ToggleSubtitle: Complete Guide to Modular Single-Row Hot Aisle Containment System – Design, Configuration, Parameters, Applications and Full Lifecycle Operation & Maintenance
1 System Introduction
1.1 Industry Background & Policy Guidance
Against the backdrop of accelerated global digital transformation and in-depth implementation of the “Dual Carbon” strategy, data centers, the core infrastructure of the digital economy, are witnessing explosive growth in construction scale and computing power density, while facing rigid constraints on energy consumption control. In accordance with the Implementation Plan for the Construction of a National Integrated Computing Power Network jointly issued by four authorities including the National Development and Reform Commission and the Ministry of Industry and Information Technology, the PUE (Power Usage Effectiveness) of newly built large and super-large data centers must be strictly controlled below 1.3, and the PUE of core node data centers in eastern regions shall be further reduced to within 1.25. Energy conservation and carbon reduction have become core indicators for the full-lifecycle construction and operation of data centers.
Refrigeration systems account for 30%~45% of total data center energy consumption, ranking as the second-largest energy-consuming unit only after IT equipment loads. Under the traditional open computer room layout, unregulated mixing of hot and cold airflows causes severe ineffective loss of cooling capacity. The low return air temperature of air conditioning units drastically reduces the COP (Coefficient of Performance) of refrigeration, and frequent local hotspots not only lead to massive energy waste but also seriously threaten the stable operation of IT equipment. To address this industry pain point, hot and cold aisle airflow containment technologies have emerged. Among them, hot aisle containment systems stand out as the core technical solution for airflow organization optimization in new-generation data centers, boasting higher refrigeration efficiency, superior energy-saving performance, and stronger adaptability to high-density loads.
Single-row hot aisle containment systems resolve the drawbacks of double-row hot aisle containment, which impose stringent requirements on computer room space and layout, targeting scenarios such as small and medium-sized computer rooms, edge computing nodes, and energy-saving retrofits of legacy computer rooms to achieve full-scenario coverage.
1.2 Core Definition of Single-Row Hot Aisle Containment System
The KITOZER single-row hot aisle containment system is an integrated airflow containment solution tailored for single-row cabinet layouts, based on the “front air intake, rear hot exhaust” heat dissipation airflow rule of IT equipment. It constructs a fully enclosed and isolated space for hot exhaust air at the rear of cabinets via modular physical structures to 100% collect and divert hot exhaust gas discharged by running IT equipment to the return air outlets of precision air conditioners. This completely physically separates hot and cold airflows, thoroughly eliminating airflow mixing, cooling capacity short-circuiting, and hot air recirculation, drastically improving refrigeration system energy efficiency, lowering computer room PUE, and maintaining stable temperature operating conditions for IT equipment.
Unlike double-row hot aisle containment systems that adopt a “back-to-back” cabinet layout to form a central hot aisle, the single-row solution enables full hot aisle enclosure relying solely on a single row of cabinets without large-scale adjustments to the original computer room layout. It is particularly suitable for scenarios with limited computer room space, wall-mounted single-row cabinets, energy-saving retrofits of legacy computer rooms, and small edge computing computer rooms. Currently, it ranks among the most adaptable, flexibly deployable, and energy-efficient airflow containment products in the data center industry.
1.3 Core Working Principle of the System
The core operating logic of the KITOZER single-row hot aisle containment system follows the airflow organization principle of “positive pressure cold air supply, negative pressure hot air exhaust”. Based on thermodynamics and fluid mechanics laws, it builds a closed airflow circulation loop of “directed cold air supply – heat absorption & heat exchange – enclosed heat collection – precise air return”, breaking the disordered airflow mode of traditional open computer rooms to realize 100% effective utilization of cooling capacity.
The complete workflow is as follows:
- Cold Air Delivery Stage: Precision air conditioning units deliver processed low-temperature cold air to the open cold pool area of the computer room, forming a uniformly positive-pressure cold environment across the entire room. No raised floor air supply is required, imposing no special structural requirements on the computer room building.
- Equipment Heat Exchange Stage: Built-in cooling fans of IT equipment actively draw low-temperature cold air from the open cold environment of the computer room. The cold air flows through heat-generating components such as chips and mainboards inside the equipment for heat exchange, after which high-temperature exhaust air carrying abundant heat is discharged from the rear of the cabinets.
- Enclosed Heat Collection Stage: All high-temperature hot exhaust air discharged from cabinet rears enters the fully enclosed hot aisle space constructed by the KITOZER single-row containment system. The fully enclosed structure fully traps hot exhaust without leakage or diffusion, preventing mixing with cold air in the computer room. A stable negative pressure environment is maintained inside the hot aisle to ensure directional flow of hot air.
- Precise Air Return Stage: High-temperature hot exhaust inside the enclosed hot aisle is 100% precisely diverted to the return air outlets of precision air conditioners via top return air ducts, static pressure boxes, or direct docking. The air conditioning units cool the high-temperature return air and resupply cold air to the computer room cold environment, completing the full airflow circulation.
Compared with cold aisle containment systems, the KITOZER single-row hot aisle containment system fully confines high-temperature hot exhaust in an independent space, keeping the overall computer room environment at low temperature. Operation and maintenance staff can complete daily equipment maintenance without entering the enclosed aisle, greatly boosting maintenance convenience and personnel comfort. Meanwhile, high-temperature air returning directly to air conditioning units significantly raises air conditioning return air temperature, substantially lifting the COP of air conditioning compressors, improving refrigeration efficiency by over 30% and delivering more remarkable energy-saving effects.
1.4 National & Industry Standards Followed in System Design
All KITOZER single-row hot aisle containment system products are designed, manufactured, installed and accepted in strict compliance with current national, industrial and international standards. All products pass third-party authoritative testing, with all performance indicators meeting or exceeding standard requirements. The core followed standards are listed below:
- GB 50174-2017 Code for Design of Data Centers
- GB 50462-2024 Code for Construction and Acceptance of Data Center Infrastructure
- GB/T 19520.16-2015 Mechanical Structures for Electronic Equipment – Outdoor Enclosures – Part 3-16: Climate, Mechanical Tests and Safety Requirements for Cabinets and Racks
- IEC 60297 Series Standards Mechanical Structures for Electrical and Electronic Equipment
- T/GDEA 002-2023 Technical Specification for Hot and Cold Aisle Airflow Organization of Data Centers
- T/DZJN 386-2025 Cooling Design Requirements for Intelligent Computing Centers
- GB 15763.2-2005 Safety Glass for Buildings – Part 2: Tempered Glass
- GB 50016-2014 (2018 Edition) Code for Fire Protection Design of Buildings
- GB 50116-2013 (2019 Edition) Code for Design of Automatic Fire Alarm Systems
- GB/T 38734-2020 Minimum Energy Efficiency Values and Energy Efficiency Grades for Data Centers
- GB 7251.1-2013 Low-Voltage Assembled Switchgear and Controlgear Assemblies – Part 1: General Specifications
- YD/T 2319-2011 Technical Requirements and Test Methods for Hot and Cold Aisle Energy-Saving Equipment in Communication Computer Rooms
1.5 Core System Value & Industry Significance
- Maximize Energy Saving & Cost Reduction to Support Dual Carbon Goals By completely isolating hot and cold airflows to eliminate ineffective cooling capacity loss, the KITOZER single-row hot aisle containment system cuts refrigeration system energy consumption by 30%~40% and reduces computer room PUE from 1.8~2.0 under traditional open layouts to 1.2~1.4, fully meeting green data center construction requirements stipulated by the state. For an IT load of 100kW, approximately 250,000 kWh of electricity can be saved annually, drastically lowering computer room operating costs while curbing carbon emissions and supporting enterprises’ carbon neutrality targets.
- Eliminate Local Hotspots to Guarantee Stable IT Equipment Operation In traditional computer room layouts, mixed hot and cold airflows create large temperature differences across cabinets and frequent local hotspots. Long-term operation of IT equipment under high temperatures drastically raises failure rates and shortens service life. The directional airflow organization of the KITOZER system ensures uniform, stable low-temperature intake air for every cabinet and every U-unit of IT equipment, controlling cabinet intake air temperature deviation within ±1℃ to fully eliminate local hotspots. IT equipment MTBF (Mean Time Between Failures) is increased by over 40%, and service life extended by 3~5 years, maintaining IT equipment within optimal operating temperature ranges.
- Adapt to High-Density Computing Power & Boost Computer Room Space Utilization Driven by rapid development of AI intelligent computing and high-performance computing, single-cabinet power density has surged from the traditional 3~5kW to 15~30kW, making traditional cooling modes unable to dissipate heat for high-density loads. The KITOZER single-row hot aisle containment system supports a maximum single-cabinet power density of 50kW. Precise heat collection and air return enable stable operation of high-density cabinets without expanding computer room floor area, lifting space utilization by over 50%. It also eliminates the need for raised floor construction, cutting computer room construction costs and cycles.
