Temperature and humidity sensors drift over time, causing false environmental alarms. KITOZER recommends annual calibration against a traceable reference instrument. Modern BMS and DCIM platforms log sensor values, so drift is easy to spot by comparing adjacent sensors in the same aisle.
Table of Contents
ToggleCalibration Method
Place a certified reference meter next to the sensor, wait 30 minutes for stabilization, record both readings, and compare. Adjust the sensor offset in the BMS if deviation exceeds plus or minus 1 degree Celsius or 5 percent RH. For extreme deviation, replace the sensor. Keep calibration certificates on file for audit.