KITOZER
KITOZER

KITOZER Surge Arrester: 35kV Station Class For Substation

The KITOZER 35kV station-class surge arrester protects 35kV substation equipment, power transformers, and circuit breakers from lightning and switching overvoltages. Station-class arresters use higher-energy zinc oxide blocks and a larger discharge rating than distribution-class units, because substation equipment represents a much higher capital investment and a single insulation failure can cause a multi-day outage. KITOZER supplies the arrester in porcelain and polymer housed versions, with graded external insulation for polluted environments and integrated discharge counters for condition monitoring.

Technical Specifications

Rated voltage 51kV, continuous operating voltage 40.5kV, nominal discharge current 10kA, high current impulse 100kA, long duration current impulse 200A, residual voltage at 10kA lightning impulse 134kV, residual voltage at switching impulse 106kV. Zinc oxide gapless design, pressure relief class, energy handling per IEC 60099-4. Housing: porcelain or silicone rubber, with optional creepage extension for heavy pollution. Discharge counter and leakage current monitor optional. Mounting: line-to-earth at transformer and breaker bays.

Applications

The KITOZER 35kV station arrester is installed at the 35kV bus, at the transformer incoming bay, and at the line entrance to the substation. It coordinates insulation levels across the substation by clamping lightning surges that enter on the overhead line to a voltage below the basic insulation level of transformers and breakers. In large industrial plants and solar farms it protects the step-up transformer and the 35kV switchgear from both external lightning and internal switching transients caused by breaker operation.

Modern substation earthing design places arresters directly at the transformer terminal to minimize lead length, and at the line entrance to intercept surges before they reach equipment. The arrester is also used on capacitor bank terminals to limit switching overvoltages when the bank is energized or de-energized. Where the substation is connected by underground cable, arresters on both line and cable sides provide coordinated protection across the transition point.

Key Advantages

Station-class arresters have higher energy absorption capacity and lower residual voltage than distribution-class units, giving a wider protection margin for expensive transformer insulation. The gapless design responds instantly to both lightning and switching surges with no follow current after the surge. Polymer housed units are lightweight, shatterproof, and self-cleaning on rain-exposed surfaces, reducing the risk of porcelain failure and injury. KITOZER factory tests every arrester for residual voltage and leakage current before shipment.

The discharge counter and leakage monitor allow condition-based maintenance: staff can count surge events and trend leakage current over years of service, replacing arresters only when they show signs of aging rather than on a fixed schedule. Standard mounting dimensions allow replacement of most existing station-class arresters without changing the support steel. Graded creepage insulators suit coastal, industrial, and desert-pollution environments.

Installation and Maintenance

Mount the arrester on a rigid support as close as possible to the protected transformer bushing, using the shortest possible connecting lead. Confirm the arrester rating matches the system maximum voltage and the earthing system neutral treatment. Torque all connections, connect the discharge counter in the earth lead, and verify station earth resistance is within design limits. After installation, record the initial leakage current and counter reading as the commissioning baseline.

During routine inspection, read the discharge counter and leakage monitor, and compare trends to the baseline. Inspect the housing for cracks, tracking, or shed damage. In heavily polluted sites, wash the insulators during dry seasons. If leakage current rises sharply or the counter shows repeated high-current discharges, schedule replacement of the arrester. Never energize a substation with a cracked or leaking arrester, because internal pressure buildup can cause violent failure.

Price

From $380/pc. Contact +86 13922289957 for station arrester coordination and pricing.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com

Scroll to Top