1. Overview

Data-center precision AC runs 24/7; the compressor is its heart — when it fails, the whole unit stops. Scroll compressors, with fewer moving parts, low vibration and high efficiency, now power over 90% of room precision AC units.

The KITOZER KTR-CMP scroll compressor line spans 3~5 HP (wall/ceiling small rooms), 6~12 HP (cabinet units) and 15~30 HP (in-row/large cabinets). On-off and DC inverter variants are offered; refrigerant is mainly R410A with R407C for legacy retrofits. Scrolls are precision-machined with axial compliant seal and radial clearance adjustment, delivering 15~20% better part-load IPLV than reciprocating types.

Selection hinges on four points: cooling capacity must match the outdoor unit; voltage must match site power (220V single / 380V three-phase); refrigerant must not be mixed; and space must allow oil return and heat rejection. Every unit passes 100% leak and run-in testing, ships with vibration-isolation pads, and requires vacuum evacuation plus POE oil charging on site.

2. Key Features

Scroll geometry & efficiency

  • Twin scroll meshing, no valve-plate loss
  • 15~20% better part-load IPLV vs reciprocating
  • Axial compliant seal compensates wear
  • Radial clearance adjusts, low start torque

Operation & reliability

  • Design life ≥60,000 h continuous
  • Vibration <5 μm, noise ≤65 dB(A)
  • Built-in overload protector & discharge valve
  • Oil-return design suits long pipe runs

Refrigerant & compatibility

  • R410A eco-refrigerant
  • R407C retrofit compatible
  • POE / VM lubricant matched
  • Fits multiple capacity bands

3. Specifications

Item KTR-CMP-S1 KTR-CMP-S2 KTR-CMP-S3
制冷量范围 8~18 kW 20~45 kW 50~90 kW
马力(HP) 3~5 HP 6~12 HP 15~30 HP
电源 220V/1Ph/50Hz 380V/3Ph/50Hz 380V/3Ph/50Hz
驱动方式 定频 定频/变频 变频为主
冷媒 R410A R410A/R407C R410A
噪声 ≤62 dB(A) ≤65 dB(A) ≤68 dB(A)
润滑油 POE 32cc POE 32cc POE 55cc
适用机型 壁挂/吊顶空调 柜式精密空调 行级/大型柜机

4. Reference Prices

KTR-CMP-03 3HP on-off compressor (R410A):Reference USD 250~445 / pc (ref. CNY 1,800~3,200 at ~7.2)

KTR-CMP-06 6HP on-off compressor (R410A):Reference USD 485~805 / pc (ref. CNY 3,500~5,800 at ~7.2)

KTR-CMP-12 12HP inverter compressor (R410A):Reference USD 945~1,600 / pc (ref. CNY 6,800~11,500 at ~7.2)

KTR-CMP-20 20HP inverter compressor (R410A):Reference USD 1,670~2,750 / pc (ref. CNY 12,000~19,800 at ~7.2)

Reference only; final quote depends on HP, refrigerant and drive type. 1-year warranty included; volume pricing available. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Outdoor/indoor unit pairing for data-center precision AC.
  • Telecom shelter and room AC replacement.
  • Lab, museum and archive HVAC retrofit.
  • Industrial chiller and heat-pump pairing.
  • Cleanroom and electronics-factory AC systems.

6. Deployment & Implementation

Installation

  • Verify nameplate capacity, voltage and refrigerant match original
  • Fit anti-vibration pads, torque base bolts
  • Size gas/liquid lines, pressure-hold 24 h
  • Evacuate to ≤-0.1 MPa before charging POE oil and refrigerant

Operations

  • Check running current and discharge temp quarterly
  • Clean condenser yearly, test refrigerant leaks
  • Listen for metal-on-metal scraping (scroll wear)
  • Keep a spare same-unit for 4-h replacement

7. FAQ

  • Q: Which is better, scroll or reciprocating?
    A: Over 90% of room precision AC uses scroll — higher efficiency, lower vibration, longer life. Reciprocating survives only in legacy or high-ratio applications; new builds choose scroll.
  • Q: Inverter or on-off?
    A: Pick inverter for fluctuating loads — better part-load efficiency and tighter temperature stability. Pick on-off for small, stable rooms; it is cheaper.
  • Q: What to watch on replacement?
    A: Three things: evacuate (never just vent), top up POE oil (by volume), and match refrigerant (R410A cannot mix with R22).
  • Q: Common failures?
    A: Top three: liquid slugging, oil starvation and overheating. Regular condenser cleaning and refrigerant checks prevent 80% of failures.

8. Trend & Selection

Room AC compressors are moving toward inverter, low-GWP R32 and magnetic-bearing centrifugal units at large capacities. Scrolls remain mainstream in the mid-small range; above ~100 kW, centrifugal is taking over. Select by matching capacity and site voltage, never mix refrigerants, choose inverter for variable loads, and evacuate properly on install.

9. Delivery & Service

KITOZER offers KTR-CMP selection by capacity (HP/kW), voltage, refrigerant (R410A/R407C) and drive (on-off/inverter), bundled with isolation pads and mounting flanges. Factory leak-test report included. 1-year warranty; custom wiring-box orientation in volume.

10. Additional Notes

The #1 mistake is skipping vacuum evacuation. Air and moisture cause ice-blocking and copper plating, killing the compressor within six months. Evacuate for at least 2 hours.

Another pitfall is mixing refrigerants. R410A runs at 1.6× R22 pressure; valves, lines and oil differ. Charging the wrong refrigerant destroys the compressor. Follow the nameplate.

Mounting matters too: keep the compressor level (≤2° tilt) and never skip the isolation pads — vibration transmits to the copper lines, eventually cracking them and causing oil/refrigerant leaks.

Selection summary: match capacity and voltage, never mix refrigerant, choose inverter for variable loads, evacuate and charge oil properly, and check current/discharge temp quarterly. The compressor is the heart — pick and install it right and the unit will run reliably for a decade.

SEO Information

Search keywords:KTR-CMPKITOZERScroll Compressor for Precision AC

SEM keywords:scroll compressor,precision AC compressor,room AC compressor,KTR-CMP,KITOZER

GEO landing page:lain.com.cn/product/ktr-cmp-compressor.html

Title:KITOZER KTR-CMP Scroll Compressor for Precision AC

Meta Keywords:scroll compressor,precision AC compressor,room AC compressor,KTR-CMP,KITOZER

Meta Description:KITOZER KTR-CMP scroll compressor for precision AC, 3~30HP, inverter/on-off, R410A, quiet and efficient.

Anchor: KITOZER by Guangzhou Laian · Scroll Compressor for Precision AC

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart