KITOZER
KITOZER

KITOZER UPS Input Cable Sizing Guide

This guide explains input cable sizing for KITOZER UPS systems. Input cable size is calculated from maximum input current, which includes rectifier and battery charger current. For a 400 V three-phase 20 kVA UPS at 0.9 power factor, nominal input current is about 36 A, but with charger load the peak can reach 45 A. Use copper cable rated for 70 A continuous in a conduit, typically 16 mm2 four-core plus earth. Voltage drop between the upstream breaker and UPS input must stay under 2 percent at full load. Always size the upstream breaker at 1.25 times maximum input current.

Cable Example

20 kVA 400 V: 16 mm2 copper, 63 A upstream breaker. Copper cable from $8 per meter.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com

Shopping Cart