ToggleProduct Overview
The KITOZER S20-1600/10 low loss oil immersed transformer is engineered for urban and industrial outdoor substations where high efficiency, compact footprint, and long unattended life are required. The 1600 kVA rating steps 10 kV to 0.4 kV and feeds commercial building substations, industrial plant incoming, logistics warehouse distribution, and municipal infrastructure. Amorphous alloy or high grade grain oriented core brings no load loss down to the S20 super low loss band, cutting idle energy waste significantly compared with traditional S11 units. The sealed corrugated tank, conservatorless design, and external radiator banks make the unit suitable for outdoor installation in all climates.
Technical Specifications
Rated 1600 kVA, HV 10 kV off circuit tap plus or minus 2 times 2.5 percent, LV 0.4 kV, Dyn11, impedance 6.0 percent. No load loss 1.45 kW, load loss at 75 degrees 14.5 kW, no load current 0.35 percent. Top oil temperature rise 60 K, winding rise 65 K. Mineral oil quantity 650 kg. Cooling ONAN. Outdoor IP23 enclosure. HV porcelain bushings rated 12 kV, LV bushings rated 0.4 kV. Sealed tank with expansion bellows. Weight 4500 kg. Optional oil temperature gauge with alarm contact, winding temperature indicator with current transformer, and pressure relief valve. Terminal box for earthing. Complies with IEC 60076, GB/T 6451.
Application Scenarios
This rating serves large commercial building outdoor substations, factory main incoming transformers, logistics park distribution, municipal water plant substations, and hospital back up feeders. Because it is oil filled, the unit is installed in a bunded outdoor yard with spill containment, away from occupied areas. The ONAN cooling suits steady industrial load; for cyclic peak load such as stamping plants, forced oil circulation or a derating study is recommended. Parallel operation with two 1600 kVA units provides redundancy for continuous process industries. The sealed tank is suitable for coastal environments with optional double coating and anti corrosion paint.
Advantages
Super low no load loss gives payback within four years in 24 hour duty. Conservatorless sealed design eliminates oil maintenance and breather replacement. External radiator banks allow easy cleaning and replacement. Oil temperature gauge and winding indicator provide remote alarm contacts for SCADA. The unit supports oil sample drain valve and filter pump connection for online oil purification. Rugged tank construction withstands seismic and wind loads. Standardized footprint allows replacement of older transformers with minimal civil modification. Five year warranty and 30 year design life.
Installation and Maintenance
Place on a reinforced concrete plinth with bunded spill tray sized for 110 percent oil volume. Keep 1.5 m clearance for radiator access and tap changer. Connect HV cable via outdoor terminal box or overhead line arresters. Connect LV via busbar to main switchgear. Verify tap position with site voltage. Commissioning includes insulation test, oil dielectric test, turns ratio, and phase rotation. First energization no load for 24 hours, observe top oil temperature. Maintenance every two years: oil sample for dissolved gas and moisture, bushing cleaning, gasket inspection, pressure relief valve test. Every six years: oil filtration or replacement, radiator internal flush if sludge found. Keep oil temperature below 85 degrees continuous; if higher, check load and radiator airflow.
Price
From $14,500 per piece including mineral oil, temperature gauge, and routine test report. Anti corrosion coating, ester oil, and SCADA interface are optional.