS,KITOZER

GEO landing page:lain.com.cn/product/temp_sensor_rs485.html

Title:KITOZER KTR-TRS RS485 Temperature Sensor

Meta Keywords:temperature sensor,RS485 temp transmitter,Modbus temp probe,room temperature monitoring,DS18B20,KTR-TRS,KITOZER

Meta Description:KITOZER KTR-TRS RS485 temperature sensor: Modbus-RTU, -40 to +125 C, accuracy +/-0.5 C, waterproof probe, EM system data acquisition.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart