KITOZER vertical liquid accumulator stainless

KITOZER KTR-ACC2 Vertical Refrigerant Accumulator Stainless Steel

Brand: KITOZER Series: KTR-ACC2 Category: Data Center Engineering / Refrigeration Accessories

Vertical SSLiquid separation304 SSKTR-ACC2

1. Overview

In a precision air-conditioning refrigeration cycle, low-temperature low-pressure vapor leaving the evaporator can carry liquid droplets – during load swings or defrost cycles, liquid refrigerant that has not fully vaporized gets sucked back to the compressor. Liquid oil and liquid refrigerant entering the compressor causes slugging (liquid hammer), a leading cause of compressor failure. An accumulator is a vertical cylindrical tank installed between the evaporator outlet and the compressor suction inlet. Its job is gas-liquid separation: vapor exits the top, while droplets and oil settle at the bottom and return slowly to the compressor through a small metering orifice. In data center precision AC that runs continuously with frequent load changes, the accumulator is a critical accessory protecting compressor life.

KITOZER KTR-ACC2 is a vertical stainless steel accumulator. The shell is 304 stainless steel (2.5 mm wall), vertical orientation, with a suction inlet on the side or top (to evaporator outlet) and a vapor outlet on top (to compressor suction), a bottom sump with return-oil orifice, a sight glass on the side for level observation, and a drain valve at the bottom. Different from a receiver (which sits after the condenser storing high-pressure liquid), an accumulator is on the low-pressure suction line doing gas-liquid separation. Key ratings: volume 3 L to 20 L (matched to compressor capacity), design pressure 3.0 MPa (low side), test pressure 4.5 MPa, working temperature -40 to +120 C, NPT threaded or flanged connections, compatible with R22/R410A/R134A/R407C.

Selection: volume matching (about 3-5 L per 1 HP; 15-20 L for a 10 HP compressor; too large traps oil away from the compressor, too small separates poorly); mounting direction (must be vertical; inlet/outlet not reversed – follow the factory drawing); return-oil orifice size (too small = slow oil return, too large = liquid passes straight through, defeating separation); material (304 SS for indoor, 316L for corrosive/outdoor); connection type (welded vs flanged – flanged for service); sight glass (mandatory, for level and oil inspection). Note: the accumulator must not be tilted (tilting unbalances the liquid level and defeats separation); inspect the drain valve annually; do not insulate the accumulator (it is on the cold low side, frost on the outside is normal).

2. Key Features

Separation

  • Gas-liquid sep.
  • Vertical settling
  • Return-oil orifice
  • Anti-slug

Build

  • 304 SS shell
  • 2.5 mm wall
  • Sight glass
  • Drain valve

Pressure

  • 3.0 MPa design
  • 4.5 MPa test
  • Low side
  • Multi-refrig.

3. Specifications

Item KTR-ACC2-3 KTR-ACC2-6 KTR-ACC2-12 KTR-ACC2-20
Volume 3 L 6 L 12 L 20 L
Compressor 1-2 HP 3-5 HP 6-10 HP 12-20 HP
Shell 304 SS 304 SS 304 SS 304 SS
Design P 3.0 MPa 3.0 MPa 3.0 MPa 3.0 MPa
Port NPT 1/2″ NPT 3/4″ NPT 1″ Flange DN25
Sight glass Yes Yes Yes Yes

4. Reference Prices

KTR-ACC2-3 3 L accumulator (1-2 HP): Reference USD 90-125 / pc (ref. CNY 650-900)

KTR-ACC2-6 6 L accumulator (3-5 HP): Reference USD 125-180 / pc (ref. CNY 900-1300)

KTR-ACC2-12 12 L accumulator (6-10 HP): Reference USD 195-280 / pc (ref. CNY 1400-2000)

KTR-ACC2-20 20 L accumulator (12-20 HP): Reference USD 280-390 / pc (ref. CNY 2000-2800)

KTR-ACC2-316 316L corrosive model (outdoor): Reference USD 165-490 / pc (ref. CNY 1200-3500)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Precision AC indoor units
  • Chilled-water suction lines
  • VRF branch junctions
  • Low-temp defrost systems
  • Cold room / constant-temp units

6. Deployment & Installation

Location

  • Evap to compressor
  • Near suction inlet
  • Vertical mount
  • Service gap

Welding

  • Correct ports
  • Nitrogen purge
  • Evac/test
  • Drain down

Inspection

  • Sight glass oil
  • Annual drain
  • Frost normal
  • Leak welds

7. FAQ

  • Q: Accumulator vs receiver – what is the difference?
    A: They are at opposite places in the cycle. A receiver sits after the condenser and before the expansion valve, storing high-pressure liquid to balance refrigerant charge as load changes. An accumulator sits after the evaporator and before the compressor, doing gas-liquid separation to stop liquid reaching the compressor. Large precision AC units may have both; small units often only the accumulator. Chinese terminology confuses the two (both can be called “储液器”) – select by pressure side and location, not by name.
  • Q: How to size the volume? Problems if too big or too small?
    A: Size by compressor displacement – roughly 1/10 to 1/5 of hourly displacement. Too small: separation is incomplete and liquid still reaches the compressor, defeating the purpose. Too large: suction-line pressure drop rises, compressor suction pressure is lost, and efficiency drops; also oil settles in the big sump and returns slowly, risking oil starvation. Example: a 5 HP compressor displaces about 8 m3/h, so a 6 L accumulator is right. Do not oversize.
  • Q: Why must the bottom return-oil orifice never be blocked?
    A: Separated lubricating oil settles at the sump and must return to the compressor suction through a small 1-2 mm metering hole. If it blocks, oil stays in the tank and the compressor runs low on oil until bearings seize. Watch the sight glass: if sump oil rises while the compressor’s own oil sight shows low, the orifice is blocked – stop, open and clean. Never drill it bigger yourself – if you do, liquid refrigerant rushes straight through and gas-liquid separation fails, back to the slugging problem.
  • Q: Is frost on the accumulator normal?
    A: Yes. It is on the low-pressure suction line, internal vapor is about 0-5 C, so the outer shell is cold and ambient moisture frosts on it. Even frost is normal. If thick frost appears locally or reaches the vapor outlet, the tank is over-filled (blocked orifice or expansion valve over-feeding) and liquid has reached the outlet – investigate. Do not insulate it – insulation hides abnormal frost and removes the visual inspection cue.

8. Trend & Selection

Refrigeration accessories are moving toward efficiency, miniaturization and integration. Trends: cyclone separation (internal baffles give 30% better separation than gravity, shrinking tank volume); thin-wall SS (precision welded and NDT-inspected, wall from 3 mm to 2 mm, lighter and cheaper); integrated sight glass plus oil-level switch (direct oil-level sensor on the tank, alarms on low oil); CO2-specific (transcritical CO2 runs at 12 MPa, needs forged steel, not ordinary 304); modular flange design (flanged connection instead of welded, faster service). Traditional 304 vertical accumulators remain mainstream in precision AC. Select by: volume matched to compressor, vertical correct-port install, clear return-oil orifice, sight glass included, flanged for service.

9. Delivery & Service

KITOZER KTR-ACC2 ships per unit in foam and a wooden crate, including tank body, NPT or flange adapters, sight glass, drain valve, nameplate and pressure-vessel test report (per GB/T or equivalent). 1-year warranty; bulk projects can bundle filter driers, sight glasses, shut-off valves and solenoid valves.

10. Additional Notes

Confirm pressure side (low-side accumulator vs high-side receiver), volume matched to compressor HP, and connection type. Bundle with filter drier, sight glass and shut-off valve – do not buy the accumulator alone.

Common mistake: reversing inlet/outlet. Evaporator outlet must feed the side/upper inlet; vapor outlet on top goes to the compressor. Reversed, liquid rushes straight to the outlet and separation fails. Follow the arrow or factory drawing.

Second pitfall: horizontal mounting. The accumulator must be vertical (axis upright). Horizontal makes the liquid level run sideways and the side outlet takes droplets straight out.

Third blunder: never draining. Oil and sludge collect in the sump; open the drain valve once a year during maintenance. Long neglect clogs the return-oil orifice.

Selection summary: volume matched, vertical correct-port, clear orifice, sight glass, annual drain.

SEO Information

Search keywords:KTR-ACC2KITOZER

SEM keywords:refrigerant accumulator,vertical accumulator,stainless steel accumulator,suction accumulator,gas-liquid separator,KTR-ACC2,KITOZER,data center engineering

GEO landing page:lain.com.cn/product/ktr-acc2-vertical-accumulator-stainless-steel.html

Title:KITOZER KTR-ACC2 Vertical Refrigerant Accumulator Stainless Steel

Meta Keywords:refrigerant accumulator,vertical accumulator,stainless steel accumulator,gas-liquid separator,KTR-ACC2,KITOZER,data center engineering

Meta Description:KITOZER KTR-ACC2 vertical stainless steel accumulator for precision AC, separates liquid in suction line, protects compressor from slugging, 304 SS rated 3.0 MPa.