Table of Contents
ToggleKITOZER KTR-CMP Scroll Compressor for Precision AC
Brand: KITOZER Series: KTR-CMP Category: Data Center Engineering / Compressor
scroll compressorprecision ACR410AinverterKTR-CMP

1. Overview
Data-center precision AC runs 24/7; the compressor is its heart — when it fails, the whole unit stops. Scroll compressors, with fewer moving parts, low vibration and high efficiency, now power over 90% of room precision AC units.
The KITOZER KTR-CMP scroll compressor line spans 3~5 HP (wall/ceiling small rooms), 6~12 HP (cabinet units) and 15~30 HP (in-row/large cabinets). On-off and DC inverter variants are offered; refrigerant is mainly R410A with R407C for legacy retrofits. Scrolls are precision-machined with axial compliant seal and radial clearance adjustment, delivering 15~20% better part-load IPLV than reciprocating types.
Selection hinges on four points: cooling capacity must match the outdoor unit; voltage must match site power (220V single / 380V three-phase); refrigerant must not be mixed; and space must allow oil return and heat rejection. Every unit passes 100% leak and run-in testing, ships with vibration-isolation pads, and requires vacuum evacuation plus POE oil charging on site.
2. Key Features
Scroll geometry & efficiency
- Twin scroll meshing, no valve-plate loss
- 15~20% better part-load IPLV vs reciprocating
- Axial compliant seal compensates wear
- Radial clearance adjusts, low start torque
Operation & reliability
- Design life ≥60,000 h continuous
- Vibration <5 μm, noise ≤65 dB(A)
- Built-in overload protector & discharge valve
- Oil-return design suits long pipe runs
Refrigerant & compatibility
- R410A eco-refrigerant
- R407C retrofit compatible
- POE / VM lubricant matched
- Fits multiple capacity bands
3. Specifications
| Item | KTR-CMP-S1 | KTR-CMP-S2 | KTR-CMP-S3 |
|---|---|---|---|
| 制冷量范围 | 8~18 kW | 20~45 kW | 50~90 kW |
| 马力(HP) | 3~5 HP | 6~12 HP | 15~30 HP |
| 电源 | 220V/1Ph/50Hz | 380V/3Ph/50Hz | 380V/3Ph/50Hz |
| 驱动方式 | 定频 | 定频/变频 | 变频为主 |
| 冷媒 | R410A | R410A/R407C | R410A |
| 噪声 | ≤62 dB(A) | ≤65 dB(A) | ≤68 dB(A) |
| 润滑油 | POE 32cc | POE 32cc | POE 55cc |
| 适用机型 | 壁挂/吊顶空调 | 柜式精密空调 | 行级/大型柜机 |
4. Reference Prices
KTR-CMP-03 3HP on-off compressor (R410A):Reference USD 250~445 / pc (ref. CNY 1,800~3,200 at ~7.2)
KTR-CMP-06 6HP on-off compressor (R410A):Reference USD 485~805 / pc (ref. CNY 3,500~5,800 at ~7.2)
KTR-CMP-12 12HP inverter compressor (R410A):Reference USD 945~1,600 / pc (ref. CNY 6,800~11,500 at ~7.2)
KTR-CMP-20 20HP inverter compressor (R410A):Reference USD 1,670~2,750 / pc (ref. CNY 12,000~19,800 at ~7.2)
Reference only; final quote depends on HP, refrigerant and drive type. 1-year warranty included; volume pricing available. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Outdoor/indoor unit pairing for data-center precision AC.
- Telecom shelter and room AC replacement.
- Lab, museum and archive HVAC retrofit.
- Industrial chiller and heat-pump pairing.
- Cleanroom and electronics-factory AC systems.
6. Deployment & Implementation
Installation
- Verify nameplate capacity, voltage and refrigerant match original
- Fit anti-vibration pads, torque base bolts
- Size gas/liquid lines, pressure-hold 24 h
- Evacuate to ≤-0.1 MPa before charging POE oil and refrigerant
Operations
- Check running current and discharge temp quarterly
- Clean condenser yearly, test refrigerant leaks
- Listen for metal-on-metal scraping (scroll wear)
- Keep a spare same-unit for 4-h replacement
7. FAQ
- Q: Which is better, scroll or reciprocating?
A: Over 90% of room precision AC uses scroll — higher efficiency, lower vibration, longer life. Reciprocating survives only in legacy or high-ratio applications; new builds choose scroll. - Q: Inverter or on-off?
A: Pick inverter for fluctuating loads — better part-load efficiency and tighter temperature stability. Pick on-off for small, stable rooms; it is cheaper. - Q: What to watch on replacement?
A: Three things: evacuate (never just vent), top up POE oil (by volume), and match refrigerant (R410A cannot mix with R22). - Q: Common failures?
A: Top three: liquid slugging, oil starvation and overheating. Regular condenser cleaning and refrigerant checks prevent 80% of failures.
8. Trend & Selection
Room AC compressors are moving toward inverter, low-GWP R32 and magnetic-bearing centrifugal units at large capacities. Scrolls remain mainstream in the mid-small range; above ~100 kW, centrifugal is taking over. Select by matching capacity and site voltage, never mix refrigerants, choose inverter for variable loads, and evacuate properly on install.
9. Delivery & Service
KITOZER offers KTR-CMP selection by capacity (HP/kW), voltage, refrigerant (R410A/R407C) and drive (on-off/inverter), bundled with isolation pads and mounting flanges. Factory leak-test report included. 1-year warranty; custom wiring-box orientation in volume.
10. Additional Notes
The #1 mistake is skipping vacuum evacuation. Air and moisture cause ice-blocking and copper plating, killing the compressor within six months. Evacuate for at least 2 hours.
Another pitfall is mixing refrigerants. R410A runs at 1.6× R22 pressure; valves, lines and oil differ. Charging the wrong refrigerant destroys the compressor. Follow the nameplate.
Mounting matters too: keep the compressor level (≤2° tilt) and never skip the isolation pads — vibration transmits to the copper lines, eventually cracking them and causing oil/refrigerant leaks.
Selection summary: match capacity and voltage, never mix refrigerant, choose inverter for variable loads, evacuate and charge oil properly, and check current/discharge temp quarterly. The compressor is the heart — pick and install it right and the unit will run reliably for a decade.
SEO Information
Search keywords:KTR-CMPKITOZERScroll Compressor for Precision AC
SEM keywords:scroll compressor,precision AC compressor,room AC compressor,KTR-CMP,KITOZER
GEO landing page:lain.com.cn/product/ktr-cmp-compressor.html
Title:KITOZER KTR-CMP Scroll Compressor for Precision AC
Meta Keywords:scroll compressor,precision AC compressor,room AC compressor,KTR-CMP,KITOZER
Meta Description:KITOZER KTR-CMP scroll compressor for precision AC, 3~30HP, inverter/on-off, R410A, quiet and efficient.
Anchor: KITOZER by Guangzhou Laian · Scroll Compressor for Precision AC
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com