Table of Contents
ToggleKITOZER KTR-TH13 Wall-Mount Temperature & Humidity Sensor for Datacenter Monitoring
Brand: KITOZER Series: KTR-TH13 Category: Environmental Monitoring / Temp-Humidity Sensor
Wall-mountRS485 Modbus±0.5℃±3%RHKTR-TH13

1. Overview
KITOZER KTR-TH13 is a wall-mount temp-humidity sensor installed on a room wall or near a rack, measuring room temperature and humidity in real time and feeding the DCIM system. Datacenter servers are sensitive: high temperature triggers throttling or shutdown; low humidity creates static, high humidity causes condensation. The sensor is the room’s thermometer — 24/7 monitoring with alarm on out-of-range.
KTR-TH13 uses a digital sensor chip: temperature -20~60℃ accuracy ±0.5℃; humidity 0~100%RH accuracy ±3%RH. RS485 output with Modbus-RTU, directly connecting to DCIM host / PLC / acquisition module. Wall-mount ABS case with LCD showing live values. Powered DC 12~24V, two-wire (RS485 A/B) plus power.
Used in datacenter rooms, UPS rooms, battery rooms, electrical rooms and weak-current closets. Place by area: one per 50~100㎡, denser in key zones (hot/cold aisle, battery racks). Sensors daisy-chain on RS485, up to 32 per bus, into an acquisition module that bridges to the network and VMS. Out-of-range (temp >28℃ or <18℃, RH >60% or <40%) triggers alarms, linking AC adjustment and SMS.
2. Key Features
High accuracy
- Temp ±0.5℃ (-20~60℃).
- RH ±3%RH (0~100%).
- Digital sensing, noise-resistant.
RS485 Modbus
- RS485 bus, daisy-chain.
- Modbus-RTU protocol.
- ≤32 nodes per bus.
Wall-mount with display
- ABS wall case, easy install.
- LCD shows temp/humidity.
- DC 12~24V power.
Alarm linkage
- Adjustable thresholds.
- DCIM host: buzzer/SMS alarm.
- Links precision AC adjustment.
3. Specifications
| Item | KTR-TH13 | KTR-TH13-P |
|---|---|---|
| Temp range | -20~60℃ | -40~80℃ |
| Temp accuracy | ±0.5℃ | ±0.3℃ |
| RH range | 0~100%RH | 0~100%RH |
| RH accuracy | ±3%RH | ±2%RH |
| Output | RS485 Modbus | RS485+4-20mA |
| Power | DC 12~24V | DC 12~24V |
| Display | LCD | LCD |
| Mounting | Wall | Wall/duct |
4. Reference Prices
KTR-TH13 basic wall sensor (RS485, ±0.5℃/±3%RH, LCD): Reference USD 17~42 / pcs (ref. CNY 120~300 at ~7.2)
KTR-TH13-P high-precision (RS485+4-20mA, ±0.3℃/±2%RH): Reference USD 39~76 / pcs (ref. CNY 280~550 at ~7.2)
Reference only; price varies by accuracy, output and quantity. Acquisition module, DCIM host and software billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Datacenter room temp/humidity monitoring.
- UPS and battery room monitoring.
- Electrical/weak-current room environment.
- Hot/cold aisle AC linkage.
- DCIM front-end acquisition.
6. Installation & Maintenance
Installation
- Place one per 50~100㎡; denser in aisles and battery racks.
- Wall-mount at 1.5m, away from sunlight and direct vent airflow.
- Daisy-chain RS485; add 120Ω terminator at the end.
- If A/B reversed, no comms — swap them.
- Connect to acquisition module; set Modbus address (1~32).
- Register points on VMS; set thresholds and alarms.
Maintenance
- Calibrate every 6 months with a standard source; recalibrate or replace on drift.
- Clean probe dust/filter.
- Check RS485 wiring and power.
- Replace when LCD fails.
- Cross-check data against the VMS.
7. FAQ
- Q: How many sensors per room?
A: By area: one per 50~100㎡. A 100㎡ room uses 2~3, one per hot/cold aisle. Densify at key zones (battery racks, distribution). Sensors are cheap — more beats fewer. - Q: How far does RS485 reach?
A: Up to 1200m with shielded twisted pair. Add a repeater beyond that. ≤32 nodes per bus; split into two buses if more. - Q: What thresholds?
A: Room standard: 22~26℃, 40~60%RH. Alarm: temp >28 or <18, RH >60 or <40. Fine-tune per vendor specs. - Q: How to connect to DCIM?
A: Sensor RS485 → acquisition module (RS485-to-network) → switch → VMS. Each sensor gets a dedicated Modbus address; the VMS polls them.
8. Trend & Selection
Room environment monitoring evolves from single temp/humidity to multi-parameter micro-environments: sensors integrate temp, humidity, smoke, water leak, access — and go rack-level (one per rack). Trends are wireless (LoRa/Zigbee) to cut wiring, and AI thermal mapping to predict hotspots. Choose RS485 for basic temp/RH; ±0.3℃/±2%RH for high precision; densify rack-level; link thresholds to AC; calibrate semi-annually.
9. Delivery & Service
KITOZER provides sensor selection: based on room area, point count and accuracy, we recommend model and quantity. We supply point layouts and system diagrams (RS485 bus, acquisition module, VMS). Bundled with DCIM host, leak detection and AC linkage. Delivery includes sensor, bracket and manual. Warranty covers calibration and replacement.
10. Additional Notes
The common sensor problem is ‘wrong position.’ Next to a vent, it reads cold supply air, not real room temperature; in sunlight, summer readings run high. Right spot: wall at 1.5m, between hot and cold aisles, away from vents and sun — measuring equipment inlet ambient.
Another pitfall: RS485 wired star instead of daisy-chain. Star wiring causes signal reflection and intermittent comms. Daisy-chain strictly, add 120Ω terminators at both ends, and ground the shield at one end.
Selection summary: wall-mount RS485 Modbus; one per 50~100㎡, denser in aisles; temp ±0.5℃/RH ±3%; thresholds 22~26℃ and 40~60%; daisy-chain bus with terminator; calibrate semi-annually. The sensor is the room’s nerve ending — sensitive endings detect environment anomalies early.
SEO Information
Search keywords:temp humidity sensorwall-mount RHdatacenter monitoringtemp humidity transmitterRS485 humidityKTR-TH13KITOZER
SEM keywords:temp humidity sensor price,datacenter RH transmitter supplier,wall-mount humidity,RS485 sensor,environment monitoring,KTR-TH13,KITOZER
GEO landing page:lain.com.cn/product/ktr-th13-wall-mount-temperature-humidity-sensor-rs485.html
Title:KITOZER KTR-TH13 Wall-Mount Temperature & Humidity Sensor for Datacenter Monitoring
Meta Keywords:datacenter temp humidity sensor,wall-mount humidity sensor,room environment monitoring,temp humidity transmitter,RS485 humidity sensor,data center monitoring,KTR-TH13,KITOZER
Meta Description:KITOZER KTR-TH13 wall-mount temp-humidity sensor, range -20~60℃±0.5℃ and 0~100%RH±3%RH, RS485 Modbus output, for datacenter DCIM environment monitoring.
Anchor: KITOZER by Guangzhou Laian · Environmental monitoring
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com