- Flexible Deployment for Full-Scenario Coverage to Meet Diverse Demands Adopting a fully modular design, the KITOZER single-row hot aisle containment system requires only a single cabinet row for deployment without relying on double-row cabinet layouts. It adapts to nearly all scenarios including standardized construction of new computer rooms, non-interruptible energy-saving retrofits of legacy computer rooms, small edge computing computer rooms, branch office computer rooms of government and enterprises, financial outlet computer rooms, and medical building computer rooms. Flexible capacity expansion starting from a single cabinet avoids excessive upfront investment, enabling “on-demand construction and phased expansion” to lower construction barriers significantly.
- Intelligent Linked Control for Unattended Operation & Maintenance The KITOZER single-row hot aisle containment system integrates a complete environment monitoring and intelligent linkage framework, supporting real-time monitoring of temperature, humidity, differential pressure, smoke, access control and other status metrics. It seamlessly links with fire protection systems, air conditioning systems and lighting systems, enabling remote monitoring, fault early warning and intelligent alarms. The system can connect to computer room BMS (Building Management System) and environment monitoring platforms to realize full-lifecycle intelligent, unattended operation and maintenance, drastically reducing maintenance difficulty and labor costs.
2 System Composition
The KITOZER single-row hot aisle containment system adopts a fully modular, sub-system design, consisting of 10 core sub-systems. Each sub-system operates independently for separate customized production while seamlessly splicing and coordinating with others. All components are prefabricated in factories, requiring only bolt assembly on-site without welding or cutting, drastically shortening on-site construction cycles while ensuring system stability and consistency. Detailed descriptions of each sub-system and core components are provided below:
2.1 Main Channel Frame System
The main channel frame system serves as the core load-bearing structure of the KITOZER single-row hot aisle containment system, providing mechanical support, structural fixation and dimensional benchmarks for the entire containment system. It is the core component guaranteeing overall system stability, air tightness and seismic performance. All frame components adopt modular prefabricated design for flexible splicing according to cabinet quantity and size to meet diverse scenario demands.
Core components:
- Vertical Support Columns: Fabricated from high-strength 6063-T5 aluminum alloy profiles or high-quality cold-rolled steel bent plates, the core vertical load-bearing components of the frame. Surfaces undergo anodizing or pickling-phosphating + electrostatic powder coating for superior anti-corrosion and rust resistance. Universal mounting holes spaced ≤25mm are pre-reserved for seamless connection with cabinets, top frames, side panels and end doors, adapting to cabinets of varying depths and heights. Static load capacity per column ≥500kg, supporting installation of various top-mounted equipment.
- Horizontal Connecting Beams: Matched with vertical support columns and manufactured from identical aluminum alloy or cold-rolled steel materials. They connect adjacent vertical columns to form the horizontal load-bearing structure of the frame, with universal mounting slots pre-reserved for direct installation of skylight modules, lighting fixtures, sensors and wiring trays without additional drilling, greatly improving installation convenience.
- Cabinet Connection & Fixing Components: Including special connecting clips, L-shaped connecting plates, fixing bolts and shock-absorbing gaskets, used for rigid connection between the frame system and cabinet tops/sides to form an integrated stable structure. Compatible with all mainstream cabinet brands and specifications without drilling or modifying original cabinets to preserve equipment integrity.
- Side/Back Enclosure Frames: Specially designed for single-sided enclosure requirements of single-row hot aisle systems to construct complete enclosed spaces by installing side and back sealing panels. Tenon-and-mortise splicing with the main frame ensures splicing gaps ≤0.3mm, delivering excellent overall air tightness and structural strength.
- Seismic Reinforcement Components: Including diagonal supports, seismic brackets and reinforcing corner brackets to upgrade overall system seismic performance, meeting installation requirements for regions of varying seismic fortification intensities. Seismic reinforcement components raise the system’s seismic rating to Grade 8 or above, preventing structural collapse or detachment under extreme seismic conditions to protect computer room equipment safety.
- Adjustable Installation Components: Including height-adjustable footings, horizontal adjustment gaskets and telescopic connecting beams to adapt to uneven computer room floors and dimensional deviations of cabinets, enabling ±50mm vertical and horizontal adjustment with installation precision deviation ≤1mm/m to meet horizontal and vertical tolerances specified by codes.
2.2 Top Enclosure System
The top enclosure system acts as the core component realizing top sealing and airflow isolation for the KITOZER single-row hot aisle containment system, integrating critical functions including fire protection linked pressure relief, daily maintenance observation and integrated equipment installation. All top modules adopt standardized unit design matching cabinet width for seamless docking with cabinet rows to form a complete top sealing plane after splicing.
Core components:
- Fixed Top Plate Modules: Base components for conventional top enclosure of hot aisles, constructed with high-strength aluminum alloy frames and flame-retardant heat-insulating panels. Optional panel materials include 5mm tempered glass, 8mm polycarbonate (PC) flame-retardant sheets and double-layer hollow sun sheets with customizable light transmittance. EPDM foamed sealing strips with compression ratio ≥35% are fitted around module perimeters to eliminate airflow leakage after splicing. Quick-release clip connections to the frame enable convenient installation and removal.
- Fire Protection Linked Flip Skylight Modules: Core functional components guaranteeing system fire safety, mounted on the hot aisle top and seamlessly linked with computer room automatic fire alarm systems and gas fire suppression systems. Normally closed during routine operation to maintain top enclosure; upon triggering of fire alarm signals, fully open within 0.5s at an opening angle ≥90° to allow rapid, complete filling of the hot aisle space with fire suppression gas for effective IT equipment fire extinguishing. Manual or electric reset is supported post fire suppression. Skylight modules adopt electromagnetic suction drive mechanisms with DC24V operating voltage, supporting dry contact fire signal access and manual emergency opening in power-off conditions. High-strength aluminum alloy border, tempered glass or PC flame-retardant panels, single-module load capacity ≥250N/m², excellent impact resistance and anti-falling protection to avoid equipment or personnel damage from accidental detachment.
- Function-Integrated Top Plate Modules: Specialized top plates designed for installation of sensors, lighting fixtures, wiring trays and air return interfaces, with standardized pre-reserved mounting holes and fixing slots for direct fitting of temperature/humidity sensors, differential pressure sensors, smoke detectors, infrared detectors and LED lighting without on-site drilling or cutting. Built-in concealed wiring troughs for strong and weak current cables, delivering a neat, aesthetic top layout without compromising system air tightness.
- Air Return Interface Top Plate Modules: Customized for duct air return and top-mounted air conditioning return air scenarios, with customizable opening dimensions matching air conditioner return outlets and duct specifications, paired with flange connecting assemblies to seamlessly link return air ducts and air conditioner return outlets, ensuring 100% diversion of hot exhaust from the hot aisle to air conditioning return points without leakage. Optional air volume regulating dampers enable precise adjustment of return air volume across different zones.
- Top Plate Splicing Sealing Components: Including special sealing strips, splicing clips, gap sealing strips and internal/external corner sealing fittings to achieve seamless air tightness between top plate modules and between modules and frames. All sealing components are flame-retardant and anti-aging with a service life ≥10 years, maintaining stable performance without hardening or cracking between -30℃ and 80℃.
2.3 Channel End Door System
Installed at both ends of the KITOZER single-row hot aisle containment system, the end door system serves as the core component for channel end enclosure, personnel access and equipment transportation, alongside safety protection, access control and status display functions. Fully compliant with GB 50462-2024 specifications, end doors feature clear opening direction and warning signs to enable rapid personnel evacuation in emergencies.
Core components:
- Double-Leaf Swing Doors: Standard end door style for single-row hot aisle systems, fabricated with high-strength aluminum alloy door frames and tempered glass door leaves. 5mm+5mm double-layer laminated tempered glass door leaves with light transmittance ≥90% deliver superior impact resistance and prevent glass fragments from falling and injuring personnel upon breakage, complying with safety glass standards. Equipped with 304 stainless steel hinges enabling opening angles ≥180° and hydraulic door closers for automatic leaf closure to maintain air tightness in the normally closed state. Optional locks include mechanical anti-theft locks, electromagnetic locks, fingerprint access locks and facial recognition locks to meet varying security grade demands. Flame-retardant sealing strips fitted around door perimeters ensure gaps ≤0.5mm after full closure to eliminate airflow leakage.
- Double-Leaf Sliding Doors: Specialized end doors for scenarios with limited computer room space and insufficient swing clearance for door leaves. Adopting top-load sliding guide rails without reserved swing space to drastically save computer room floor area. High-strength aluminum alloy door frames and tempered glass door leaves fitted with silent pulleys and damping buffers for smooth, low-resistance sliding (pull force ≤50N) without noise. Magnetic locking mechanisms secure fully closed positions, with optional electric drive for automatic opening/closing to fit unattended operation and maintenance scenarios.
- Single-Leaf Emergency Doors: Designed for short-row single hot aisle scenarios or as auxiliary emergency doors paired with double-leaf end doors, mounted on channel sides or ends for quick routine personnel access without opening full-size double doors to minimize hot air leakage. Customizable dimensions, standard mechanical locks and door closers, plus emergency push bar locks allowing one-touch rapid opening from inside the channel in emergencies to satisfy fire evacuation requirements.
- Specialized Equipment Transport Doors: Detachable or folding end doors customized for transport of large IT equipment and cabinets, adopting modular splicing structures enabling rapid removal of door leaves and frames to form a complete transport passage without dismantling the full end door system. Quick reset post equipment transport to minimize transport difficulty without compromising system air tightness or structural stability.
- Auxiliary End Door Functional Components: Including access controllers, card readers, facial recognition terminals, door magnetic sensors, emergency push bar locks, door closers, hinges, warning signs and observation windows, flexibly configurable to realize access control, open/close status monitoring, illegal intrusion alarms and fire protection linked unlocking. The access control system can seamlessly connect to computer room environment monitoring systems for real-time upload and unified management of all personnel access records.
2.4 Side & Back Enclosure Sealing System
The side and back enclosure sealing system represents a distinctive core component differentiating single-row hot aisle systems from double-row alternatives, realizing full enclosure of single-row hot aisle sides and rears to construct complete confined hot aisle spaces and fully block hot air leakage from side and back areas for optimal airflow isolation. Adopting full modular design, it can be customized to match cabinet row lengths, wall distances and spatial dimensions to adapt to irregular computer room layouts.
Core components:
- Fixed Enclosure Panels: Base components of the side and back enclosure system, constructed with high-strength aluminum alloy frames and flame-retardant heat-insulating panels. Optional panel materials include cold-rolled steel plates (thickness ≥1.5mm, electrostatic powder coated for anti-corrosion and rust resistance), PC flame-retardant sheets (UL94 V-0 flame retardant rating, high temperature and impact resistance) and tempered glass. Modular single-unit design with customizable dimensions, quick-release clip frame connections for easy installation and removal, splicing gaps ≤0.3mm with matching special sealing strips to guarantee air tightness.
- Openable Maintenance Side Panels: Designed for zones requiring routine maintenance, adopting identical materials and structures as fixed enclosure panels, fitted with hinges and locks for instant opening to facilitate internal cable sorting, equipment maintenance and sensor calibration without full panel removal, greatly boosting maintenance efficiency. Limit devices secure fixed opening angles to prevent accidental closure and personnel injury, with full sealing strips eliminating airflow leakage after closure.
- Flexible Sealing Components: Critical fittings for blocking irregular gaps between cabinets and frames, frames and walls, enclosure panels and floors, and between adjacent cabinets to guarantee overall system air tightness. Including high-elastic brush strips, flame-retardant foamed sealing strips, silicone gaskets and cuttable flexible blocking plates. Special cabinet gap brush strips feature flame-retardant nylon bristles ≥50mm long to perfectly fit uneven cabinet surfaces and block gaps up to 10mm without hindering normal cabinet door operation. Flame-retardant foamed sealing strips can be freely cut to match irregular gaps, delivering overall system air leakage rate ≤0.1L/s, leading industry performance.
- Blank Rack Panels for Unused U-Slots: For blocking vacant U-slots inside cabinets without IT equipment, a vital auxiliary component preventing hot air recirculation to cabinet fronts and mixing of hot and cold airflows. KITOZER blank panels are manufactured from 1.2mm cold-rolled steel complying with 19-inch standard cabinet specifications, adopting tool-free clip-on quick installation. Sealing strips fitted around perimeters ensure gaps ≤0.2mm after mounting with blocking efficiency ≥99%, fully eliminating hot air backflow through vacant U-slots.
- Bottom Sealing Components: For blocking gaps between hot aisle bottoms and floors, including bottom sealing baffles, floor sealing strips and height-adjustable blocking bars with flexible height adjustment to adapt to uneven floors and eliminate bottom air leakage without interfering with raised access floors and cable trays. Compatible with raised floors, cement floors and anti-static floor tiles of all types.
2.5 Fire Protection Linked Control System
The fire protection linked control system forms the safety core of the KITOZER single-row hot aisle containment system, enabling seamless linkage between the system and the computer room fire protection framework to ensure rapid system response upon fire outbreaks, meeting fire suppression requirements and protecting personnel and equipment safety in the computer room. Fully compliant with GB 50116-2013 Code for Design of Automatic Fire Alarm Systems and GB 50016-2014 Code for Fire Protection Design of Buildings, all components pass fire product certification with stable and reliable performance.
Core components:
- Fire Protection Linked Controller: Central brain of the full fire protection linked control system, adopting an industrial-grade PLC control unit with dual AC220V/DC24V power supply and power-off emergency operation capability. Equipped with multi-channel dry contact input/output interfaces for access to fire alarm signals, linkage signals from automatic fire alarm systems and release/feedback signals from gas fire suppression systems, with signal isolation and anti-interference functions for stable operation under complex electromagnetic environments of computer rooms, MTBF ≥100,000 hours.
- Skylight Drive Actuators: For driving opening and closing of fire protection linked flip skylights, powered by safe DC24V voltage complying with computer room safety power standards, categorized into electromagnetic suction and electric pushrod types. Electromagnetic suction types deliver response time ≤0.5s for instant skylight opening upon fire signal triggering; electric pushrod types enable precise opening angle control and staged opening, plus manual unlocking functionality. Drive actuators feature anti-jam and overload protection with service life ≥100,000 opening/closing cycles and fault-free long-term operation.
- Manual Emergency Control Devices: Mounted in prominent positions at both channel ends, equipped with emergency stop buttons, manual opening buttons and status indicator lights for manual control in emergencies. Even if the fire linked control system loses power or malfunctions, operation and maintenance staff can open all fire skylights with one touch to satisfy fire suppression requirements, paired with locking devices to prevent misoperation.
- Status Monitoring & Feedback Components: Including door magnetic sensors, position sensors, voltage monitoring modules and current monitoring modules for real-time tracking of skylight open/closed status, drive actuator operating status and power supply voltage. All status signals are uploaded in real time to the fire linked controller and computer room environment monitoring system for remote status viewing. Audible and visual alarms trigger immediately upon abnormal conditions such as failed skylight opening, drive actuator faults or power supply anomalies, with alarm information uploaded simultaneously.
- Audible & Visual Alarm Devices: Mounted at both channel ends and matched with fire linked controllers. Upon fire signal triggering, system faults or unauthorized operation, high-decibel audible and visual alarms activate with volume ≥110dB and adjustable light flashing frequency to alert on-site operation and maintenance staff for timely disposal.
- Uninterruptible Backup Power Supply: Industrial-grade UPS backup power fitted with standard 12V/7Ah maintenance-free lead-acid batteries, providing no less than 2 hours of emergency power supply to the fire linked system upon main power failure. This guarantees normal system operation and reliable skylight opening in fire emergencies even with complete loss of computer room mains power, meeting fire code requirements.
2.6 Environment Monitoring System
The KITOZER single-row hot aisle containment system integrates an all-in-one environment monitoring system for real-time measurement, data collection, analysis, early warning and intelligent linkage of environmental parameters, equipment operating status and safety conditions inside hot aisles to realize full-lifecycle intelligent management of the entire system. It seamlessly connects to existing computer room environment monitoring platforms and BMS building management systems, supporting remote access and mobile viewing to drastically upgrade the intelligent level of computer room operation and maintenance.
Core components:
- Environment Monitoring Host: Core of the full environment monitoring system, adopting an industrial-grade ARM architecture processor and embedded Linux operating system for stable, crash-free operation. Equipped with multiple RS485, RJ45, DI/DO interfaces supporting standard communication protocols including Modbus-RTU, Modbus-TCP and SNMP for access to all types of sensors and actuators, alongside seamless docking with third-party platforms. Built-in high-capacity storage chips retain historical data for no less than 5 years with support for data export, query and analysis. Edge computing functionality enables local intelligent logic control, threshold configuration and linkage strategy setup for independent operation without reliance on upper-level platforms.
- Temperature & Humidity Sensors: Fitted with industrial high-precision temperature and humidity collection chips, installed at key positions including hot aisle interiors, cabinet air intakes and air conditioning return outlets for real-time temperature and humidity measurement. Temperature measurement range: -20℃~80℃, accuracy ±0.2℃; humidity measurement range: 0~100%RH, accuracy ±2%RH. Configurable sampling frequency up to 1 reading per second with RS485 communication for real-time data upload to the monitoring host. Automatic alarms trigger when temperature and humidity exceed set thresholds, alongside linkage to air conditioning systems for operational parameter adjustment to stabilize computer room environments.
- Differential Pressure Sensors: For real-time measurement of static differential pressure between hot aisle interiors and the computer room cold environment, the core metric judging system sealing performance and airflow organization normality. Differential pressure measurement range: 0~100Pa, accuracy ±1Pa, response time ≤1s with RS485 communication for real-time data upload. Under normal operating conditions, negative pressure of 5~10Pa shall be maintained inside the hot aisle relative to the computer room environment. Early system warnings activate when differential pressure deviates beyond set ranges to prompt operation and maintenance staff to inspect sealing performance and air conditioning operating status for timely anomaly resolution.
- Smoke Detectors: Photoelectric smoke detection sensors passing fire product certification, mounted on hot aisle tops for real-time monitoring of smoke concentration inside channels. Smoke concentration exceeding thresholds triggers alarms within 3 seconds, with signals uploaded to fire linked controllers and environment monitoring hosts alongside activation of audible and visual alarm devices and fire linkage logic for early detection and resolution of fire hazards.
- Access Control Management Unit: Including access controllers, card readers, facial recognition terminals and door magnetic sensors for access control of channel end doors and maintenance doors. Supporting multiple opening methods including card swiping, passwords, fingerprint and facial recognition with configurable personnel access permissions and time windows, automatic recording of all personnel access timestamps, opening methods and identity information for query and export. Additional functions include illegal intrusion alarms, door ajar alarms and duress alarms, alongside linkage with computer room video surveillance systems to trigger automatic camera recording upon door opening and elevate computer room physical security grades.
- Video Surveillance Unit: Including high-definition network cameras and NVR storage devices. 2MP/4MP high-definition infrared cameras with wide dynamic and low-light performance mounted at key channel end and top positions for real-time monitoring of internal equipment status and personnel activity. Live video streams upload to monitoring platforms with support for remote viewing, playback and motion detection alarms, linkable with access control and alarm systems to realize comprehensive safety management.
- Water Leak Detection Sensors: Including positioning and non-positioning water leak detection cables and water leak controllers, installed at hot aisle bottoms, beneath air conditioning units and along cable trays in water-prone zones for real-time water leak monitoring. Positioning detection cables deliver leak location precision ±0.5m, triggering instant alarms upon water detection alongside linkage to shut off inlet valves to prevent short-circuit damage to IT equipment from water leakage.
- Air Conditioning Linked Control Unit: Connects to precision air conditioning units in computer rooms via standard communication protocols to enable real-time reading and remote adjustment of air conditioning operating parameters. Based on hot aisle temperature/humidity data and IT load variations, the system automatically modulates air conditioning supply air temperature, fan speed and operating modes to realize adaptive refrigeration regulation for further energy savings, alongside monitoring of air conditioning operating status and fault alarms for full-lifecycle management of air conditioning equipment.
2.7 Lighting System
The lighting system provides illumination for daily operation and maintenance inside the KITOZER single-row hot aisle containment system, adopting modular integrated design seamlessly fused with the top enclosure system without additional mounting brackets for a neat, aesthetic overall layout, alongside intelligent sensing control to balance energy conservation and maintenance convenience.
Core components:
- LED Lighting Fixtures: Elongated LED panel lights integrated as a single unit with top skylight and top plate modules. Aluminum alloy lamp housings deliver superior heat dissipation; high-CRI LED chips with CRI Ra≥90 and 4000K neutral light produce soft, flicker-free illumination complying with computer room lighting standards. IP20 protection grade, optional AC220V/DC24V operating voltage, power density ≤5W/m, illumination brightness ≥300lux, service life ≥50,000 hours with long-term light attenuation ≤5%.
- Intelligent Sensing Control Devices: Including human infrared sensors, illuminance sensors and intelligent controllers enabling automatic lighting control. Lights activate upon detection of personnel entering the channel and auto-shut down after a set delay following personnel departure. Lamp brightness automatically adjusts according to channel ambient illuminance for further energy conservation. Sensing distance ≥5m, sensing angle ≥120°, response time ≤0.5s with effective false trigger prevention, plus support for manual forced switching and remote control to fit diverse maintenance scenarios.
- Emergency Lighting Fixtures: Fire-certified emergency lighting lamps with built-in backup batteries, automatically switching to emergency power supply upon loss of computer room mains to deliver no less than 90 minutes of emergency illumination meeting fire evacuation standards, emergency brightness ≥50lux, linkable with the computer room fire emergency lighting system for unified management.
- Lighting Power Distribution & Control Components: Including lighting distribution boxes, air switches, contactors, wiring terminals and cables. All power distribution components are premium products passing 3C certification with overload and short-circuit protection to guarantee safe lighting power supply, supporting partitioned and centralized control for channel layouts of varying lengths.
2.8 Cable Routing & Management System
The cable routing and management system realizes orderly layout, management and protection of strong/weak current and communication cables inside the KITOZER single-row hot aisle containment system, ensuring neatly arranged, clearly marked cables for convenient maintenance without disrupting airflow organization or compromising system air tightness and heat dissipation performance.
Core components:
- Top Cable Tray System: Aluminum alloy enclosed or open trays integrated as a single unit with channel top frames for laying strong/weak current cables and communication optical fibers. Customizable tray sizes matched to cable quantities, fitted with cable organizers, tie-down bases and partition plates for separated routing of strong current, weak current and optical fibers to avoid signal interference. Clip-on frame connections enable convenient installation with pre-reserved cable inlet/outlet holes paired with sealing grommets to preserve system air tightness.
- Vertical Cable Management System: Mounted on cabinet sides and channel vertical columns for vertical cable routing from top trays to cabinet interiors, including vertical cable management racks, cable rings and fixing clips to guarantee neat vertical cable routing without sharp bends or tension, complying with cable bend radius requirements to prevent cable damage without hindering normal cabinet door operation or channel air tightness.
- Cable Protection Components: Including flame-retardant corrugated tubes, cable sleeves, wrapping tubes, waterproof joints and sealing grommets for cable protection against abrasion and scratches, alongside sealing blockage of cable inlet/outlet holes to maintain system air tightness. All protection components are flame-retardant and anti-aging to meet computer room fire protection standards.
- Cable Identification Components: Including label paper, label boxes, identification plaques and number tubes for standardized, clear marking of all cables. Identification content covers cable number, origin, destination, purpose and specification to enable rapid cable identification and tracing during maintenance, boosting operational efficiency and preventing misoperation.
2.9 Matching Cabinet System
The KITOZER single-row hot aisle containment system fully supports all KITOZER server cabinets, network cabinets and row-end distribution cabinets, alongside compatibility with all mainstream standard 19-inch cabinet brands on the market. For optimal sealing performance and adaptability, KITOZER matching cabinet systems are recommended, delivering superior overall performance via integrated original factory design, production and commissioning alongside hot aisle containment systems.
Core components:
- Standard Server Cabinets: Complying with international 19-inch standards, available in 600mm/800mm widths, 1000mm/1100mm/1200mm depths and 42U/47U heights. Manufactured from high-quality cold-rolled steel with frame thickness ≥2.0mm and static load capacity ≥1500kg. Front doors feature high-airflow mesh panels with ventilation rate ≥75%, rear doors adopt double-leaf mesh panels compatible with front-in rear-out heat dissipation air ducts. Surfaces undergo pickling-phosphating + electrostatic powder coating for anti-corrosion and rust resistance, with special pre-reserved connecting holes for seamless docking with hot aisle containment systems without on-site cabinet modification.
- High-Density Intelligent Cabinets: Designed for single-cabinet loads above 10kW. In addition to all performance attributes of standard server cabinets, integrated built-in cabinet-level temperature/humidity monitoring, intelligent PDUs, access control management and auxiliary local heat dissipation units enable refined single-cabinet management with intelligent linkage to hot aisle containment systems, adapting to high-density computing power scenarios including AI intelligent computing and high-performance computing.
- Row-End Distribution Cabinets: Divided into strong-current and weak-current row-end cabinets, installed at the ends of cabinet rows with integrated design matching hot aisle containment systems. Strong-current row-end cabinets deliver power distribution, metering and protection for in-cabinet IT equipment, equipped with molded case circuit breakers, intelligent molded case switches and multi-function power meters supporting real-time single-loop current, voltage, power and energy measurement alongside remote switching control. Weak-current row-end cabinets accommodate optical fiber distribution frames and network patch panels for communication cable termination and management. Row-end cabinet dimensions fully match standard cabinets for seamless integration into hot aisle layouts to maintain consistent aesthetics and air tightness.
- Intelligent PDUs: Cabinet power distribution units categorized into basic, metering and intelligent control models with 220V/380V input voltage, customizable output jacks complying with national standard 10A/16A and IEC C13/C19 specifications. Intelligent models support real-time single-jack current, voltage and power metering alongside remote switching control, overload, over-temperature and short-circuit protection. RS485/TCP/IP communication enables connection to environment monitoring systems for refined cabinet-level power distribution management.
2.10 Auxiliary & Customized Component System
The KITOZER single-row hot aisle containment system offers a full range of auxiliary and customized components for tailored design and production according to on-site scenarios and special user demands to achieve full-scenario adaptability and meet personalized requirements of diverse customers.
Core components:
- Air Return Static Pressure Boxes: Customized for duct air return scenarios and integrated with hot aisle tops to equalize return air pressure inside hot aisles, balancing return air volume across all cabinet positions and eliminating uneven airflow between near and far zones for superior overall heat dissipation performance. Customizable dimensions matched to on-site air volume and duct specifications, fitted with internal flow deflectors and sound-absorbing cotton for noise reduction, cutting airflow noise by 5~8dB.
- Noise Reduction Components: Including sound-absorbing cotton, silencers and shock-absorbing gaskets for reducing airflow and equipment vibration noise generated during system operation, limiting ambient noise surrounding channels to ≤60dB in compliance with computer room noise control standards and delivering a comfortable working environment for operation and maintenance staff.
- Anti-Static Components: Including anti-static grounding bars, anti-static grounding cables and anti-static floors for reliable full-system grounding with overall system grounding resistance ≤4Ω to prevent static accumulation interfering with or damaging IT equipment while safeguarding personnel personal safety.
- Customized Enclosure Structures: For irregular scenarios featuring columns, pipelines and fire protection facilities inside computer rooms, customized enclosure structural designs perfectly bypass obstacles while preserving overall system air tightness without modification to original computer room infrastructure, adapting to complex scenarios including legacy computer room retrofits.
- Heat Recovery Components: Matched for scenarios requiring hot water supply, heat recovery devices capture waste heat from high-temperature hot exhaust air inside hot aisles for hot water production and winter heating to further boost energy utilization efficiency, enabling waste heat recycling and supporting zero-carbon data center construction.
3 System Classification
KITOZER single-row hot aisle containment systems adopt multi-dimensional full-range product classification based on installation method, structural form, load grade, application scenario, enclosure mode and intelligent grade, fully covering differentiated demands of diverse customers and scenarios. All classified products adopt modular design with shared core components for flexible combination and customization according to requirements. Detailed classification descriptions are provided below:
3.1 Classification by Installation Load-Bearing Mode
The core primary product classification, categorized into floor-mounted, cabinet-supported and overhead suspension types based on system installation method and load-bearing structure, adapting to varying computer room building structures, spatial layouts and cabinet installation forms.
3.1.1 Floor-Mounted Single-Row Hot Aisle Containment System
Also named independent load-bearing single-row hot aisle containment systems, the full system main frame adopts floor-mounted installation with the entire system weight borne by the ground rather than cabinets, with cabinets serving only as one side of the enclosure system and independent structural stability. The most widely adopted mainstream variant with exceptional stability.
Core Structural Features
- Independent load-bearing structure: Vertical columns are floor-mounted and rigidly fixed to computer room floors via expansion bolts. All top and lateral loads are borne by the floor frame without imposing extra loads on cabinets, preventing cabinet deformation or tipping under excessive weight, particularly suitable for thin-profile legacy network cabinets with low load-bearing capacity.
- Exceptional structural stability: The floor frame forms an independent hexahedral enclosure structure with high overall rigidity and superior seismic performance, upgradable to Grade 8 seismic fortification via seismic reinforcement components for computer room construction in high-seismic regions.
- Extensive adaptability: Independent of cabinet dimensions, specifications and installation alignment. Even misaligned or uneven-height cabinets can be adapted via customized design, ideal for legacy computer room retrofits without cabinet replacement to drastically cut retrofit costs and cycles.
- High maintenance convenience: Flexible connections between system frames and cabinets enable independent removal of individual enclosure panels and skylights without shifting or dismantling cabinets, supporting non-interruptible operation and maintenance retrofits without downtime for in-cabinet IT equipment.
- Broad spatial adaptability: Compatible with cabinet depths ranging from 600mm to 1500mm, channel widths from 800mm to 3000mm and maximum channel lengths up to 30m to meet enclosure demands for ultra-long cabinet rows, alongside complex irregular layouts with columns and pipelines inside computer rooms.
Applicable Scenarios
- Standardized construction of new small and medium-sized data centers and enterprise computer rooms
- Energy-saving retrofits of legacy computer rooms retaining original cabinets
- Scenarios with thin-profile, low load-bearing network cabinets
- Computer room construction in regions requiring high seismic fortification grades
- Ultra-long cabinet rows and wide-channel layouts
- Complex irregular computer room layouts with internal obstacles
3.1.2 Cabinet-Supported Single-Row Hot Aisle Containment System
The full system main frame mounts directly atop cabinets for load-bearing without floor-standing columns, forming an integrated unit with cabinets to minimize floor space occupation, featuring rapid installation and ultra-short construction cycles as the preferred option for standardized new computer rooms and short cabinet rows.
Core Structural Features
- Integrated cabinet load-bearing: The system frame fastens directly to cabinet tops via special connecting fittings to form a rigid whole, with all top loads borne by cabinets without floor installation or ground drilling, fully compatible with raised floor computer rooms and layouts with cable trays on floors.
- Ultra-convenient installation & short construction cycles: All components are prefabricated in factories; on-site installation consists only of frame fastening to cabinet tops plus splicing of top plates and end doors without ground drilling or fixing, cutting on-site construction volume by over 70%. A standard 10-cabinet row system can be fully installed within 4 hours, minimizing disruption to routine computer room operation.
- Superior overall aesthetics: No floor-standing column obstructions deliver a transparent, tidy channel layout fully integrated with cabinets for outstanding visual effects, ideal for exhibition demo computer rooms and high-standard enterprise computer rooms prioritizing appearance.
- Excellent air tightness: Seamless docking between the system and cabinet tops eliminates extra gaps to reduce leakage points at the source for superior overall air tightness and hot/cold airflow isolation performance.
- Flexible capacity expansion: Supports modular expansion in single-cabinet increments; new cabinets only require splicing matching frame and top plate segments without modification to existing systems, enabling on-demand phased expansion aligned with business growth.
Applicable Scenarios
- New standardized small and medium-sized computer rooms and enterprise branch office computer rooms
- Raised floor computer rooms with ground drilling restrictions
- Short cabinet rows (≤20 cabinets) with load-bearing capacity meeting single-cabinet top static load ≥200kg
- Scenarios requiring ultra-fast deployment with tight construction cycle deadlines
- Computer rooms with strict aesthetic requirements
- Rapid construction of edge computing node small computer rooms
3.1.3 Overhead Suspended Single-Row Hot Aisle Containment System
The full system main frame mounts to computer room floor slabs or structural steel beams via suspension assemblies, with system weight borne by building structures. Suspended above cabinet rears without rigid connections to cabinets or floors, a specialized variant designed for unique niche scenarios.
Core Structural Features
- Top suspension load-bearing: Special suspension assemblies rigidly fasten to floor slabs or steel beams, with the entire system suspended without contact with cabinets or floors, imposing zero loads on cabinets or ground surfaces. Perfect for legacy computer room retrofits with cabinets lacking sufficient load-bearing capacity and floors prohibited from drilling.
- Superior seismic performance: Suspension systems are fitted with dedicated seismic brackets adopting three-way diagonal bracing seismic reinforcement design to withstand vertical and horizontal loads, achieving seismic rating Grade 8 or above to prevent system detachment or collapse under extreme operating conditions.
- Exceptional adaptability: Compatible with uneven-height, misaligned cabinets and irregular cabinet-wall spacing with flexibly adjustable suspension heights to perfectly bypass pipelines, trays and fire protection facilities inside computer rooms, particularly suited for legacy computer room retrofits and customized irregular layouts.
- Fully open bottom: No floor-standing columns create unobstructed channel bottoms without interfering with installation and maintenance of ground cable trays and raised access floors, delivering tidy computer room floors and unimpeded staff passage.
- High installation flexibility: Suspension point positions, channel heights and widths can be adjusted per on-site requirements, enabling stable installation even with irregular top building structures via customized suspension assemblies to adapt to all complex building structures.
Applicable Scenarios
- Legacy computer room retrofits with cabinets lacking sufficient load-bearing capacity to support top loads
- Raised floor/anti-static floor computer rooms prohibiting ground drilling and floor-mounted installation
- Computer rooms with extensive ground cable trays and pipelines where floor-standing columns block passage and maintenance
- Uneven-height, misaligned cabinet rows incompatible with cabinet-supported installation
- Computer rooms with adequate top installation space and load-bearing building structures
- Special industrial and customized computer room scenarios
3.2 Classification by Enclosure Structural Form
Categorized into fully enclosed, semi-enclosed and partially enclosed types based on hot aisle enclosure and cladding form, adapting to varying cooling modes, load densities and computer room scenarios with distinct energy-saving effects and maintenance characteristics.
