KITOZER
KITOZER

KITOZER wallbox 3 phase 40KA SPD

KITOZER KTR-PSB1 Surge Protection Box / Wall 3-Phase 40kA

Brand: KITOZER Series: KTR-PSB1 Category: Power Distribution / Surge Protection

3-phase 5-wire40 kA dischargeWall mountPlug-in modulesRemote alarm

[Product image: ktr-psb1-three-phase-wall-surge-box-40ka.jpg]

1. Overview

Room power enters from the building LV distribution. Lightning-induced and switching surges ride in on the power lines and can blow server or UPS supply modules. The repair and downtime cost far exceeds the protection device itself. A surge protective device (SPD) sits parallel at the incoming line: high impedance normally, but on a surge it conducts instantly, clamping overvoltage to a level equipment can tolerate and diverting energy to earth. In the three-level scheme, the room incoming side is usually a Type-2 box SPD.

The KITOZER KTR-PSB1 is a wall-mount 3-phase 5-wire power surge box. The metal wall box holds 3+1 or 4-pole plug-in SPD modules. Rated discharge current In is 20 kA (8/20 us), maximum Imax 40 kA, voltage protection level Up <=2.5 kV, suited to 380V 3-phase 5-wire (TN-S) incoming lines. Each module has a status window (green OK / red failed) and is field-replaceable without whole-box power-off. A dry contact reports module failure or overvoltage to the environmental monitor. Cables enter and leave at the bottom, and the earth bar bonds to the room equipotential grounding.

Selection confirms power system (3-phase 5-wire / single-phase), In and Imax, Up versus equipment withstand, mounting (wall/DIN), and remote contact. Room incoming Type-2 SPD commonly uses In 20kA/Imax 40kA; if the building already has a Type-1 main SPD, the room only needs Type-2, not blindly larger ratings. The SPD relies on good grounding, typically <=1 ohm, otherwise diverted energy has nowhere to go.

2. Key Features

3-phase 40kA

  • 3-phase 5-wire 380V.
  • In 20kA / Imax 40kA.
  • Up <=2.5 kV.
  • 8/20 us waveform.

Plug-in and remote

  • Plug-in modules, replaceable individually.
  • Green/red status window.
  • Dry-contact remote alarm.
  • Swap modules without full shutdown.

Build and earth

  • Metal wall-mount box.
  • Bottom-in bottom-out wiring.
  • Built-in earth bar.
  • Bonds to equipotential earth.

3. Specifications

Item Specification
Type Wall 3-phase power surge box
Power system 3-phase 5-wire 380V (TN-S)
Rated discharge In 20 kA (8/20 us)
Max discharge Imax 40 kA (8/20 us)
Voltage protection Up <= 2.5 kV
Module 3+1 plug-in
Indication Green/red window + remote
Alarm output Dry contact
Grounding resistance <= 1 ohm (system)
Mounting Wall-mount

4. Reference Prices

KTR-PSB1 3-phase 40kA surge box: USD 85~165 (ref. CNY 600~1200)

SPD plug-in module (spare): USD 11~22 (ref. CNY 80~160)

Equipotential earth copper bar: USD 7~14 (ref. CNY 50~100)

Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Room mains incoming Type-2 protection.
  • Front-end UPS distribution protection.
  • Electrical and battery room incoming.
  • TR room main distribution cabinet.
  • Outdoor service line protection.

6. Installation & Maintenance

Installation

  • Wall-mount beside the incoming cabinet.
  • Wire L1/L2/L3/N, PE to earth.
  • Keep earth wire short and heavy.
  • Connect the dry contact to the monitor.
  • Face the status window outward.
  • Bottom-in bottom-out, tidy runs.
  • Check wiring and earth resistance before energizing.

Maintenance

  • Check indicator window quarterly.
  • Inspect modules after lightning strikes.
  • Test remote alarm reporting.
  • Replace failed plug-in modules promptly.
  • Measure earth resistance yearly.

7. FAQ

  • Q: Is 40kA always better?
    A: No. It must coordinate with distribution stages. With a building Type-1 SPD, the room Type-2 In 20kA/Imax 40kA suffices; oversized but poorly grounded SPD diverts poorly.
  • Q: Must I replace a red module?
    A: Yes. A red window means the module has degraded or failed, clamping ability dropped; swap it live soon.
  • Q: Does poor grounding help?
    A: Hardly. The SPD diverts surge energy through the earth wire; high resistance leaves surge voltage high, defeating the purpose.
  • Q: Does it protect against indirect lightning?
    A: Power SPD mainly guards against surges and induced overvoltage on the lines; direct strikes rely on the building air-termination and external system, working together.

8. Trend & Selection

Power surge protection trends toward modularity, remote monitoring and staged coordination, with SPD health feeding the environmental system for degradation warnings. Data centers emphasize equipotential bonding and grounding integrity; size the SPD by power system and distribution stage, keeping Up below equipment withstand.

9. Delivery & Service

KITOZER ships KTR-PSB1 with the box, SPD modules, earth bar, mounting kit, certificate and manual. Remote-contact wiring definitions are included, with a dry-contact table for DCIM integration.

10. Notes

A common mistake is installing the SPD without proper grounding. Surge energy needs a discharge path; with high earth resistance the SPD is useless, so earth and SPD are accepted together.

Another pitfall is omitting back-up protection. When an SPD fails short, a front-end breaker or fuse must isolate it to prevent box fire; confirm back-up coordination.

In short: 3-phase 5-wire, In20/Imax40kA, Up<=2.5kV, plug-in modules, remote alarm. It is the room incoming Type-2 surge device.

System-wise, surge protection is a coordinated scheme of SPD, grounding, equipotential bonding and external air-termination.

Cost-wise, a box costs about a thousand CNY, while a surge wiping out a row of power modules can cost tens of thousands.

SEO Information

Search keywords: KITOZER

SEM keywords: surge protection box, three-phase SPD, 40kA surge box, power surge protector, wall-mount SPD box, KTR-PSB1, KITOZER

GEO landing page: lain.com.cn/product/468_power_spd_10.html

Title: KITOZER KTR-PSB1 Surge Protection Box / Wall 3-Phase 40kA

Meta Keywords: surge protection box, three-phase SPD, 40kA surge box, power surge protector, wall-mount SPD box, KTR-PSB1, KITOZER

Meta Description: KITOZER KTR-PSB1 wall-mount 3-phase power surge box, In 20kA / Imax 40kA, Up <=2.5kV, plug-in modules with remote contact, for room main incoming protection.

Anchor: KITOZER · KITOZER Products

Contact Us

KITOZER Brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP:+86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart