ToggleKITOZER KTR-SBSP3 DIN-Rail Signal SPD Surge Protector
Brand: KITOZER Series: KTR-SBSP3 Category: Power Distribution / Lightning Protection
DIN RailIn 10 kARS485/NetworkRemote ContactKTR-SBSP3
1. Overview
A Signal SPD (Surge Protective Device) clamps surges on signal lines, preventing lightning-induced or switching transients from riding in on cables and burning switches, sensors and the EM host. Data center protection has two layers: power SPD (installed in the distribution cabinet, class B + class C) and signal SPD (on every signal, network or antenna line entering the building). Typical signal SPD points: (1) outdoor Ethernet cables (CCTV camera runs from the riser to a pole – induced lightning rides in); (2) RS485 buses (temp/humidity sensors on an outside wall run back to the indoor EM host); (3) access control wires (readers outside pick up surges); (4) telephone trunk lines if the room has a staff phone. Signal SPD differs from power SPD: power SPD handles large current (20-100 kA) but higher residual voltage (1.5-2.5 kV); signal SPD handles less current (5-20 kA) but must clamp to a low residual voltage (below the electronics’ withstand). On many sites, installers think a power SPD is enough – then a thunderstorm kills switch RJ45 ports. MLPS 2.0 requires signal-side protection on every cable entering the building.
KITOZER KTR-SBSP3 is a DIN-rail signal SPD. It clips onto a standard 35 mm DIN rail next to MCBs and relays; housing 90x65x40 mm. Inside: a two-stage MOV + GDT (gas discharge tube) design – the front GDT diverts large current (10 kA, 8/20 us), the rear MOV clamps voltage; response time <=1 ns; nominal discharge In = 10 kA (8/20 us); max Imax = 20 kA; rated voltage 6/12/24 V options; insertion loss <=0.5 dB; data rate 100 Mbps (network) or 1 Mbps (RS485). Wiring: Line side connects to the outdoor cable, Equipment side to indoor gear - do not reverse (reversing disables protection). Models: KTR-SBSP3-24 for RS485 (2-wire A/B, 24 V); KTR-SBSP3-RJ45 for network (RJ45, 100 Mbps); KTR-SBSP3-12 for access control (12 V, 2-wire + 4-wire); KTR-SBSP3-BOX 8-port integrated box (8 SPD channels in one enclosure for concentrated riser protection).
Selection: signal type (RS485 uses 2-wire SPD; network uses RJ45 SPD; access control uses 12 V SPD – do not mix); operating voltage (SPD max continuous voltage Uc should sit just above the line’s normal voltage – RS485 24 V picks Uc=24 V; PoE 48 V picks Uc=58 V; too low causes nuisance trips, too high means no protection); mounting point (the SPD goes in the first distribution box where the cable enters the building, not next to the device – lightning current is best dissipated at the entry); grounding (SPD ground via 6 mm2 yellow-green wire to the equipotential bonding bar, lead <=0.5 m); count (one SPD per signal line entering the building - not one SPD protecting many lines; the SPD is in series on the line). The SPD is in series (line -> SPD -> gear), not parallel; watch the degradation window (green good / red failed); keep leads short between SPD and device (long leads raise residual voltage).
2. Key Features
Electrical
- In 10 kA
- Imax 20 kA
- Residual <=800 V
- Response <=1 ns
Circuit
- GDT + MOV two-stage
- MOV clamping
- Insertion <=0.5 dB
- Degradation window
Mount
- DIN 35 mm rail
- Line/Equip terminals
- Remote alarm contact
- UL94-V0 housing
3. Specifications
| Item | SBSP3-24 RS485 | SBSP3-RJ45 Net | SBSP3-12 Access | SBSP3-BOX 8-port |
|---|---|---|---|---|
| Signal | RS485 2-wire | 100M Ethernet | Door 12V | 8-ch mixed |
| Uc | 24 V | 58 V (PoE) | 12 V | 24 V |
| In (8/20 us) | 10 kA | 10 kA | 10 kA | 10 kA/ch |
| Imax | 20 kA | 20 kA | 20 kA | 20 kA/ch |
| Data rate | 1 Mbps | 100 Mbps | 1 Mbps | mixed |
| Port | 2 terminal | RJ45 | 4 terminal | 8 terminals |
4. Reference Prices
KTR-SBSP3-24 RS485 SPD: Reference USD 11-21 / pc (ref. CNY 80-150)
KTR-SBSP3-RJ45 100M network SPD: Reference USD 17-31 / pc (ref. CNY 120-220)
KTR-SBSP3-12 access control SPD: Reference USD 11-21 / pc (ref. CNY 80-150)
KTR-SBSP3-BOX 8-channel box: Reference USD 83-139 / pc (ref. CNY 600-1000)
KTR-SBSP-MOD SPD spare module: Reference USD 6-11 / pc (ref. CNY 40-80)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Outdoor camera cable entry
- RS485 sensor bus
- Access control reader line
- Telephone trunk
- Riser concentrated protection
6. Deployment & Installation
Position
- First box at entry
- DIN rail clip
- Line = outdoor
- Equip = indoor
Ground
- 6 mm2 Y/G wire
- To equipotential bar
- Lead <=0.5 m
- Earth resistance <=4 ohm
Maintain
- Check window
- Red = replace
- Post-monsoon inspect
- Remote to EM alarm
7. FAQ
- Q: Do I need signal SPD if I already have power SPD?
A: Yes. They protect different paths. Lightning near the building drives surges in on both power and signal cables; the power SPD ignores signal lines. Burned switch ports, access-control boards and EM serial ports are common on rooms without signal SPD. MLPS 2.0 also mandates signal-side protection. - Q: What if Line and Equip are swapped?
A: Protection stops working. Line faces the outdoor cable (surge source); Equip faces the protected gear. The internal GDT/MOV sit between Line and ground – if reversed, a surge from the equipment side has no protection. Long leads also raise residual voltage. Follow the L/IN and E/OUT labels. - Q: How often to replace SPD?
A: Watch the window: green = good, red = degraded (MOV has been hit many times). Check after every monsoon season: red means replace. Typical: 3-5 years in ordinary rooms; 1-2 years in high-lightning regions (south China). SPD is consumable – a degraded SPD raises residual voltage and offers no protection. Keep KTR-SBSP-MOD spares on hand. - Q: Can one SPD cover multiple signal lines?
A: No. The SPD is in series on one line. Eight outdoor lines need eight SPDs (or a KTR-SBSP3-BOX 8-channel enclosure). Do not parallel multiple lines onto one SPD – crosstalk develops and a surge on one line couples to others.
8. Trend & Selection
Signal SPD is moving toward integrated, intelligent designs. Trends: plug-in DIN modules (swap without power-down); remote-contact SPD (degradation alarm to EM – no manual window check); PoE++ SPD (60 W, protecting outdoor APs and PTZ cameras); combined power+signal boxes (one box protects both power and signal on a single outdoor drop); multi-stage coordination (class B at building entry, class D at equipment end). Traditional DIN single-channel SPD remains mainstream in small-to-mid data centers. Select by: signal type (RS485/RJ45/access), Uc just above line voltage, install in entry box, 6 mm2 ground lead <=0.5 m, one SPD per line, check window after monsoon.
9. Delivery & Service
KITOZER KTR-SBSP3 ships by RS485/network/access/8-box model, each with SPD module, DIN clip, manual and certificate. 1-year warranty; bulk projects can bundle power SPD, bonding bar and 6 mm2 Y/G ground wire.
10. Additional Notes
Confirm signal type, operating voltage (24 V/48 V PoE/12 V) and channel count (by outdoor entries). For batch orders, install one channel and verify before rollout.
Common mistake: installing SPD next to the device instead of at entry. For convenience, installers put the SPD in the rack near the switch, but the 30 m outdoor run from the riser is itself an antenna – the end-of-line SPD cannot dissipate induced current. Mount in the first box where the cable enters the building (riser or exterior wall).
Second pitfall: undersized, overlong ground. A 1.5 mm2 ground wire routed 2 m to the bonding bar adds inductance that pushes residual voltage above 2 kV and kills gear anyway. Use 6 mm2 Y/G wire straight to the bar, <=0.5 m, no loops.
Third blunder: ignoring a red window. Maintenance sees red and thinks “still works”. A degraded MOV leaks more current; in summer heat the SPD can overheat and ignite. Replace the same day.
Selection summary: match signal type, Uc just above line voltage, mount at entry box, 6 mm2 lead <=0.5 m, one SPD per line, replace on red window.
SEO Information
Search keywords:KTR-SBSP3KITOZER
SEM keywords:signal SPD,DIN rail signal surge protector,RS485 surge protector,data line SPD,surge protective device,KTR-SBSP3,KITOZER
GEO landing page:lain.com.cn/product/ktr-sbsp3-signal-spd-box.html
Title:KITOZER KTR-SBSP3 DIN-Rail Signal SPD Surge Protector
Meta Keywords:signal SPD,DIN rail signal surge protector,RS485 surge protector,data line SPD,surge protective device,KTR-SBSP3,KITOZER
Meta Description:KITOZER KTR-SBSP3 DIN-rail signal SPD for RS485/network lines, nominal discharge 10 kA, remote contact, DIN 35 mm mount.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com