Ladder-Type Open Cable Tray Installation, Wiring and Commissioning Manual

Scope of Application: Selection, installation, wiring, commissioning, operation & maintenance, and acceptance of ladder-type open cable trays in scenarios such as data center computer rooms, telecommunication equipment rooms, and industrial power distribution rooms.

Applicable Standards: JB/T 10216-2013 *Cable Tray for Electric Control and Power Distribution*, GB 50303-2015 *Acceptance Standard for Construction Quality of Building Electrical Engineering*, GB 50311-2016 *Code for Engineering Design of Generic Cabling System*, GB 50174-2017 *Code for Design of Data Centers*, T/CECS 31-2017 *Technical Specification for Engineering of Steel Cable Tray*

Version Number: V2.0

Compiled by: Guangdong Lain Intelligent Computer Room Equipment Co., Ltd.

Service Hotline: +86 13538869979 (Same number for WeChat)

Technical Support: +86 13538869979

Company Address: Zhongrun Industrial Park, No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou City

Official Website: https://gdlain.com

Table of Contents

Preface

The ladder-type open cable tray (also known as ladder-type cable tray or open ladder tray) is a core cable support and management carrier in modern computer room cabling systems. Its unique ladder-shaped open-frame structure offers multiple advantages including high-strength load-bearing, efficient heat dissipation, flexible deployment, and convenient maintenance. It is widely used in data centers, telecommunication equipment rooms, industrial control, commercial buildings, and many other fields. With the rapid development of the digital economy, the demands for high-density cabling, heat dissipation for high-computing-power equipment, and high-reliability power supply in computer rooms continue to escalate. The ladder-type open cable tray, with its strong adaptability and low full-lifecycle cost, has become the preferred solution for main trunk cabling in computer rooms.

This manual is based on current national standards and industry practices, combined with years of R&D and engineering experience in computer room cabling products by Guangdong Lain Intelligent Computer Room Equipment Co., Ltd. It systematically elaborates the full-process content of ladder-type open cable trays, including product definition, structural composition, classification and selection, technical parameters, installation and construction, cable routing and laying, system commissioning, maintenance and fault handling, and acceptance standards. It aims to provide comprehensive, professional, and implementable technical guidance for engineering design units, construction units, and operation & maintenance units, ensuring the safe, reliable, and long-term operation of the ladder-type open cable tray system.

This manual covers full lifecycle management from product delivery to final acceptance, taking into account the differentiated requirements of ordinary computer rooms and high-grade data centers. It also provides specific explanations for special requirements in computer room cabling scenarios (such as separation of power and communication lines, cold/hot aisle adaptation, fire and lightning protection, and energy-saving heat dissipation). If technical questions arise during use, please contact our technical support hotline for targeted solutions.

Chapter 1 Product Introduction

1.1 Product Definition and Basic Overview

A ladder-type open cable tray is an open cable support component formed by two longitudinal side rails and multiple transverse ladder rungs (cross members) fixed together. The overall structural form resembles a ladder, hence the name ladder-type cable tray, abbreviated as ladder tray. Unlike the closed/semi-closed structures of trough-type and tray-type cable trays, the ladder-type open cable tray has no continuous bottom plate or cover plate (which can be added as required). Cables are placed directly on the transverse rungs, with air able to circulate freely on all sides, making it a typical open-type cabling carrier.

From a functional perspective, the core role of the ladder-type open cable tray is to provide structured support and routing paths for various types of cables, including power cables, control cables, telecommunication optical cables, and network twisted-pair cables, while achieving classified cable management, mechanical protection, heat dissipation optimization, and electrical safety assurance. In computer room cabling systems, ladder-type open cable trays typically undertake the laying of main trunk cables, working together with trough-type trays, wire mesh trays, cable organizers, and other products to form a complete cabling hierarchy.

According to the definition in JB/T 10216-2013, a cable tray refers to the general term for a continuous rigid structural system composed of troughs, ladder sections (straight sections, bends, branches), accessories, and supports/suspensions used to support cables. The ladder-type open cable tray is one of the most widely applied structural types, particularly suitable for laying large-diameter, high-current-capacity power cables and high-density trunk cables.

1.2 Product Development History and Technical Evolution

1.2.1 Global Cable Tray Technology Development Trajectory

The development of cable tray technology is deeply tied to the advancement of the power industry and building electrical industry. In the early 20th century, with the rapid development of industry in Europe and America, power cables in factories were initially laid using angle-steel welded brackets and wooden wire ducts, which had problems of complex installation, poor protection, and low standardization. In the 1930s, the United States took the lead in launching steel trough-type cable trays, achieving factory prefabrication and on-site assembly for cable laying, greatly improving construction efficiency.

