The KITOZER ZGS11-Z-500/10 American style pad mounted box substation integrates a 500 kVA oil immersed transformer, HV load break switch, and LV distribution breaker into a single weatherproof steel enclosure. It steps 10 kV medium voltage down to 0.4 kV and feeds commercial parks, residential communities, shopping plazas, and industrial plant perimeter substations. The loop feed or radial feed arrangement reduces cabling cost, while the fully sealed enclosure eliminates outdoor bushings and improves safety. American style design is compact, tamper resistant, and widely used in urban distribution where space is limited and visual impact matters.
Technical Specifications
Rated transformer 500 kVA, HV 10 kV loop feed, LV 0.4 kV, Dyn11, impedance 4.0 percent. HV side: load break switch with 630 A rated, 20 kA short time, fusible switch with current limiting fuses. LV side: main breaker 800 A, branch breakers up to 4 x 400 A or 12 x 100 A depending on configuration. Enclosure sheet steel, RAL paint, IP33 weatherproof, lockable doors. Temperature rise top oil 60 K. Mineral oil quantity 250 kg. Ground lightning arrester on HV side. Cable entry underground. Overall dimensions approximately 2200 x 1400 x 1800 mm. Weight 2200 kg. Complies with ANSI/IEEE C57.12.26, IEC 60076.
Application Scenarios
Pad mounted units are the standard choice for residential community power, commercial plaza feeders, school campus distribution, hospital back up substations, and industrial site perimeter supply. The loop feed configuration allows two medium voltage cables to pass through, enabling ring network supply and improving reliability. Underground cable entry keeps sidewalks clean and safe. Lockable doors and tamper proof design protect public areas. The unit is often used in place of indoor substations when building space is unavailable, and it blends into landscaping with decorative paint options.
Advantages
Factory integrated package reduces site wiring and commissioning time. Loop feed HV switch allows sectionalizing without shutting down the whole ring. Current limiting fuses protect the transformer from internal faults. LV breaker compartment provides organized distribution with modular breakers. Weatherproof steel enclosure withstands rain, dust, and UV. Front and rear door access simplifies maintenance. Compact footprint saves civil work. Five year warranty covers transformer, switch, and breakers.
Installation and Maintenance
Place on a concrete pad at least 100 mm above grade with drainage slope. Provide underground HV and LV cable conduits. Keep 1.0 m clearance around doors for operation. Before energizing, verify HV cable phase sequence, LV branch breaker configuration, and ground connection. Operate HV load break switch manually a few times to confirm smooth action. Maintenance every two years: inspect gasket, tighten breakers, test oil dielectric, clean arrester. Every six years: oil sample dissolved gas analysis, hinge and lock lubrication. Keep pad free of vegetation and water pooling. The unit should not be moved after cable connection without disconnecting underground cables.