KITOZER shielded patch panel 24 port network

KITOZER KTR-SPP 24-Port Shielded Patch Panel

Brand: KITOZER Series: KTR-SPP Category: ELV System 2 / Copper Patching

patch panel24 portshieldedCat6aKTR-SPP

KITOZER KTR-SPP shielded 24 port patch panel Cat6a 1U rack mount

1. Overview

KITOZER KTR-SPP 24-port shielded patch panel is the copper-cable termination point of horizontal cabling. Cable runs from wall outlets terminate at the rear of the panel; the front has 24 RJ45 ports, and patch cords connect to the switch. The panel separates fixed wiring from movable patching — later switch changes or port reassignments touch only patch cords, not the permanent cabling.

KTR-SPP is a 1U-high, 19-inch-wide standard rack unit in a metal housing. “Shielded” means the whole housing and each port’s metal module are grounded, working with shielded cable (F/UTP, SF/UTP) to block EMI/RFI. In environments with VFDs, power cables, medical equipment or RF interference, shielded panels are mandatory; ordinary offices use unshielded (U/UTP).

The rear has IDC 110 termination blocks wired per T568A/T568B. Each port has a dust cap; the front has a label strip for port numbers. Panels pair with a cable manager: panel above, manager below, patch cords routed neatly through it.

2. Key Features

Spec & ports

  • 1U 19-inch, 24×RJ45.
  • Cat6 (250MHz) / Cat6a (500MHz).
  • Shielded (S/FTP) or unshielded (U/UTP).

Shielding & ground

  • Full metal housing; port modules metal-shielded.
  • Rear ground lug to rack frame.
  • Use shielded plugs/patch cords.

Termination

  • IDC 110; T568A/B color code.
  • Tool-less punch-down tool.
  • Gold-plated contacts, corrosion-resistant.

Structure & accessories

  • Rear cable tray and tie-posts.
  • Front label strip + dust caps.
  • Brackets and screws included.

3. Specifications

Item KTR-SPP-24-6 KTR-SPP-24-6A KTR-SPP-48-6A
Category Cat6 shielded Cat6a shielded Cat6a shielded
Ports 24 24 48 (2U)
Bandwidth 250MHz 500MHz 500MHz
Shield S/FTP S/FTP S/FTP
Height 1U 1U 2U
Termination IDC 110 IDC 110 IDC 110
Ground Yes Yes Yes

4. Reference Prices

KTR-SPP-24-6 24-port Cat6 shielded (1U, IDC 110, grounded, metal): Reference USD 28~56 / unit (ref. CNY 200~400 at ~7.2)

KTR-SPP-24/48-6A 24/48-port Cat6a shielded (500MHz, 10G, S/FTP): Reference USD 56~111 / unit (ref. CNY 400~800 at ~7.2)

Reference only; final quote depends on category (Cat6/Cat6a), port count (24/48) and shielding. Rack-row bulk discounted. Punch tool, patch cords and cable manager extra. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Data center server racks, switch patching.
  • ELV network racks, horizontal consolidation.
  • EMI environments (VFDs, power, RF).
  • Medical, industrial and laboratory networks.
  • 10G-to-desk (Cat6a) high-density patching.

6. Installation & Maintenance

Installation

  • Mount panel at a 1U rack position (with brackets).
  • Wire ground lug to rack frame.
  • Enter cable from rear; separate 8 conductors by color.
  • Punch each conductor into IDC block with tool.
  • Trim excess; fit dust cap.
  • Label front against wall outlet location.
  • Patch from panel port to switch.
  • Test: cable tester or Fluke for the link.

Maintenance

  • Limit patch cycles (module life ~750 mates).
  • Replace lost labels; keep port map.
  • Check ground wire tightness.
  • Dust with air blower; no water.
  • If a link fails, check patch cord first, then termination.

7. FAQ

  • Q: Shielded vs unshielded?
    A: Strong EMI (VFDs, motors, high-voltage, RF) → shielded; ordinary ELV offices → unshielded (cheaper, simpler). A shielded system must be fully shielded end to end (cable + plug + panel + module) — any gap kills it.
  • Q: Cat6 vs Cat6a?
    A: Cat6 does 10G at 55m; Cat6a does 10G at 100m (to the desk). Short in-rack runs use Cat6; 100m horizontal 10G-to-desk uses Cat6a.
  • Q: How many panels per rack?
    A: By outlet count. 24 ports per panel; 48 outlets → 2 panels; round up plus 20% spare. Server racks size by server count.
  • Q: Does a shielded panel work if ungrounded?
    A: No. Ungrounded shielding acts as an antenna. The ground wire must bond to the rack frame and through the rack to the room earth bar.

8. Trend & Selection

Panels evolve from “Cat5e/Cat6” to “Cat6a/Cat8 high-shielded”: 10G-to-desk and even short-reach 25G/40G push Cat6a mainstream. Trends: high density (1U 48 or even 96 ports), modular (replaceable port modules), integrated shielded connectivity. Selection: set bandwidth first (gigabit Cat6, 10G-to-desk Cat6a); EMI environments use S/FTP shielded; shielded must be end-to-end; ground it; pair with a cable manager; size ports by outlets +20% spare; labels match drawings.

9. Delivery & Service

KITOZER provides selection: based on outlet count, bandwidth (gigabit/10G) and EMI environment (shielded/unshielded), we configure category, port count and shielding. Bundled with copper cable (KTR-FC), cable manager (KTR-CM), patch cords and wall modules. Delivery includes panel, ground wire, brackets and manual. IDC blocks, housing and labels replaced free in warranty.

10. Additional Notes

The most common pitfall is “incomplete shielding.” Using shielded cable and panel but an unshielded plug or module — a hole in the shield system destroys the effect. Shielding must be whole: shielded cable, shielded plug, shielded panel, shielded module, all grounded.

Another pitfall is “poor termination.” Conductors not in color order, or not fully punched in, so the link works but with packet loss and errors. After termination always test with Fluke or a tester — don’t just “plug it and see.”

Also: “unmanaged patch cords.” Cords drop straight from panel to switch without a manager, tangling the rack — moving one cord tugs ten. Always fit a cable manager below the panel and route cords through its rings.

Selection summary: 10G choose Cat6a; EMI choose shielded end-to-end; ground it; punch and test; pair with a manager; keep 20% spare. The panel is the copper network’s junction point — a clean panel keeps the whole rack maintainable.

SEO Information

Search keywords:patch panel24 portshielded patch panelCat6a1U patch panelKTR-SPPKITOZER

SEM keywords:patch panel price,shielded 24 port supplier,Cat6a patch panel,10G patch panel,KTR-SPP,KITOZER

GEO landing page:lain.com.cn/product/ktr-spp-shielded-patch-panel-24-port.html

Title:KITOZER KTR-SPP 24-Port Shielded Patch Panel

Meta Keywords:shielded patch panel,24 port patch panel,Cat6 patch panel,Cat6a patch panel,1U network patch panel,KTR-SPP,KITOZER

Meta Description:KITOZER KTR-SPP 24-port shielded patch panel, 1U 19-inch, Cat6/Cat6a, fully shielded metal housing, IDC 110 termination, grounding, for horizontal cabling.

Anchor: KITOZER by Guangzhou Laian · Environmental monitoring systems

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart