1. Overview
Water leaks are the most overlooked yet costliest room incident. A dripping AC condensate pipe, a chilled-water pipe sweating under the floor, a fresh-air duct, or water seeping from a restroom next door — any of these can cost tens of thousands of dollars when it reaches servers or power gear. A leak system has two parts: the sensing cable laid under likely water sources (under ACs, along pipes, under the floor) and the controller that reads the cable, detects water and reports it via RS485 or relay to the EM host. There are non-locating controllers (alarm only) and locating controllers (report distance along the cable). Long cable runs need locating; otherwise ops must trace dozens of meters by hand.
KITOZER KTR-WLC is a locating water leak controller. Housing: desktop or DIN-rail, ABS panel, LCD showing current location and status; input: one locating sensing cable loop up to 100 m, displays distance in meters to the leak; outputs: RS485 Modbus-RTU plus 2 relays (NO/NC, to shut down AC or trigger sounder); power: DC12-24 V, under 3 W. Models: KTR-WLC-L: single-channel locating, 100 m max; KTR-WLC-L2: dual-channel locating, two independent loops; KTR-WLC-N: non-locating (alarm only), half the price. Matching sensing cable KTR-RL-100: 6 mm OD, 100 m per spool, -10 to +60 C, cut-to-length, with end terminator resistor.
Selection: locating vs non-locating (over 10 m needs locating); cable length (5-10 m around an AC, 20-50 m along a mains pipe); channel count (use dual-channel for separate water zones); output matching (RS485 to the EM host, or relay if only dry contacts). Note: do not run the sensing cable alongside power trays, do not step on it, and always fit the end terminator or the controller faults out.
2. Key Features
Detection
- Locating accuracy +/-1 m
- Max 100 m cable
- Response <1 s
- Dual channel (L2)
Outputs
- RS485 Modbus-RTU
- 2 relay NO/NC
- LCD location
- Sound/light indicator
Build
- Desktop / DIN rail
- DC12-24 V wide range
- ABS flame-retardant
- <3 W power
3. Specifications
| Item | KTR-WLC-L | KTR-WLC-L2 | KTR-WLC-N |
|---|---|---|---|
| Type | Locating | Dual locating | Non-locating |
| Cable | 100 m | 2×100 m | 100 m |
| Accuracy | +/-1 m | +/-1 m | None |
| Output | RS485+2 relay | RS485+4 relay | Relay |
| Display | LCD location | LCD location | LED |
| Power | DC12-24V | DC12-24V | DC12-24V |
| Use | AC zone | AC+pipe | Small room |
4. Reference Prices
KTR-WLC-L single-channel locating: Reference USD 62 to 90 / unit (ref. CNY 450-650 at ~7.2)
KTR-WLC-L2 dual-channel locating: Reference USD 104 to 146 / unit (ref. CNY 750-1050 at ~7.2)
KTR-WLC-N non-locating: Reference USD 31 to 49 / unit (ref. CNY 220-350 at ~7.2)
KTR-RL-100 sensing cable (100 m): Reference USD 53 to 78 / roll (ref. CNY 380-560 at ~7.2)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Beneath precision AC units
- Under-floor chilled-water runs
- Next to fresh-air drain pans
- Restroom / pantry shared walls
- Power room fire pipes
6. Deployment & Installation
Cable run
- Loop around water source
- Tie down, do not step
- Leave ends for connectors
- Fit end terminator
Mount
- Controller on rack wall
- Daisy-chain RS485
- Relay interlocks shutdown
- No duplicate DIP
Commission
- Spray-test locating
- Calibrate distance offset
- Set alarm thresholds
- Log baseline
7. FAQ
- Q: Is the locating model worth the price gap?
A: It depends on room size. Under 10 m, a non-locating alarm says water is present and you can see it on entry. Over 20 m, a non-locating alarm sends you tracing dozens of meters by flashlight, taking half an hour. The locating model says 8.3 m from the end and you walk straight to it in minutes. Large rooms need locating. - Q: Can the sensing cable be cut and extended?
A: Yes. The locating cable is a four-wire resistive network; cut it and rejoin with the matching connector, and length can be adjusted to any number of meters. Each joint adds about 0.5 m of locating error, so keep joints to a minimum. Always fit the 150 ohm end terminator, or the controller faults continuously. - Q: How to reduce false alarms?
A: Common causes: dust and oil on the cable lower insulation; wipe the cable with a damp cloth. The cable lies on a damp floor under raised floors; keep the floor dry and elevate the cable 1-2 cm. Condensation dripping from a nearby pipe is actually a real leak; link to AC dehumidification. Missing end terminator causes a permanent fault. - Q: How long does the sensing cable last?
A: 3-5 years. Prolonged immersion, foot traffic and UV accelerate aging. Spray-test once a year to confirm the controller sees the signal; replace when the jacket cracks or discolors. Do not wait until the cable snaps — a broken section is blind to leaks.
8. Trend & Selection
Leak detection is moving from discrete cable runs to full-floor sensing. Newer approaches use conductive floor mats, fiber-optic temperature/leak sensing and capacitive sensor arrays that cover the whole floor instead of one cable. But cable systems are cheap, accurate and fast to install, and remain the workhorse in traditional precision-AC rooms. Smart direction: leak controllers link to the BMS to shut nearby water valves, start drain pumps and notify ops. Wireless leak cables (battery-powered, LoRa/Zigbee) are growing in old rooms where cabling is hard. Select by: locating for large rooms, cable length covering all likely sources, end terminator, RS485 to EM host, relay interlocked to water valves, and an annual spray test.
9. Delivery & Service
KITOZER supplies KTR-WLC by model. Each ships with unit, mounting accessories and manual. 1-year warranty; batch projects can bundle peripheral gear and on-site commissioning.
10. Additional Notes
Confirm port specs, power rating and communication protocol against field equipment before ordering; keep clear of strong EMI and heat sources; verify wiring and labels before energizing. For batch orders, request samples first to confirm compatibility with existing systems.
Common mistake: comparing price but ignoring parameters. Models in the same series look similar, but ports, load and accuracy differ — wrong models cause on-site rework. Send the full part number (including suffix such as -SM/-MM/-S) to sales to confirm.
Second pitfall: not planning service space. Leave at least 600 mm rear cable/service space and 800 mm front operating space, or future swaps and cable work become painful.
Third blunder: shipping factory alarm thresholds. Default thresholds rarely match site conditions — tune them after commissioning based on real readings to avoid both false and missed alarms.
Selection summary: match site conditions first, pick model, reserve service space, calibrate thresholds on-site, and pilot one unit before bulk.
SEO Information
Search keywords:KTR-WLCKITOZER
SEM keywords:water leak controller,locating leak detection,room leak cable,leak sensor,KTR-WLC,KITOZER
GEO landing page:lain.com.cn/product/ktr-wlc-water-leak-controller.html
Title:KITOZER KTR-WLC Locating Water Leak Controller
Meta Keywords:water leak controller,locating leak detection,room leak cable,leak sensor,KTR-WLC,KITOZER
Meta Description:KITOZER KTR-WLC locating water leak controller with sensing cable, precise leak location, RS485 plus relay, for room EM systems.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com