Table of Contents
ToggleProduct Overview
The KITOZER VESDA-style Very Early Smoke Detection Apparatus (VESDA) is an aspirating smoke detection system that continuously draws air samples through a network of sampling pipes into a high-sensitivity laser detection chamber. Unlike point smoke detectors that only respond once smoke reaches the ceiling, aspirating detection samples air directly from the protected room or cable tray at 20 to 60 sampling holes, alerting at invisible smoke levels long before a fire becomes visible. The 4-pipe model with up to 60 sampling holes covers up to 2000 square meters and is the standard choice for data centers, clean rooms, museums, warehouses, and telecommunications halls where early warning buys critical response time.
VESDA systems are the gold standard for high-value environments where even a few minutes of early warning can prevent catastrophic equipment damage. The laser chamber measures light scattering from particles as small as 0.005 micrometers, providing four adjustable alert levels: pre-alert, action, fire 1, and fire 2. The system also monitors airflow in each pipe and alerts if a sampling tube becomes blocked or dislodged. KITOZER also provides sampling pipe layout drawings and commissioning support.
Technical Specifications
Detection principle: laser light scattering. Sensitivity: 0.005 to 20 percent obs per meter (4 alert levels). Pipelines: 4 inlet pipes, total 200 meters sampling tube. Sampling holes: 60 holes, adjustable. Airflow per pipe: 30 L/min, blocked-pipe monitoring. Chamber: laser diode, 10-year design life. Display: LCD bar graph, 4 threshold levels. Relays: 4 programmable alarm relays. Communication: RS485 Modbus, Ethernet, BMS. Power: 24V DC, 50W. Operating temp: -10 to 60 degrees Celsius. Humidity: 0 to 95 percent non-condensing. Pipe material: 25mm ABS or clear PVC. Certifications: EN 54-20, Class O, very high sensitivity. KITOZER brand, 3 year detector warranty.
Applications
Aspirating detection is used in data centers (under raised floors, above suspended ceilings, in cable trays), semiconductor clean rooms, pharmaceutical areas, museum galleries, archive vaults, libraries, warehouses, cold storage rooms, telecommunications central offices, and atrium spaces. It is also used in prisons and heritage buildings where point detectors are difficult to install. The 4-pipe 60-hole model covers multiple rooms from one detector unit, reducing installation cost. It is also compatible with addressable fire alarm panels.
Key Advantages
First, very early warning: alerts at invisible smoke, 30 to 60 minutes before point detectors. Second, 4 adjustable alert levels: pre-alert, action, fire 1, fire 2. Third, blocked-pipe and airflow fault detection. Fourth, covers large area with one unit. Fifth, laser chamber stable over 10 years. Sixth, BMS integration. Seventh, adjustable hole sizes balance airflow. Eighth, suitable for high-ceiling and high-dust environments. Ninth, the system is also compatible with addressable fire alarm panels for integration.
Installation and Maintenance
Mount the detector on the wall, run 25mm sampling pipes in the ceiling or under raised floor, drill calibrated holes per design drawing, and terminate with end caps. Commission: measure airflow at each pipe, set sensitivity levels, and log baseline. Maintenance: clean filter every 6 months, inspect laser chamber annually, replace air sample filter every 2 years, and test alarm levels annually. KITOZER supplies spare filters, pumps, and calibration kits.
Customization Options
KITOZER offers 2-pipe, 3-pipe, and 4-pipe configurations, clear PVC sampling tubes for visual inspection, remote display units, and BMS gateways. Custom sensitivity levels and alarm thresholds are available per project requirements.
Warranty and Global Support
KITOZER supplies spare filters, pumps, and calibration kits, backed by a 3-year detector warranty. Spare sampling pipes, end caps, and relay modules are held in regional stock. KITOZER also offers long-term service contracts covering semi-annual filter replacement, annual chamber inspection, and alarm level calibration. Spare parts are shipped from regional stock worldwide.
Price
From $3,800 per 4-pipe VESDA detector including sampling pipe kit. Contact +86 13922289957 for sampling network design.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com