The KITOZER 400kVA UPS output cabinet distributes conditioned UPS power from the UPS system to multiple downstream critical load panels and server rows. It takes the single large UPS output and splits it into rated branch feeders, each with its own breaker and monitoring, so that individual loads can be isolated without taking the whole UPS output offline. The cabinet is a standard component in data center power rows, hospital critical power systems, and industrial control rooms where the UPS output must be divided into manageable feeders for rack, panel, and equipment supply.
Table of Contents
ToggleTechnical Specifications
Rated power 400kVA, rated voltage 400V three phase, rated main current 630A. Main input breaker 630A, 8 branch outputs with MCCB ratings from 63A to 250A depending on load. Each branch with current measurement and status contact. Optional power meter on main busbar. IP20 floor-standing cabinet, RAL7035. Conforms to IEC 61439. Busbar rated for 630A with short-time withstand. KITOZER brand, compatible with 400kVA three-phase UPS systems.
Applications
The KITOZER output cabinet is installed immediately downstream of the UPS in data center power rows, feeding server rack power distribution units, network closets, and storage arrays. In hospitals it feeds operating theatre panels, intensive care equipment, and laboratory instruments. In industrial plants it feeds PLC control panels, safety systems, and critical process instruments. By splitting the UPS output into branch feeders, the cabinet allows one server row or panel to be isolated for maintenance while the rest of the critical load stays online.
The cabinet is also used to balance the load across three phases, so that no single phase is overloaded while others are lightly loaded. Branch current monitoring gives operators visibility of each load feeder, which is valuable for capacity planning and fault diagnosis. In dual-redundancy data centers, two output cabinets are used, one on each UPS path, so that each rack receives feeds from two independent sources.
Key Advantages
Centralized distribution reduces the need to run many large cables from the UPS, simplifying installation and maintenance. Branch breakers allow individual load isolation without shutting down the entire UPS output. Current monitoring on each branch gives early warning of overloaded feeders before they trip. KITOZER builds the cabinet as a factory-wired assembly, with busbar and breakers preinstalled, so site work is limited to connecting the UPS input and load cables.
The cabinet can be specified with branch remote monitoring that reports breaker status and current to the DCIM system, enabling real-time power usage monitoring per rack row. Standardized dimensions fit in typical data center power rows, and spare branch positions allow future expansion without replacing the cabinet. Clear labeling and mechanical interlocks support safe operation.
Installation and Maintenance
Position the output cabinet close to the UPS and load panels to keep cable runs short. Connect the UPS output to the main input breaker, and run branch cables to downstream distribution panels. Torque all busbar and cable connections to the specified value and confirm earthing. Commission each branch by verifying breaker operation and current reading against a reference meter.
During preventive maintenance, inspect breaker contacts, tighten busbar bolts, and verify current readings on each branch. Test branch breakers annually to confirm they trip correctly. Keep spare MCCBs of the ratings used in the cabinet. Do not exceed the branch breaker rating, and rebalance loads if one phase carries significantly more current than the others.
KITOZER builds the UPS output cabinet in ratings from 100kVA to 800kVA, with branch counts from 4 to 24 depending on the distribution plan. Branch breakers can be specified in a range of ratings to match downstream PDUs and panels, and each branch can be fitted with current measurement and remote status monitoring. When ordering, specify the main input kVA, the number of branches, and the breaker rating for each branch. KITOZER performs load balance calculations across the three phases so that no phase is overloaded. The cabinet is factory-wired and tested before shipment. Spare branch MCCBs of each rating are recommended as spares, because a breaker failure should not leave a critical row without power. For dual-power racks, KITOZER supplies matched output cabinets on each UPS path so that each rack receives two independent feeds. Optional branch energy metering supports rack-level power usage reporting to the DCIM system, which is useful for chargeback and capacity planning in multi-tenant data halls.
KITOZER can supply the output cabinet as part of a complete power row or as a stand-alone addition to an existing UPS. Factory wiring and test reports accompany each cabinet. Common branch configurations are held in stock for short lead times. Remote branch monitoring options allow the cabinet to report status to the DCIM system.