In the 1960s, with the enlargement of industrial plants and the increase in power cable cross-sections, the defects of closed-type cable trays — insufficient heat dissipation, excessive self-weight, and high cost — gradually became apparent, and the ladder-type open cable tray came into being. Its open-frame structure significantly reduced material usage and overall self-weight while greatly improving heat dissipation efficiency, perfectly adapting to the laying requirements of large cross-section power cables. It quickly became widespread in heavy industries such as petrochemicals, electric power, and metallurgy.

In the 1990s, with the rise of the data center and telecommunications industries, computer room cabling imposed higher requirements on heat dissipation performance, expansion flexibility, and maintenance convenience. The ladder-type open cable tray, leveraging the natural advantages of its open structure, gradually extended from the industrial sector to computer room scenarios, becoming the mainstream solution for data center trunk cabling. Concurrently, product technology continued to evolve, giving rise to aluminum alloy materials, stainless steel materials, long-span structures, modular splicing, and other upgraded forms.

1.2.2 Domestic Development History of Ladder-Type Open Cable Trays

China’s cable tray industry began in the 1980s. Initially, foreign technologies and production lines were introduced, with products mainly consisting of trough-type and tray-type trays, applied primarily to large industrial projects and municipal engineering. In the early 1990s, domestic enterprises began independent R&D of ladder-type cable trays, and product standards were gradually established. In 1991, the first cable tray industry standard, JB/T 10216-1991, was issued, followed by two revisions in 2000 and 2013, forming the current technical specification system.

After 2000, the domestic internet and data center industry experienced explosive growth, with a surge in computer room cabling demand, and the ladder-type open cable tray entered a period of rapid development. On one hand, product specifications continued to expand, developing from the single ordinary steel ladder tray into multiple series including fire-resistant, anti-corrosion, long-span, and partition-plate types. On the other hand, production processes were continuously upgraded, with technologies such as cold-bend roll forming, automated welding, and high-precision surface treatment being widely applied, greatly improving product precision and quality.

In recent years, with the promotion of the dual-carbon policy and the construction of high-density data centers, the energy-saving and heat-dissipation value of ladder-type open cable trays has been further highlighted. The products are also developing toward intelligence, with some high-end products integrating intelligent modules such as cable temperature monitoring, fire early warning, and load monitoring, upgrading from traditional mechanical support components to intelligent cabling infrastructure.

1.3 Positioning of Ladder-Type Open Cable Trays in the Computer Room Cabling System

Computer room cabling systems are typically divided into three levels: the trunk cabling subsystem, the horizontal cabling subsystem, and the work area subsystem. The ladder-type open cable tray undertakes the core trunk load-bearing function among these, with the specific positioning as follows:

1.3.1 Core Carrier for Trunk Cabling

Large-pair-count power cables, trunk optical cables, and large-pair-count network cables running from the main distribution frame (MDF) to each floor distribution frame (IDF), and from the power distribution room to the cabinet row distribution units in a computer room, are typically laid using ladder-type open cable trays. These cables are numerous, large in diameter, and generate high heat. The open structure of the ladder tray provides ample load-bearing capacity and heat dissipation space, while also facilitating batch cable laying during the construction phase and expansion adjustments during the operation & maintenance phase.

1.3.2 Physical Basis for Power/Communication Separation

Power cables and communication signal cables in a computer room must maintain sufficient separation to avoid electromagnetic interference. Ladder-type open cable trays can achieve layered laying of power and communication cables through multi-tier suspension layouts, or metal partition plates can be installed within a single-layer tray for same-layer isolation. They serve as an important physical carrier for implementing electromagnetic compatibility requirements in computer rooms.

1.3.3 Wiring Solution Compatible with Cold/Hot Aisle Containment

In data center computer rooms with cold/hot aisle containment, the overhead cable routing system above cabinets predominantly uses ladder-type open structures. Cables naturally descend from the tray into the cabinets without obstructing the flow of cold and hot air. Additionally, the open-frame structure of the tray itself does not impede air conditioning return airflow, helping to improve computer room cooling efficiency and reduce PUE.

1.3.4 Flexible Platform for Maintenance and Expansion

With rapid business iteration in computer rooms, cable additions, removals, and adjustments are frequent. The coverless design of the ladder-type open cable tray allows maintenance personnel to directly observe cable conditions and quickly troubleshoot faults. When adding new cables, there is no need to remove cover plates — cables can be laid directly — greatly improving maintenance efficiency and expansion flexibility while reducing the risk of business interruption.

