This FAQ outlines the recommended KITOZER UPS battery test routine for sealed VRLA strings. A routine discharge test should be performed annually under at least 50 percent load, with site personnel present to monitor inverter runtime, cell voltages, and ambient temperature. Measure each block with a calibrated voltmeter and record values in the battery log. Any block dropping below 1.80 V per cell during discharge must be replaced. Between annual tests, the UPS front panel performs an automatic short battery self-test every 30 days, and every quarter a technician should measure float current and look for bulging case evidence.
Test Schedule
Monthly visual inspection, quarterly float measurement, annual capacity discharge test. Replacement blocks from $45 each.