The KITOZER DN50 pneumatic selector valve directs a single bank of gas suppression cylinders to the correct protected zone when multiple rooms share one cylinder group. When the fire alarm panel identifies which zone is on fire, it energizes the corresponding solenoid pilot valve, which opens the selector valve before the main cylinder discharges, ensuring agent flows only to the fire zone rather than flooding all rooms. The valve body is forged brass with a pneumatic piston actuator and manual override, suitable for FM200, IG541, and FK-5-1-12 systems.
Without selector valves, each protected room would need its own cylinder bank, which multiplies hardware cost and cylinder room footprint. With selector valves, one bank of cylinders can serve 5, 10, or even 20 zones, because only one zone fires at a time. The selector valve is the key component that makes this shared-cylinder architecture safe, because it guarantees the agent route is open before the cylinder discharges. The pneumatic actuator is driven by a small auxiliary nitrogen bottle, which provides reliable pilot pressure even if the main cylinder pressure fluctuates.
Technical Specifications
Nominal diameter DN50, inlet flange PN16, outlet flange PN16, working pressure 6 MPa, opening pressure from pilot air 0.4 to 0.6 MPa, body material forged brass, piston actuator aluminum alloy, pilot solenoid 24V DC 1.5A, manual override lever, visual position indicator open closed, CCCF certified, GB 25972 compliant. Response time under 2 seconds, flow coefficient Kvs 40, operating temperature 0 to 50 degrees Celsius.
The valve body is a two-way straight pattern, forged from HPb59-1 brass and pressure tested at 9 MPa. The piston actuator is aluminum alloy with nitrile seals, driven by pilot air from the auxiliary nitrogen bottle. The pilot solenoid is a 24V DC direct acting valve, with a manual override screw for local testing. The position indicator is a red and green mechanical flag that shows open or closed from across the room. The valve includes a small filter regulator on the pilot air line, which removes moisture and particles before they reach the solenoid. The flange connections match PN16 drilled holes, so the valve drops into standard pipe flanges.
Application Scenarios
This selector valve is used in multi-zone gas suppression systems where several protected rooms share one cylinder bank, such as a data center with multiple server rooms, a banking headquarters with several equipment floors, a university campus with multiple electrical substations, or a museum with several display wings. Sharing cylinders reduces hardware cost and floor space compared with independent cylinder groups for each room. Typical installations use one selector valve per zone, piped to a common cylinder manifold via flexible stainless steel hoses.
For a data center with 10 server rooms on one floor, 10 selector valves are piped to one bank of 12 cylinders, with the valve for the fire zone opening 3 seconds before the cylinders discharge. For a hospital with electrical rooms on multiple floors, selector valves in the basement cylinder room route agent to each floor independently. For a campus with several buildings, selector valves can be grouped in a central cylinder room, with long discharge pipes running to each building. KITOZER offers selector valves in DN32, DN50, DN80, and DN100 sizes, covering zone flows from 10 kg to 200 kg of agent.
Key Advantages
The pneumatic piston actuator opens the valve fully within 2 seconds of pilot signal, fast enough to sequence before the main cylinder discharge. The position indicator provides clear visual feedback to the commissioning engineer, confirming which valve is open during each test. The manual override allows local testing without energizing the pilot circuit, simplifying commissioning. KITOZER supplies the selector valve as a complete assembly with pilot solenoid, filter regulator, and tubing, reducing on-site assembly work for the contractor.
The brass body resists corrosion from long-term exposure to dry nitrogen pilot air, and the aluminum actuator is light enough to mount on the pipe without additional supports. The piston design has no springs to fatigue, so the valve survives decades of standby. The position indicator is mechanical, so it remains accurate even if the pilot air pressure drifts. KITOZER tests every valve on a test bench before shipment, verifying opening time, sealing, and position indicator, and ships each with a test certificate. The CCCF certificate covers the complete valve range.
Installation and Maintenance Recommendations
Mount the selector valve in a vertical or horizontal position near the cylinder manifold, with the position indicator visible from the maintenance walkway. Pipe the pilot air from the auxiliary nitrogen bottle, and set the regulator to 0.5 MPa. Sequence the test so the selector valve opens at least 3 seconds before the main cylinder discharges, to ensure the route is fully open. Inspect the pilot solenoid and filter quarterly, and verify valve position indicator operation semiannually. Replace piston seal kits every 5 years or after 10 full actuation cycles.
Keep the pilot air filter drain valve closed, and drain any accumulated water monthly. Test the selector valve annually by simulating a zone fire, with the main cylinder solenoids isolated, and confirm the correct valve opens and the position indicator moves. Check pilot air pressure monthly on the auxiliary bottle gauge, and refill the bottle when pressure drops below 4 MPa. Keep a spare pilot solenoid on site, because it is the most likely failure component. KITOZER recommends a 10-year overhaul that includes replacing piston seals and inspecting the brass body for internal erosion.
Price
From $480 per valve. Contact +86 13922289957 for selector valve pricing.