KITOZER wall LCD temp humidity sensor

KITOZER KTR-THL4 Wall-Mount LCD Temp & Humidity Sensor

Brand: KITOZER Series: KTR-THL4 Category: Environmental Monitoring / Temp & Humidity

temp humidity sensorwall LCDRS485Modbusroom monitor

KITOZER KTR-THL4 Wall-Mount LCD Temp & Humidity Sensor

1. Overview

Temp/humidity sensors are the basic sensing nodes of data-center environmental monitoring. Too hot and servers throttle; too humid and condensation shorts; too dry and static builds up. A wall-mount LCD sensor integrates measurement, display and comms in a single 86-box panel — an LCD shows live values on site while RS485 uploads data to the DCIM platform. It mounts on the room wall: inspectors read it at a glance; the platform reads it remotely.

The KITOZER KTR-THL4 is a wall-mount LCD temp/humidity sensor with a digital probe: temp -20℃~+60℃, ±0.5℃; humidity 0~100%RH, ±3%RH. LCD shows temp and RH together, backlight configurable. RS485 with standard Modbus-RTU; baud 9600/19200; address 1~247. Power DC 12V/24V. ABS flame-retardant white case, 86-box mount.

In room environmental monitoring, KTR-THL4 wall-mounts at 1.5 m, away from outlets and corners; multiple sensors distribute by rack zone on a hand-in-hand RS485 bus to the host. The LCD is softer than LED and can show temp, RH, time and alarm status. It is the eye of the environmental network — temp/RH drives precision-AC control, alarm thresholds and PUE analysis.

2. Key Features

Measurement

  • Temp -20℃~+60℃, ±0.5℃.
  • RH 0~100%RH, ±3%RH.
  • Resolution 0.1℃/0.1%RH.
  • Response ≤15 s.

Display & comms

  • LCD, temp+RH together, backlight configurable.
  • RS485 Modbus-RTU.
  • Baud 9600/19200.
  • Address 1~247 (DIP/software).

Construction

  • 86-box wall mount.
  • Power DC 12V/24V.
  • ABS flame-retardant white.
  • Internal probe (external option).

3. Specifications

Item KTR-THL4
Temp range -20℃~+60℃ (±0.5℃)
RH range 0~100%RH (±3%RH)
Comm RS485 Modbus-RTU
Display LCD (temp+RH together)
Power DC 12V/24V
Mount 86-box wall
Address 1~247
Case ABS flame-retardant

4. Reference Prices

KTR-THL4 wall LCD temp/RH sensor (RS485 Modbus): Reference USD 13~25 (ref. CNY 90~180 at ~7.2)

Reference only; final quote applies. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Server room temp/RH monitoring.
  • Electrical/UPS room environment.
  • Warehouse, archive rooms.
  • Lab, cleanroom monitoring.
  • Museum HVAC.

6. Installation & Maintenance

Installation

  • 86-box at 1.5 m; away from outlets/corners.
  • Hand-in-hand RS485: DATA+/DATA- matched.
  • Power DC 12V/24V; no reverse polarity.
  • Set unique address.
  • Fit 120Ω terminator at bus end.
  • Add device in host; read registers.
  • Set upper/lower alarm thresholds.

Maintenance

  • Clean probe; no dust.
  • Calibrate RH with saturated salt.
  • Check A/B not reversed.
  • Verify LCD backlight.
  • Add signal SPD at line entry.

7. FAQ

  • Q: How many sensors per bus?
    A: Theoretically 32 (128 with repeaters); practically ≤20. Unique address each.
  • Q: Where to mount?
    A: At a representative 1.5 m position, away from AC outlets (direct airflow reads low), corners (stagnant air) and doors (swing).
  • Q: LCD vs LED display?
    A: LCD is soft, shows characters/time/status; LED is bright and far-readable but digits only. Choose LCD for duty rooms/inspection, LED for long-distance viewing.
  • Q: How to read Modbus?
    A: Standard Modbus-RTU: temp and RH each hold a register (e.g. 40001 temp, 40002 RH); see manual.

8. Trend & Selection

Room DCIM moves toward multi-parameter fusion (temp/RH + leak + smoke + current); RS485 remains mainstream, with LoRa/NB-IoT emerging for dispersed sites. LCD on-site display improves inspection. Choose RS485 Modbus; ±0.5℃; LCD wall display; representative position; unique address; bus terminator.

9. Delivery & Service

KITOZER provides sensor sizing: based on point count, mounting positions and comm distance, we configure KTR-THL4 quantity and bus topology. Bundled with DCIM hosts, precision AC and leak detection. Delivery includes sensor, box and manual. Warranty covers calibration and comms commissioning.

10. Additional Notes

A common pitfall is mounting next to an AC outlet. Direct cold air reads 2~3℃ low, tricking the AC into stopping while other racks overheat. Mount away from outlets.

Another pitfall is reversed RS485 A/B. Reversed, the whole bus dies. Match DATA+(A)/DATA-(B) by label.

Selection summary: RS485 Modbus; LCD wall display; ±0.5℃; representative position; away from outlets; unique address; terminator. It is the room’s thermometer — accurate measurement makes AC and alarms reliable. Place one in each hot and cold aisle.

Keep the probe at least 5 cm off the wall for air circulation.

SEO Information

Search keywords:KTR-THL4KITOZER

SEM关键词:temperature humidity sensor, wall LCD temp humidity, data center temp humidity, RS485 transmitter, LCD humidity display, KTR-THL4, KITOZER

GEO landing page:lain.com.cn/product/367-temp-hum-lcd-ktr-thl4.html

Title:KITOZER KTR-THL4 Wall-Mount LCD Temp & Humidity Sensor

Meta Keywords:temperature humidity sensor, wall LCD temp humidity, data center temp humidity, RS485 transmitter, LCD humidity display, KTR-THL4, KITOZER

Meta Description:KITOZER KTR-THL4 wall-mount LCD temp/humidity sensor, RS485 Modbus, LCD shows temp and RH together, ±0.5℃, 86-box mount, for server room, electrical room and warehouse monitoring.