3.2.1 Fully Enclosed Single-Row Hot Aisle Containment System
The full six-sided enclosure of the hot aisle rear zone delivers complete sealing of top, ends, sides, back and bottom surfaces to form a fully independent confined hot aisle space with 100% physical isolation between hot exhaust and the computer room cold environment, the mainstream flagship variant delivering optimal energy-saving performance and high load density compatibility as KITOZER’s standard primary product.
Core Performance Characteristics
- Ultimate air tightness: Six-sided full enclosure with all gaps blocked via specialized sealing components, overall system air leakage rate ≤0.1L/s@10Pa differential pressure and hot air capture efficiency ≥99% to fully eliminate hot and cold airflow mixing for 100% utilization of cooling capacity with industry-leading energy-saving performance.
- Ultra-high load adaptability: Supports single-cabinet power densities ranging from 3kW to 50kW, delivering perfect heat dissipation even for AI intelligent computing high-density cabinets to fully eliminate local hotspots. Computer room PUE can be reduced below 1.2 to meet the highest national green data center standards.
- Fully controllable airflow organization: The fully enclosed structure enables complete directional diversion of hot air, paired with return air static pressure boxes and air volume dampers for precise regulation of return air volume per cabinet to guarantee uniform temperature across full cabinet rows with cabinet intake air temperature deviation ≤±0.5℃.
- Broad air conditioning compatibility: Fully compatible with nearly all air conditioning unit types including in-row precision air conditioners, dedicated computer room precision air conditioners, top-mounted air conditioners and ducted air conditioners, seamlessly adapting to top/bottom air supply and top/bottom air return modes to drastically lift air conditioning COP and boost refrigeration efficiency by over 40%.
- Superior safety performance: The fully enclosed structure integrates complete fire protection linkage and environment monitoring systems for seamless connection to computer room fire protection frameworks and rapid response upon fire outbreaks to guarantee effective fire suppression. The fully enclosed structure also restricts fire spread, confining fire impacts to minimal zones.
Applicable Scenarios
- Medium-to-high density computer rooms with single-cabinet power density ≥5kW
- New large, super-large data centers and intelligent computing centers
- Computer rooms with strict PUE control and high energy conservation requirements
- Core data centers of finance, telecom operators and government authorities
- Energy-saving computer rooms adopting high-temperature return air air conditioning and free cooling systems
- Mission-critical business computer rooms requiring maximum stability for IT equipment
3.2.2 Semi-Enclosed Single-Row Hot Aisle Containment System
Also named top-sealed single-row hot aisle containment systems, primarily enclosing hot aisle tops and ends with partial side cladding and rear diversion structures for basic hot and cold airflow isolation and energy-saving effects, targeting low-power-density cabinets, computer rooms adopting top-return air conditioning and budget-limited scenarios.
Core Performance Characteristics
- Simple structure & controlled costs: Only top enclosure frames, end doors and diversion structures are required without complex side and back cladding, drastically cutting product costs alongside convenient on-site installation and short construction cycles.
- Significant basic energy-saving effects: Top enclosure and diversion capture over 80% of hot exhaust air and divert it to air conditioning return outlets to eliminate large-scale mixing of hot and cold airflows, cutting refrigeration energy consumption by 15%~25% and reducing PUE to 1.4~1.6 to satisfy basic energy-saving retrofit demands.
- Ultra-high maintenance convenience: Absence of side and back enclosure panels enables unrestricted staff access to cabinet rears for cable sorting and equipment maintenance without opening channel doors for extremely convenient operational procedures.
- Adaptation to low-load scenarios: Perfectly suited for enterprise branch and small-medium computer room low-density loads with single-cabinet power density ≤5kW to meet heat dissipation demands of most small and medium enterprise branch network computer rooms.
- High retrofit flexibility: Supports phased transformation; basic energy savings can be achieved via initial semi-enclosed system installation, with subsequent addition of enclosure panels to upgrade to fully enclosed systems as business loads rise without replacement of original components to protect upfront customer investment.
Applicable Scenarios
- Low-density enterprise and branch computer rooms with single-cabinet power density ≤5kW
- Budget-limited legacy computer rooms requiring low-cost energy-saving retrofits
- Network computer rooms and weak current rooms with frequent rear-cabinet maintenance operations
- Computer rooms equipped with top-return precision air conditioners enabling natural upward hot air flow to top return outlets
- Small-medium office, educational institution and medical building computer rooms
3.2.3 Partially Enclosed Single-Row Hot Aisle Containment System
Also named cabinet-level hot aisle containment systems, realizing partial hot aisle enclosure only for single or small groups of high-density cabinets with targeted diversion of hot exhaust air from these cabinets to air conditioning return outlets, designed to resolve isolated local hotspot issues for a small number of high-power cabinets without full cabinet row transformation, featuring low costs and ultra-rapid deployment.
Core Performance Characteristics
- Targeted resolution of local hotspots: Enclosure is limited exclusively to high-density cabinets with hotspot issues without full computer room or cabinet row transformation, delivering fast heat dissipation solutions at minimal input costs.
- Ultra-flexible deployment: Customized design for individual cabinets without modification to original computer room layouts or disruption to normal operation of other cabinets; full installation completed within only 2 hours to rapidly resolve isolated computer room hotspots.
- Ultra-low retrofit costs: Partial enclosure transformation costs only 10%~20% of full-row enclosure retrofits, delivering heat dissipation requirements for high-power cabinets with minimal investment without full replacement of computer room air conditioning systems triggered by upgrades of a small number of cabinets.
- Stackable & expandable: Additional partial enclosure units can be deployed incrementally with business growth, with multiple partial enclosure units spliceable to form full-row enclosed systems for phased, on-demand investment.
- Broad compatibility: Compatible with all mainstream cabinet brands and specifications on the market, adapting even to irregular layouts and mixed cabinet brands inside legacy computer rooms, ideal for legacy computer rooms with newly added high-power servers.
Applicable Scenarios
- Computer rooms with only a small subset of high-density load cabinets generating local hotspots, alongside majority low-density cabinets
- Legacy computer rooms with temporary additions of high-power servers and AI computing equipment requiring rapid hotspot resolution
- Budget-limited projects unable to fund full-row or full-computer room transformation
- Computer rooms with residual air conditioning capacity insufficient to boost cooling power via overall transformation, requiring only isolated hotspot resolution
- Edge computing nodes and small computer rooms housing single high-density equipment
3.3 Classification by Load Power Density Grade
Categorized into basic, standard, high-density and ultra-high-density variants based on supported single-cabinet IT load power density, with targeted optimization of product structures, air tightness, supporting components and compatible air conditioning systems to perfectly match diverse load power demands.
3.3.1 Basic Grade Single-Row Hot Aisle Containment System
Supported load range: Single-cabinet power density 1kW~3kW Core positioning: For low-density network computer rooms, weak current rooms and small branch computer rooms to deliver basic hot and cold airflow isolation alongside fundamental heat dissipation and energy-saving demands with controlled costs and rapid deployment.
Core Configuration & Characteristics
- Cabinet-supported semi-enclosed structure with frames fabricated from 1.5mm cold-rolled steel or entry-level aluminum alloy profiles to meet basic load-bearing and structural stability requirements
- Fixed top sealing panels and entry-level fire protection linked flip skylights delivering fundamental fire linkage functionality
- Standard double-leaf swing end doors fitted with mechanical locks without complex access control systems
- Basic environment monitoring package only supporting fundamental temperature, humidity and fire status measurement without advanced intelligent linkage functions
- Compatible with standard computer room cabinet air conditioners and wall-mounted precision air conditioners to meet heat dissipation demands of low-density loads
- Low product costs and convenient rapid deployment delivering over 15% refrigeration energy savings to satisfy basic energy conservation and heat dissipation requirements
3.3.2 Standard Grade Single-Row Hot Aisle Containment System
Supported load range: Single-cabinet power density 3kW~10kW Core positioning: The most widely deployed flagship KITOZER model targeting mainstream scenarios including small-medium enterprise, government agency, medical and educational institution computer rooms, balancing optimal cost-performance, energy-saving performance, stability and intelligence.
Core Configuration & Characteristics
- Floor-mounted or cabinet-supported fully enclosed structure with frames fabricated from high-strength 6063-T5 aluminum alloy or 2.0mm cold-rolled steel for robust structural load-bearing capacity
- Fixed top sealing panels paired with fire protection linked flip skylights seamlessly connected to computer room fire protection systems with response time ≤0.5s fully complying with fire code specifications
- Standard double-leaf swing end doors fitted with hydraulic door closers and mechanical anti-theft locks, with optional electronic locks and access control systems
- Complete integrated environment monitoring system delivering full measurement of temperature, humidity, differential pressure, smoke, access control and water leakage, alongside intelligent linkage with air conditioning and fire protection systems
- Compatible with in-row and dedicated computer room precision air conditioners to match mainstream enterprise computer room load demands, cutting refrigeration energy consumption by over 30% and reducing PUE below 1.3
- Fully modular design supporting flexible capacity expansion balancing stability and economy as the primary selection for most new computer room projects
3.3.3 High-Density Grade Single-Row Hot Aisle Containment System
Supported load range: Single-cabinet power density 10kW~30kW Core positioning: For medium-to-high density load scenarios including AI intelligent computing computer rooms, high-performance computing rooms, core telecom operator computer rooms and financial data centers, optimizing sealing performance, airflow organization and air return systems to guarantee stable operation of high-density loads and maximize energy conservation.
