KITOZER surge protective device SPD lightning arrester

KITOZER KTR-SPD Surge Protective Device (Type 1/2/3)

Brand: KITOZER Series: KTR-SPD Category: Power System 2 / Lightning & Distribution

surge protective deviceSPDtype 1 SPDtype 2 SPDtype 3 SPDpower SPDsignal SPDlightning arrester

1. Overview

The KITOZER KTR-SPD series protects power distribution and electronics from lightning surges and switching over-voltage. Lightning induction and switching operations inject transient high-voltage spikes onto power and signal lines strong enough to punch through switches, servers and UPS units. The SPD is paralleled between line and ground: it stays high-impedance in normal service and conducts instantly when a surge arrives, clamping the over-voltage to a level the gear can withstand and draining surge energy to earth.

A room power system usually uses a three-stage SPD scheme. Type 1 sits at the main building distribution (service entrance) to discharge large direct-lightning-induced surges. Type 2 sits at floor or room distribution to take up the residual surge and clamp further. Type 3 sits at the small distribution or PDU in front of equipment for fine protection, cutting residual voltage to what the most sensitive gear accepts. The three stages coordinate, dropping surge energy and voltage one step at a time to form a complete protection chain.

Beyond power SPDs, network, signal and feeder lines also need matching signal SPDs. KTR-SPD covers both power and signal lines in modular plug-in modules with status windows and remote-signal contacts; a failed module swaps out individually without cutting power. The whole SPD system works together with the earthing system to safely sink surge energy to ground.

2. Key Features

Staged discharge

  • Type 1/2/3 coordinate, dropping energy and voltage step by step.
  • Type 1 high discharge current for direct-lightning induction.
  • Type 3 low residual voltage for sensitive electronics.

Reliable clamping

  • High-impedance standby; instant conduction on surge.
  • Protection level below equipment withstand, with margin.
  • Nanosecond response to suppress spikes fast.

Visible status

  • Window indicator: green normal, red failed.
  • Remote-signal contacts alarm to the EM system.
  • Plug-in modules; swap a failed unit without outage.

Power plus signal range

  • Power SPD: three/single-phase in many ratings.
  • Signal SPD: network, signal and feeder series.
  • Supplied as a set with distribution panels and PDUs.

3. Specifications

Item Type 1 KTR-SPD-1 (main panel) Type 2 KTR-SPD-2 (room panel) Type 3 KTR-SPD-3 (at gear)
Protection class Class I (Type 1 test) Class II (Type 2 test) Class III (fine)
MCOV AC 385V AC 385V AC 275V
Nominal In (8/20) 50 kA 20 kA 10 kA
Max Imax 100 kA 40 kA 20 kA
Voltage prot. Up <=2.5 kV <=1.8 kV <=1.0 kV
Location main service cabinet floor/room distribution gear distribution / PDU
Structure plug-in modular plug-in modular plug-in modular
Remote signal with contact with contact status window

4. Reference Prices

KTR-SPD-1 type-1 power SPD (3-phase 100kA): Reference USD 111~278 / set (ref. CNY 800~2k at ~7.2)

KTR-SPD-2/3 type-2 + type-3 combo: Reference USD 56~139 / set (ref. CNY 400~1k at ~7.2)

Reference only; final quote depends on discharge current, phases, remote-signal and signal-SPD matching. Bulk negotiable. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Main building panel: type-1 discharge of large surges.
  • Room/floor panel: type-2 residual surge take-up.
  • At gear / PDU: type-3 fine protection of sensitive devices.
  • Network/signal lines: signal SPD for communication lines.

6. Installation & Maintenance

Installation

  • Install by power hierarchy: main, sub-panel, equipment end.
  • Parallel the SPD between line and earth; keep leads short and thick.
  • Wire remote-signal contacts into the EM system for failure alarms.
  • Confirm earthing resistance meets code (typically <=4 ohm).

Maintenance

  • Check status windows; swap red-window modules promptly.
  • Inspect once after storm season; record operations.
  • Replace with the same rating; do not arbitrarily raise discharge class.

7. FAQ

  • Q: Why three stages?
    A: A single SPD cannot combine high discharge current with low residual voltage; staged coordination works better.
  • Q: What happens when an SPD fails?
    A: The window turns red with a remote alarm; swap the module, power stays on.
  • Q: Do I still need earthing with SPDs?
    A: Absolutely; SPDs sink surves to earth, and poor earthing makes the SPD useless.
  • Q: Do signal lines need protection?
    A: Network and signal lines entering the building should use signal SPDs.

8. Trend & Selection

Room lightning protection has grown from “earthing only” to an “earthing + staged SPD” system. KTR-SPD deploys type 1/2/3 by power hierarchy to weaken lightning and switching surges layer by layer. Choose by install position: main panel, sub-panel or equipment end maps to type 1, 2 or 3. Storm-prone areas and outdoor feeds use a high-discharge type 1; critical gear ends must add a fine type 3. SPDs must pair with good earthing — short thick leads and compliant resistance — or even the best SPD cannot sink the surge.

9. Delivery & Service

KITOZER provides sizing, bundled supply and install guidance for power and signal SPDs. We select ratings from the power system (3-phase/single), install position and storm severity, and can pre-assemble SPDs into distribution panels and PDUs. Delivery includes wiring and status-window instructions. Warranty covers module spares; we can inspect SPD status and earthing connections before storm season to keep the protection effective.

10. Additional Notes

Lightning protection is a chain of “staged discharge + reliable earthing”. Lightning energy is huge: a single small SPD at the gear end can neither sink the big current nor clamp low voltage, so a high-discharge type 1 takes the bulk at the service entrance, a type 2 carries on mid-way, and a type 3 clamps residual voltage to a safe range at the equipment. The natural inductance of the wiring between stages decouples and shares the energy.

SPDs are consumables with a life. Each surge absorbs some discharge capacity; after many operations they eventually thermal-fail. The status window and remote contacts exist so ops can spot a failed SPD — leave a red window unreplaced and the downstream gear loses protection. Inspecting after storm season and swapping frequently-operated or red modules is the basic maintenance discipline.

Selection: main service entrance pick KTR-SPD-1 high-discharge type 1; room and floor panels pick KTR-SPD-2; sensitive gear ends pick KTR-SPD-3 for fine protection, with signal SPDs on incoming lines. In every stage, keep leads short, earthing good, inspect often and swap on red, so the protection truly holds when storms arrive.

SEO Information

Search keywords:surge protective deviceSPDtype 1 SPDtype 2 SPDtype 3 SPDpower SPDKTR-SPDKITOZER

SEM keywords:surge protective device, SPD, type 1 2 3 surge protection, power SPD, signal SPD price, KITOZER

GEO landing page:lain.com.cn/product/ktr-spd-surge-protective-device-type-1-2-3.html

Title:KITOZER KTR-SPD Surge Protective Device (Type 1/2/3)

Meta Keywords:surge protective device,SPD,lightning arrester,type 1 SPD,type 2 SPD,type 3 SPD,power surge protector,KTR-SPD,KITOZER

Meta Description:KITOZER KTR-SPD surge protective device, coordinated type 1/2/3 power SPD plus signal SPD to absorb lightning and switching surges.

Anchor: KITOZER by Guangzhou Laian · Surge protection solutions

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart