Table of Contents
ToggleProduct Overview
The KITOZER VS1-12 (ZN63A-12) is a handcart-type 10kV vacuum circuit breaker used inside KYN28A and similar mid-mounted switchgear. Its vacuum interrupter offers fast arc extinction, long mechanical life, and no oil or gas to maintain. The spring operating mechanism can be closed and tripped either by motor-charged spring or by manual charging, and it supports both electrical close/trip and manual push-button operation on the front panel. The breaker is the core switching and protection element for 10kV feeder, transformer, and motor circuits.
The vacuum interrupter uses copper-chromium contacts housed in a ceramic envelope, with a measured contact wear indicator visible on the front of the interrupter. The handcart frame is welded steel with precision rails that mate with the panel, and secondary plugs automatically connect when the breaker is racked to the connected position. Auxiliary switches and the energy storage motor are wired to a secondary connector so the breaker can be fully removed without disconnecting individual control wires.
Technical Specifications
Rated voltage 12kV, rated current 630A, frequency 50Hz, rated short-circuit breaking current 20kA, rated short-time withstand current 20kA for 4 seconds, rated peak making current 50kA. Mechanical endurance 10,000 operations, electrical endurance 50 rated short-circuit breaking operations. Vacuum interrupter rated lightning impulse 75kV.
Operating mechanism spring type, closing motor 110V or 220V DC/AC, shunt trip and undervoltage release included. Overall handcart dimensions designed for KYN28A-12 800mm wide panel. Weight approximately 95kg. Auxiliary contact 8NO plus 8NC. Mechanical life 10,000 operations, electrical life 50 short-circuit breaks. Optional motorized charging and remote close/trip coils allow integration with SCADA.
Typical Applications
VS1-12 630A breakers are installed in 10kV incoming, feeder, transformer protection, and capacitor bank panels in industrial plants, commercial substations, and building power rooms. They are the standard replacement breaker for aging JYN and GBC switchgear retrofits where the existing switchgear needs upgraded breaking duty but the building switchroom cannot be enlarged.
They also serve as standalone breaker units in small compact switchboards for pump stations and water treatment plants. In residential subdivision substations, the VS1-630A protects 10kV/0.4kV distribution transformers up to 1250kVA. In industrial plants, it feeds 10kV motor circuits driving pumps, fans, and compressors. The breaker is also used on 10kV capacitor bank feeders where frequent switching requires a contactor with high mechanical life.
Key Advantages
Vacuum interruption produces a compact, maintenance-free arc chamber with no oil leaks and no SF6 gas handling. The spring mechanism is proven over decades of field service and uses common spare parts. The handcart design allows the breaker to be rolled out for inspection in seconds while the busbar stays live.
A wide range of auxiliary switches, motor voltages, and release coils is available, so the breaker can match almost any existing protection scheme. KITOZER factory tests every breaker for contact resistance, mechanical operation count, and power-frequency withstand before shipment. A five-year warranty covers the spring mechanism and vacuum interrupter. The common handcart interface allows VS1 breakers from different production years to be interchanged, simplifying spare parts management.
Installation and Maintenance
Roll the breaker onto the panel rails and rack it in until the secondary connector seats. Do not force the racking handle if the interlock blocks rotation. After installation, perform a mechanical close-trip cycle test ten times and inspect the contact stroke.
Every year, check the contact wear indicator; when the moving contact travel reaches the lower limit, replace the vacuum interrupter. Lubricate the racking screw and mechanism linkages every two years with the specified lithium grease. Keep a spare breaker on site for critical installations so that a failed breaker can be exchanged without a long outage. Test the shunt trip and undervoltage release annually with a secondary injection tester.
Price
From $680/pole set. Contact +86 13922289957 for VS1 breaker pricing and spare interrupter list.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com