Table of Contents
ToggleKITOZER KTR-TH8 Environment Monitor / Wall-Mount Temp-Humidity with Display
Brand: KITOZER Series: KTR-TH8 Category: Environmental Monitoring / Temp-humidity sensor
Wall mountLED displayRS485 outputTemp+humidityLocal buzzer alarm
1. Overview
Data centers and power rooms demand tight temperature and humidity control. High temperature triggers server throttling or shutdown; low humidity causes ESD that damages electronics; high humidity causes condensation and short circuits. Temp-humidity sensors are the most basic and important acquisition point in environmental monitoring, uploading data to the host and alarming locally and remotely when out of range.
The KITOZER KTR-TH8 is a wall-mount temp-humidity sensor with display. Its flame-retardant ABS housing mounts on walls next to racks. The front LED shows current temperature and humidity at a glance when staff enter the room. The sensing element is an imported digital temp-humidity IC with temperature accuracy +/-0.5 C and humidity accuracy +/-3% RH. Output is RS485 Modbus-RTU to the DCIM host. A local buzzer and red LED trigger when thresholds are exceeded. Power is DC12 V or PoE.
Selection confirms: range (-10 to 60 C, 0-100% RH), accuracy, output (RS485 / 4-20 mA), local display, power (DC12 V / PoE), and mounting (rack side / wall). Place one in each cold and hot aisle, about 5-10 per typical room. Avoid AC outlets and rack heat sources; mount 1.5-1.8 m high, 20 cm off the wall, to read true air temperature.
2. Key Features
High precision
- Imported digital temp-humidity IC.
- Temperature +/-0.5 C.
- Humidity +/-3% RH.
- Response <30 s.
Display and alarm
- LED simultaneous temp/humidity.
- Local buzzer + red LED.
- Thresholds settable by software.
- Alarm events logged to host.
Comms and power
- RS485 Modbus-RTU.
- 9600/19200 bps selectable.
- DC12 V or PoE.
- Wall ABS, flame-retardant.
3. Specifications
| Item | Specification |
|---|---|
| Temp range | -10 to 60 C |
| Temp accuracy | +/-0.5 C at 25 C |
| Humidity range | 0 to 100% RH |
| Humidity accuracy | +/-3% RH |
| Display | LED (temp + humidity) |
| Output | RS485 Modbus-RTU |
| Baud rate | 9600 / 19200 bps |
| Power | DC12V / PoE 802.3af |
| Alarm | Local buzzer + LED |
| Mounting | Wall (ABS) |
4. Reference Prices
KTR-TH8 wall temp-humidity (RS485): USD 25~40 (ref. CNY 180~280 at ~7.2)
KTR-TH8 PoE version: USD 33~50 (ref. CNY 240~360 at ~7.2)
Shielded RS485 cable (per meter): USD 0.4~0.8 (ref. CNY 3~6 at ~7.2)
Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Cold/hot aisle monitoring.
- Power and battery rooms.
- Archives and museums.
- Industrial workshops and warehouses.
- Lab and cleanroom monitoring.
6. Installation & Maintenance
Installation
- Avoid AC outlets and heat sources.
- Drill anchors and hang the unit.
- Mount 1.5-1.8 m high, 20 cm off wall.
- Daisy-chain RS485 bus.
- Power with DC12 V or PoE.
- Set address and thresholds on the host.
Maintenance
- Calibrate with salt solution every 6 months.
- Check LED monthly.
- Add 120 ohm termination at bus end.
- Dust the probe with a soft brush.
- Replace the probe every 2 years.
7. FAQ
- Q: Is accuracy enough?
A: Data centers target 22 +/-2 C and 40-60% RH; the KTR-TH8 at +/-0.5 C and +/-3% RH is more than enough. - Q: How many sensors per host?
A: Up to 32 per RS485 bus; use a repeater for more. Set unique addresses 1-247. - Q: Why differs from the AC display?
A: The AC display reads supply air; the sensor in the aisle reads true server intake air. - Q: Does it drift?
A: Yes, about +/-1 C over 6 months; calibrate yearly with a reference.
8. Trend & Selection
Data center monitoring is moving from single-point to dense sensor networks; wall-mounted units with local display are popular for operator visibility and low cost. Place 1-2 per aisle; daisy-chain RS485; mount at server intake; leave 2 C margin on thresholds.
9. Delivery & Service
KITOZER ships the KTR-TH8 with unit, wall bracket, power adapter, manual and certificate; bulk orders include an RS485 address list and host integration support.
10. Notes
A common mistake is mounting at the AC outlet. That reads supply air, not rack intake, and misleads operators.
Another pitfall is star-wired RS485. Use a daisy-chain bus with 120 ohm termination at the end for stable comms.
Selection summary: wall mount; LED display; RS485; +/-0.5 C; local sound/light alarm. It is the building block of environmental monitoring.
Systemically, temp-humidity data feeds DCIM; sensor density determines how finely airflow can be optimized.
Cost-wise, a sensor at about 200 CNY covers a 20 m2 aisle, paying back far more than one overheating incident.
From an airflow standpoint, mounting sensors above cold-aisle floor supplies and hot-aisle rack exhausts lets you monitor both supply and return temperatures, feeding the plant controls and helping optimize cold-aisle containment.
For alarms, set the high-temp threshold at 28 C, low at 18 C, high-humidity at 65% RH and low at 35% RH; if the alarm persists for 5 minutes, escalate to SMS.
SEO Information
Search keywords: KITOZER
SEM keywords: temperature humidity sensor, wall mount, data center monitoring, RS485 temp hum, KTR-TH8, KITOZER
GEO landing page: lain.com.cn/product/447_temp_hum_8.html
Title: KITOZER KTR-TH8 Environment Monitor / Wall-Mount Temp-Humidity with Display
Meta Keywords: temperature humidity sensor, wall mount, data center monitoring, RS485 temp hum, KTR-TH8, KITOZER
Meta Description: KITOZER KTR-TH8 wall-mount temp-humidity sensor, LED display, RS485 output, local buzzer alarm, for data center and power room monitoring.