KITOZER Surge Arrester: 10kV Metal Oxide Without Gaps

The KITOZER 10kV metal oxide surge arrester (MOA) protects medium-voltage equipment from lightning and switching overvoltages. Built with zinc oxide varistor blocks and no series gaps, the arrester conducts surge energy to earth rapidly when overvoltage appears, then returns to a high-impedance state that allows normal system voltage to continue uninterrupted. Gapless metal oxide design gives faster response and simpler construction than old gapped silicon carbide arresters. KITOZER supplies the arrester in porcelain-housed and polymer-housed versions for 10kV switchgear, transformers, cable terminations, and overhead line insulation coordination.

Technical Specifications

Rated voltage 17kV, continuous operating voltage 13.5kV, nominal discharge current 5kA, high current impulse 100kA, residual voltage at 5kA lightning impulse 50kV, power frequency sparkover none (gapless). Zinc oxide varistor elements sealed in porcelain or silicone rubber housing. Leakage current monitoring terminal optional. Housing pollution class suitable for indoor or outdoor service. Conforms to IEC 60099-4 and GB 11032 standards. Mounting: horizontal or vertical, line connection at top, earth connection at bottom.

Applications

The KITOZER 10kV surge arrester is installed at the incoming of 10kV switchgear, on transformer bushings, at cable terminals, and on the line side of ring main units. It protects 10/0.4kV distribution transformers from lightning surges that travel down overhead lines, which is the most common cause of transformer insulation failure. In industrial plants it protects motor feeders, capacitor banks, and instrument transformer secondary circuits from switching surges generated by vacuum breakers and contactors.

In solar and wind farms, arresters protect the 10kV collection switchgear at each inverter station and at the substation. On overhead distribution lines, pole-mounted arresters reduce flashover rates on lines exposed to lightning. At data center and hospital 10kV incomers, arresters work together with lower-voltage surge protective devices on the LV side to create a coordinated protection scheme. The arrester is normally fitted as close as possible to the equipment it protects, because lead length adds inductance and raises the residual voltage seen by the protected equipment.

Key Advantages

The gapless metal oxide design has no sparkover delay, so it clamps overvoltages almost instantly. Zinc oxide blocks have excellent nonlinear volt-ampere characteristics, drawing negligible leakage current at normal operating voltage yet conducting high surge currents when voltage rises. The silicone rubber housed version is light, shatterproof, and resistant to pollution tracking, making it ideal for outdoor and coastal installations. KITOZER arresters are factory-tested for residual voltage, leakage current, and pressure relief, and carry a standard warranty against manufacturing defects.

The optional leakage current monitor gives maintenance staff a simple way to trend arrester health without taking equipment out of service, because aging varistors show rising resistive leakage current before failure. This predictive approach reduces unplanned outages. Standardized mounting brackets fit most 10kV switchgear bus supports, and the arrester can be retrofitted into existing panels with minimal modification.

Installation and Maintenance

Install the arrester vertically, line terminal upward, as close as possible to the protected equipment. Keep connecting leads short and straight to minimize series inductance. Torque line and earth connections to the specified value and confirm that the earth lead runs directly to the station earth bar without daisy-chaining through other equipment. Check that the housing is not cracked and that the discharge current counter or monitor is connected.

Inspect the arrester annually for surface contamination, cracks, or flashover marks. Measure total leakage current and, where a monitor is fitted, compare readings against the commissioning baseline. If leakage rises sharply or the monitor indicates an internal fault, replace the arrester immediately. After a nearby lightning strike that the arrester survived, inspect it for damage even if no external sign is visible. Keep the earth resistance within the design value, because high earth resistance raises the residual voltage seen by protected equipment.

KITOZER offers the 10kV surge arrester in a range of rated voltages to match 6kV, 10kV, and 12kV system nominal voltages, and with discharge currents from 5kA to 10kA depending on the lightning exposure of the site. It can be supplied in porcelain or silicone rubber housing, and with or without a discharge counter and leakage monitor. When ordering, specify the system maximum voltage, the required discharge current class, the housing material, and whether a monitor is needed. KITOZER provides factory test data for residual voltage and leakage current. Spare arresters of the same rating are recommended as critical spares, because a failed arrester leaves equipment unprotected until replacement. The arrester is normally selected so that its continuous operating voltage exceeds the maximum system voltage, and its residual voltage is below the basic insulation level of the protected transformer or switchgear by a safe margin. KITOZER engineering supports insulation coordination studies for new substations and for retrofit projects where the existing arrester rating may be inadequate.

Price

From $120/pc. Contact +86 13922289957 for surge arrester pricing and BIL coordination.