Core Configuration & Characteristics
- Floor-mounted fully enclosed structure with thickened high-strength aluminum alloy or cold-rolled steel frames delivering enhanced overall structural rigidity and seismic performance, paired with return air static pressure boxes and diversion systems to optimize airflow organization
- High-air-tightness fixed top sealing panels paired with high-response redundant fire protection linked flip skylights with opening angle ≥95° and response time ≤0.3s fitted with redundant drive mechanisms to guarantee absolute reliability of fire linkage
- Heavy-duty double-leaf sliding or swing end doors fitted with access control systems, facial recognition terminals and door magnetic sensors for high-grade personnel access management, alongside optional detachable dedicated equipment transport doors
- High-end intelligent environment monitoring system delivering refined cabinet-level measurement of temperature, humidity, differential pressure, smoke, access control, water leakage, air conditioning operating status and power distribution, alongside AI intelligent early warning and adaptive linkage control with seamless connection to computer room BMS systems for unattended operation and maintenance
- Matched with high-density intelligent cabinets, intelligent PDUs and auxiliary cabinet-level heat dissipation units, compatible with in-row air conditioners, row-level air-cooled air conditioners and rear door water cooling heat sinks to perfectly meet high-density load heat dissipation demands and fully eliminate local hotspots, cutting refrigeration energy consumption by over 35% and reducing PUE below 1.25
- All components fabricated from high-flame-retardant, high-temperature-resistant materials capable of stable long-term operation under 45℃~50℃ return air temperatures, compatible with high-temperature return air energy-saving air conditioning systems for further energy efficiency gains
3.3.4 Ultra-High-Density Grade Single-Row Hot Aisle Containment System
Supported load range: Single-cabinet power density 30kW~50kW Core positioning: Customized fully enclosed structures and airflow organization systems for ultra-high-density load scenarios including supercomputing centers, AI large model training computer rooms and liquid cooling auxiliary air cooling computer rooms to guarantee stable, safe operation of ultra-high-density loads as the top-tier premium airflow containment solution in the industry.
Core Configuration & Characteristics
- Customized floor-mounted fully enclosed hexahedral enclosure structure adopting high-strength steel-aluminum composite frames with static load capacity ≥1000kg/m, top-tier industry standards for structural strength, seismic performance and air tightness, compatible with liquid cooling + air cooling composite heat dissipation scenarios
- Customized integrated return air static pressure boxes paired with fully sealed top plates and redundant fire protection linked skylight systems with dual redundant drive design supporting three opening modes (fire signal, manual, emergency) for reliable opening under extreme conditions, alongside built-in pressure relief valves to balance channel internal pressure
- Customized heavy-duty fireproof/explosion-proof end doors meeting Grade A fire door standards, fitted with high-security facial recognition access control systems and emergency evacuation push bar locks for full personnel access control alongside compliance with fire evacuation and fire resistance requirements
- Industrial-grade redundant architecture environment monitoring system delivering chip-level temperature measurement, full-channel airflow organization simulation monitoring and precise differential pressure control with redundant linkage to fire protection systems, millisecond-level alarm response and full intelligent linkage with cooling and power distribution systems to adapt to unattended computer room operation
- Matched with dedicated ultra-high-density cabinets, liquid cooling auxiliary heat dissipation units, intelligent busbar power distribution systems and precise air return control systems, compatible with immersion liquid cooling, cold plate liquid cooling + air cooling backup and rear door water cooling heat sinks to guarantee stable operation of 50kW single-cabinet ultra-high-density loads without local hotspots
- Optional waste heat recovery modules capturing waste heat from high-temperature hot exhaust air for recycling to further boost energy utilization efficiency, enabling PUE ≤1.15 to meet national zero-carbon data center construction standards
- All products fully customized with one-on-one CFD fluid simulation modeling for load types, computer room layouts and cooling modes to optimize system structures and diversion schemes for optimal scenario matching
3.4 Classification by Intelligent Grade
Categorized into basic, standard intelligent and full intelligent variants based on system intelligence level and control functionality, covering all operation and maintenance management demands from fundamental monitoring to full intelligent unattended operation.
3.4.1 Basic Grade Single-Row Hot Aisle Containment System
Intelligence Level: Entry Basic Grade Core functionality: Only fundamental physical enclosure and fire linkage capabilities without complex intelligent monitoring and control functions, featuring simple structures, controlled costs and convenient operation.
Core Configuration
- Only basic fire protection linked controllers delivering linkage between fire signals and skylights without additional intelligent control functions
- No integrated environment monitoring system, only pre-reserved sensor mounting positions with compatibility for connection to existing on-site computer room environment monitoring systems
- Lighting systems controlled manually without intelligent sensing functionality
- Access control systems adopting purely mechanical locks without electronic access control or personnel management functionality
- No air conditioning linkage, intelligent early warning or remote management capabilities
Applicable Scenarios: Small budget-limited computer rooms, legacy computer room retrofits, and projects with fully equipped existing computer room environment monitoring systems requiring only additional physical enclosure structures.
3.4.2 Standard Intelligent Grade Single-Row Hot Aisle Containment System
Intelligence Level: Standard Intelligent Grade Core functionality: Integrated complete environment monitoring system delivering real-time measurement of environmental parameters, equipment status monitoring, intelligent alarms, fire linkage and air conditioning linkage as core intelligent capabilities, supporting local and remote management as the mainstream intelligent variant.
Core Configuration
- Standard industrial-grade environment monitoring host delivering real-time measurement, data storage and historical query of temperature, humidity, differential pressure, smoke and door magnetic signals
- Intelligent alarm functionality triggering local audible and visual alarms, SMS and email notifications to alert operation and maintenance staff upon threshold breaches
- Integrated intelligent lighting systems with human infrared sensing control for automatic activation upon personnel entry and auto-shutdown post-departure to save energy
- Standard electronic access control systems supporting card swiping and password entry with personnel access record and permission management, linkable with video surveillance systems
- Seamless linkage with computer room fire protection and precision air conditioning systems for automatic skylight opening upon fire alarms and real-time air conditioning parameter adjustment upon abnormal temperature/humidity
- Support for local WEB management and remote access enabling real-time remote status viewing, parameter configuration and equipment control
Applicable Scenarios: Most small-medium enterprise, government agency, medical and educational institution computer rooms requiring intelligent operation and maintenance to reduce operational difficulty and labor workloads.
3.4.3 Full Intelligent Grade Single-Row Hot Aisle Containment System
Intelligence Level: Full AI Intelligent Grade Core functionality: AIoT full-intelligent architecture integrated with edge computing units delivering refined full-parameter measurement, AI intelligent early warning, adaptive intelligent linkage, digital twin visualization and full unattended operation functionality, the top-tier industry intelligent solution for large data centers, unattended computer rooms and mission-critical business computer rooms with strict intelligent operation, safety control and compliance requirements.
Core Configuration
- Redundant architecture industrial-grade environment monitoring host integrated with AI edge computing units delivering cabinet and U-unit level refined parameter measurement with maximum sampling frequency of 100ms per reading for real-time collection, analysis and storage of full-scenario data
- AI intelligent early warning functionality leveraging big data analysis to predict equipment faults and environmental trend changes in advance, shifting from passive to proactive operation and maintenance with fault early warning accuracy ≥95%
- Adaptive intelligent linkage automatically adjusting air conditioning operating parameters, return air volume and skylight status according to IT load variations, environmental temperature/humidity and outdoor meteorological parameters to deliver maximum energy savings without compromising equipment safety, cutting an additional 10%~15% energy consumption compared with standard intelligent grade variants
- Standard digital twin visual management platform constructing a 1:1 digital twin model of the hot aisle system for real-time display of internal temperature/humidity distribution, airflow organization, equipment operating status and personnel access records, supporting 3D visual roaming, fault positioning and emergency disposal guidance to drastically boost maintenance efficiency
- High-security facial recognition access control systems supporting multi-mode access including facial scan, fingerprint, card swiping, password and NFC with hierarchical personnel permission management, black/white lists, duress alarms and anti-tailgating functionality, linkable with computer room video surveillance systems to trigger automatic camera recording upon door opening and personnel trajectory tracking
- Seamless connection with computer room BMS building management systems and DCIM data center infrastructure management systems enabling full data interconnection alongside compatibility with provincial and national data center energy consumption monitoring platforms to meet government regulatory requirements
- Support for mobile APP and mini-program management enabling real-time remote viewing, control, alarm push and work order management for mobile operation and maintenance
- Complete log and audit management automatically recording all operations, alarms, personnel access and equipment operating data with tamper-proof records to satisfy compliance audit demands of finance, telecom operator and government industries
Applicable Scenarios: Large data centers, supercomputing centers, AI intelligent computing centers, financial core data centers, telecom operator core computer rooms and fully unattended computer rooms with strict requirements for intelligent operation and maintenance, safety control and compliance auditing.
3.5 Specialized Classification by Application Scenario
KITOZER develops customized single-row hot aisle containment systems tailored to unique demands of diverse industries and scenarios for precise scenario matching, core specialized variants described below:
3.5.1 Financial Industry Specialized Single-Row Hot Aisle Containment System
Customized to meet financial industry requirements for high safety, reliability and compliance auditing, core characteristics:
- Compliant with financial industry data center construction specifications with high-grade physical security protection, access control and audit functionality
- Full redundant architecture design for fire protection linkage, environment monitoring and power supply systems eliminating single points of failure to guarantee business continuity
- Complete disaster recovery emergency response plans meeting financial industry non-stop business continuity requirements
- All products pass national authoritative testing with full qualification certification packages to satisfy financial industry compliance audit standards
3.5.2 Telecom Operator Specialized Single-Row Hot Aisle Containment System
Customized to meet telecom operator demands for ultra-long cabinet rows, high load density and unified multi-site remote management, core characteristics:
- Support for maximum 30m ultra-long cabinet rows enabling unified full-row enclosure and control
- Seamless connection to telecom operator environment monitoring platforms and network management systems for unified remote management across multiple sites
- Adapted to telecom operator computer room raised floor and overhead cable tray layouts with customized wiring and enclosure structure design
- Superior reliability and extended service life to meet 7×24-hour non-stop operation requirements of telecom operator computer rooms
3.5.3 Edge Computing Specialized Single-Row Hot Aisle Containment System
Customized for edge computing node small-space, rapid deployment, unattended operation and complex ambient conditions, core characteristics:
- Ultra-compact design adapting to ultra-short row layouts of 2~6 cabinets, supporting single-cabinet minimum enclosure
- Fully prefabricated factory pre-commissioned design requiring only simple on-site splicing for commissioning and operation within 1 day maximum deployment cycle
- Integrated all-in-one environment monitoring and remote management system supporting unattended operation with automatic fault alarms and remote disposal
- Wide-temperature operating design enabling stable operation under complex ambient conditions of edge computer rooms
3.5.4 Legacy Computer Room Retrofit Specialized Single-Row Hot Aisle Containment System
Customized for legacy computer room retrofit demands of retaining original equipment, irregular layouts, non-interruptible construction and controlled budgets, core characteristics:
- Fully modular customized design compatible with mixed original cabinet brands, specifications and misaligned layouts without cabinet replacement to drastically cut retrofit costs
- Tool-free quick-release design without welding, cutting or drilling enabling non-stop construction and transformation without disruption to routine computer room business operation
- Support for phased transformation and staged investment; core hotspot zones can be upgraded first with subsequent expansion without replacement of original components to protect upfront customer investment
- Controlled transformation costs delivering over 20% PUE reduction post-retrofit with payback period ≤3 years
3.5.5 Medical Industry Specialized Single-Row Hot Aisle Containment System
Customized to meet medical industry requirements for 7×24-hour non-stop operation, high reliability and safety, core characteristics:
- Compliant with medical industry data center construction specifications with high-grade safety protection and redundant design to guarantee stable operation of core medical systems including HIS, LIS and PACS
- Low-noise design limiting overall system operating noise ≤55dB to avoid noise interference with medical environments for computer rooms adjacent to medical technology buildings
- Complete emergency disposal contingency plans ensuring system faults do not disrupt core medical equipment operation to meet medical business continuity requirements
- All materials adopt medical-grade eco-friendly, flame-retardant and mold-resistant formulations adapting to sanitary hospital environments
4 System Schematic Diagrams
KITOZER single-row hot aisle containment system schematic diagrams form core technical documents designed based on thermodynamics and fluid mechanics principles integrating system structures, functional logic, control flows to fully display airflow organization paths, equipment connection relationships, control linkage logic and electrical operating principles, serving as core references for system design, installation, commissioning and operation & maintenance. This chapter provides comprehensive breakdown explanations across four core dimensions: airflow organization schematics, fire protection linked control schematics, environment monitoring system schematics and electrical control schematics.
4.1 Core System Airflow Organization Schematic
The core of the KITOZER single-row hot aisle containment system lies in complete isolation and directional circulation of hot and cold airflows. Airflow organization schematics represent the foundational core schematic of the full system, fully displaying the complete airflow circulation path from cold air supply by air conditioning units through IT equipment heat exchange to hot exhaust recirculation back to air conditioning units, clarifying airflow status, pressure variations and temperature changes at each stage to guarantee scientific, rational airflow organization design.
4.1.1 Standard Grade Single-Row Hot Aisle Containment Airflow Organization Schematic
Complete core airflow circulation path (4 primary stages, 12 key nodes):
- Stage 1: Cold Air Delivery & Diffusion (Nodes 1~4) Node 1: Precision air conditioning supply air segment. Air conditioning units deliver processed low-temperature cold air (standard supply air temperature 18℃~22℃) through air outlets into the open cold environment of the computer room. Node 2: Computer room cold environment diffusion. Under air conditioning supply pressure and overall computer room positive pressure, cold air uniformly diffuses across the entire computer room space to form a stable uniform positive-pressure cold environment with overall cold environment temperature uniformity controlled within ±1℃ without localized low/high temperature zones. Node 3: Cabinet front air intake segment. Negative pressure generated by built-in cooling fans of IT equipment draws low-temperature cold air from the computer room cold environment through high-airflow mesh front cabinet doors into cabinet interiors. Cabinet front door ventilation rate ≥75% with intake air resistance ≤5Pa for unobstructed cold air intake without throttling losses. Node 4: In-cabinet cold air distribution segment. Upon entering cabinet interiors, cold air distributes evenly to IT equipment intake ports at every U-unit via vertical in-cabinet air ducts to guarantee adequate, uniform low-temperature cold air supply for all IT equipment without uneven air volume distribution.
- Stage 2: IT Equipment Heat Exchange Stage (Nodes 5~6) Node 5: Internal IT equipment heat exchange segment. Low-temperature cold air flows through heat-generating components including CPUs, GPUs, memory modules and mainboards inside IT equipment for forced convection heat exchange, absorbing heat from components to raise air temperature and complete heat exchange. Node 6: Cabinet rear hot air exhaust segment. High-temperature hot exhaust air post heat exchange is pushed out from cabinet rears by IT equipment fans into the confined hot aisle space constructed by the single-row containment system, with standard exhaust air temperature ranging from 35℃~45℃ and up to 50℃~60℃ under high-density load conditions.
- Stage 3: Confined Hot Aisle Heat Collection & Diversion Stage (Nodes 7~9) Node 7: Confined hot aisle heat collection segment. All high-temperature hot exhaust air discharged from cabinet rears fully enters the fully enclosed hot aisle space, fully trapped by the containment enclosure without leakage or diffusion to prevent mixing with cold air in the computer room cold environment. A stable negative pressure of 5~10Pa is maintained inside the hot aisle to guarantee directional hot air flow without reverse recirculation. Node 8: Uniform airflow equalization inside hot aisles. Upon entering the hot aisle, high-temperature hot exhaust air equalizes via diversion structures and return air static pressure boxes to deliver uniform return air volume across the full cabinet row length, eliminating uneven airflow with high return air volume near air conditioning outlets and insufficient return air volume at far ends, with exhaust air resistance deviation ≤3Pa across all cabinets. Node 9: Directed hot air diversion segment. Driven by negative pressure at air conditioning return outlets, high-temperature hot exhaust air inside the hot aisle flows directionally toward air conditioning return outlets through top return air interfaces, ducts and static pressure boxes with unobstructed diversion paths free of throttling and eddy currents and airflow transport resistance ≤10Pa to guarantee smooth delivery of hot exhaust air.
- Stage 4: High-Temperature Return Air Cooling Stage (Nodes 10~12) Node 10: Air conditioning return air segment. 100% of high-temperature hot exhaust air enters precision air conditioning return outlets without bypass leakage. Return air temperature rises by 10℃~15℃ compared with traditional open computer rooms, drastically lifting air conditioning compressor COP and boosting refrigeration efficiency by over 30%. Node 11: Internal air conditioning cooling segment. High-temperature return air enters air conditioning units and undergoes heat exchange with refrigerants via evaporators to transfer heat to refrigerants, cooling high-temperature