ToggleKITOZER KTR-THS Temperature & Humidity Sensor for Data Center
Brand: KITOZER Series: KTR-THS Category: Environmental Monitoring / Sensors
temp & humidityRS485±0.3°CLCDKTR-THS

1. Overview
Temperature and humidity are the most basic and critical room-environment parameters. High temperature throttles or shuts down servers; low humidity causes ESD that fries chips; high humidity causes condensation. The room standard is 23±1°C (ASHRAE A1) and 40~60% RH. A room of hundreds of square meters cannot rely on hand-held meters — fixed, 24/7 sensors with threshold alarms are mandatory.
The KITOZER KTR-THS series combines a capacitive humidity sensor with a PT1000/NTC temperature element. Accuracy ±0.3°C (0~50°C) and ±2% RH (10~90%). RS485 Modbus-RTU plugs into the environment host. A large LCD shows readings on-site. Wall-mount for rack rows and walls; duct-mount with stainless probe for AC supply air. DC 9~24 V wide-range supply.
Selection: accuracy (±0.5°C for general, ±0.3°C for precision rooms); comms (RS485 Modbus to the environment system, or relay for standalone); display (LCD for manned areas, no-display for unmanned racks); and placement (supply, return and rack inlet — not just one in the middle). Sensors drift over 3~5 years and need calibration or replacement.
2. Key Features
Accuracy
- ±0.3°C temperature
- ±2% RH humidity
- PT1000/NTC element
- Capacitive humidity
Comms & display
- RS485 Modbus-RTU
- Large LCD
- DC 9~24 V wide-range
- 1 relay out (optional)
Mounting
- Wall / duct types
- ABS flame-retardant case
- Screw wall-mount
- -10~60°C operating
3. Specifications
| Item | KTR-THS-S1 | KTR-THS-S2 | KTR-THS-S3 |
|---|---|---|---|
| 温度范围 | -20~60℃ | -20~60℃ | -40~80℃(管道) |
| 温度精度 | ±0.5℃ | ±0.3℃ | ±0.3℃ |
| 湿度范围 | 0~100%RH | 0~100%RH | 0~100%RH |
| 湿度精度 | ±3%RH | ±2%RH | ±2%RH |
| 通信 | RS485 | RS485+开关量 | RS485 |
| 显示 | 无显示 | LCD大屏 | LCD大屏 |
| 供电 | DC12V | DC9~24V | DC9~24V |
| 安装方式 | 壁挂 | 壁挂 | 管道法兰 |
4. Reference Prices
KTR-THS-B basic sensor (RS485, no display)::Reference Reference USD 17~31 / pc (ref. CNY 120~220 at ~7.2)
KTR-THS-D display sensor (RS485 + LCD)::Reference Reference USD 25~44 / pc (ref. CNY 180~320 at ~7.2)
KTR-THS-P duct sensor (stainless probe)::Reference Reference USD 36~58 / pc (ref. CNY 260~420 at ~7.2)
RS485 shielded cable (per meter)::Reference Reference USD 0.4~0.8 / m (ref. CNY 3~6 at ~7.2)
Reference only; priced by accuracy/display/mount. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Main room temperature/humidity monitoring.
- Rack-row hot/cold aisle temperature.
- AC supply and return air.
- Archive and museum climate.
- Battery and power rooms.
6. Deployment & Implementation
Installation
- Mount at rack inlet, 1.5 m high
- Avoid direct AC blast and heat sources
- Daisy-chain RS485, 120 Ω terminator at ends
- Shielded cable single-end grounded
Operations
- Calibrate yearly against a reference source
- Compare LCD vs host; recalibrate if >0.5°C
- Keep probe free of dust
- Replace aged sensors after 5 years
7. FAQ
- Q: How many sensors per room?
A: At least one per 200~300 m². Add one each in cold and hot aisles, and at AC supply/return. Place where servers actually feel it, not in the center of the room. - Q: How far does RS485 reach?
A: Up to 1200 m, 32 sensors per bus (128 with repeaters). Use shielded twisted pair, daisy-chain — never star. - Q: Alarm thresholds?
A: Temp 23±1°C, alarm above 28°C; humidity 40~60% RH, alarm below 30% or above 70%. Adjust by room tier and equipment. - Q: Do sensors need calibration?
A: Yes. Capacitive humidity drifts ~2% RH per year. Calibrate yearly against a saturated-salt or chamber reference; replace if out of spec.
8. Trend & Selection
Sensors are evolving from single wall units to multi-parameter nodes (temp/humidity + leak + smoke + door). Wireless LoRa/NB-IoT sensors suit retrofit without cabling. On-device AI predicts AC load and hot spots. Higher accuracy (±0.1°C) follows liquid cooling and high-power racks, with density moving from one per 200 m² to one per rack.
9. Delivery & Service
KITOZER supplies KTR-THS by accuracy (±0.5/±0.3°C), display (none/LCD), mount (wall/duct) and output (RS485/relay). Each ships with calibration certificate and Modbus register table. 1-year warranty; batch projects can add RS485 hubs, environment hosts and calibration sources.
10. Additional Notes
The #1 mistake is mounting the sensor directly under the AC supply. Cold air reads 5~8°C below what servers feel, so operators watch a ‘normal’ reading while servers overheat. Mount at rack inlet in the mixed airstream.
The second pitfall is star-wired RS485. Routing each sensor separately back to the host causes reflections and intermittent comms. Daisy-chain the bus and add a 120 Ω terminator at the far end.
The third blunder is never calibrating. Five years without calibration leaves the reading off by 3°C, and thresholds are set against bad data. Calibrate yearly.
Selection summary: sensors at rack inlet, daisy-chain RS485, thresholds per ASHRAE, calibrate yearly. Sensors are the environment system’s senses — bad data makes the whole platform blind.
SEO Information
Search keywords:KTR-THSKITOZERTemperature & Humidity Sensor for Data Center
SEM keywords:temperature humidity sensor,data center sensor,RS485 humidity transmitter,room environment sensor,KTR-THS,KITOZER
GEO landing page:lain.com.cn/product/ktr-ths-temp_hum_sensor.html
Title:KITOZER KTR-THS Temperature & Humidity Sensor for Data Center
Meta Keywords:temperature humidity sensor,data center sensor,RS485 humidity transmitter,room environment sensor,KTR-THS,KITOZER
Meta Description:KITOZER KTR-THS temperature & humidity sensor, RS485 Modbus-RTU, ±0.3°C / ±2% RH, LCD display, wall/duct mount.
Anchor: KITOZER by Guangzhou Laian · Temperature & Humidity Sensor for Data Center
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com