1.4 Comparative Analysis with Other Types of Cable Trays

The cable tray types commonly used in computer room cabling currently include ladder-type open cable trays, trough-type cable trays, tray-type cable trays, and wire mesh cable trays. These products differ significantly in structure, performance, and applicable scenarios. The specific comparison is as follows:

Comparison Dimension Ladder-Type Open Cable Tray Trough-Type Cable Tray Tray-Type Cable Tray Wire Mesh Cable Tray
Structural Form Two side rails + transverse rungs, fully open with no bottom plate Fully enclosed trough body + cover plate, enclosed on all sides Perforated bottom plate + side rails, semi-enclosed with optional cover Welded metal mesh structure, open-frame with perforations
Heat Dissipation Performance Excellent — 360° air circulation, lowest cable temperature rise Poor — heat accumulates in enclosed space Fair — bottom perforations assist heat dissipation Excellent — mesh open-frame provides strong ventilation
Load-Bearing Capacity Strong — side rail load-bearing structure, suitable for long spans and heavy loads Medium — overall trough body load-bearing, limited span Medium — bottom plate load-bearing, relatively short span Weak — mesh structure has limited load capacity, short spans only
Protection Performance Weak — no dust or waterproof capability Strong — dustproof, foreign object protection, some waterproof capability Medium — bottom dustproof, sides open Weak — fully open-frame with no protection
Electromagnetic Shielding Weak — no shielding effect Strong — enclosed structure can shield electromagnetic interference Fair — semi-enclosed with limited shielding effect Weak — no shielding effect
Installation Efficiency High — modular splicing, light weight Low — heavy weight, cumbersome cover plate installation Medium — moderate weight High — clip-on connection, fastest installation
Maintenance Convenience Excellent — directly visible, convenient expansion Poor — cover plate removal required Fair — cover plate removal required Excellent — cables can be added or removed at any time
Applicable Cables Large cross-section power cables, trunk optical cables, high-density cables Control cables, signal cables, low-voltage circuits Small and medium cross-section power and control cables Network patch cords, optical fibers, lightweight cables
Unit Cost Relatively low Relatively high Medium High

From the perspective of computer room suitability, the ladder-type open cable tray has irreplaceable advantages in laying trunk power cables and trunk optical cables. It is typically used in combination with trough-type trays: trunk routes use ladder trays, while horizontal cabling branching to cabinets uses trough-type or wire mesh trays, forming a layered cabling architecture of “open trunk, enclosed branches” that balances the multiple requirements of heat dissipation, load-bearing, protection, and maintenance.

1.5 Product Standards and Specification Basis

The ladder-type open cable trays produced by our company strictly comply with the following national and industry standards. All indicators meet or exceed the standard requirements:

1. Product Manufacturing Standard: JB/T 10216-2013 *Cable Tray for Electric Control and Power Distribution* — specifies the classification, technical requirements, test methods, and inspection rules for cable trays.

2. Engineering Construction Standard: GB 50303-2015 *Acceptance Standard for Construction Quality of Building Electrical Engineering* — specifies the construction quality requirements and acceptance indicators for cable tray installation.

3. Cabling Design Standard: GB 50311-2016 *Code for Engineering Design of Generic Cabling System* — specifies the design and selection requirements for cable trays in generic cabling systems.

4. Data Center Standard: GB 50174-2017 *Code for Design of Data Centers* — proposes special requirements for cable tray routing in data center scenarios.

5. Steel Cable Tray Specification: T/CECS 31-2017 *Technical Specification for Engineering of Steel Cable Tray* — details the engineering design, construction, and acceptance requirements for steel cable trays.

6. Standard Atlas: 04D701-3 *Cable Tray Installation* — provides common structural configurations and installation detail drawings for cable tray installation.

7. Fire Protection Standard: GB/T 51410-2020 *Standard for Technical Application of Building Fire Stop* — specifies the sealing requirements for cable trays penetrating fire compartments.

8. Seismic Standard: GB 50981-2014 *Code for Seismic Design of Mechanical and Electrical Equipments in Building* — specifies the seismic design and installation requirements for cable tray systems.

1.6 Product Naming Rules and Model Number Meaning

Ladder-type open cable trays use national standard universal naming rules. The model number consists of three parts: type code, specification code, and material & surface treatment code. A complete model number example: XQJ-T-600×200-HD-G, with each part explained as follows:

  • XQJ: Cable tray series code (X-Cable, Q-Tray, J-Rack)
  • T: Structure type code — T denotes ladder type (ladder)
  • 600×200: Specification code, in mm; the former is the tray width, the latter is the tray height
  • HD: Load class code — A-Light, B-Medium, C-Heavy, D-Extra Heavy
  • G: Surface treatment code — D-Electro-galvanized, R-Hot-dip galvanized, S-Electrostatic powder coating, F-Fire-resistant coating, L-Aluminum alloy, B-Stainless steel

Products with special structures will have additional supplementary codes after the type code, for example:

  • T-G: Partition plate ladder-type cable tray
  • T-K: Long-span ladder-type cable tray
  • T-S: Double-side-rail reinforced ladder-type cable tray
  • T-W: Ladder-type cable tray with cover plate

Chapter 2 Product Composition

The ladder-type open cable tray system consists of six major categories of components: main structural components, connection and fixing components, support and suspension components, electrical grounding components, functional expansion components, and protective identification components. Each component group is modularly designed and can be flexibly combined according to on-site requirements, adapting to different installation scenarios and cabling needs.

2.1 Main Structural Components

The main structural components are the core load-bearing part of the ladder-type open cable tray, directly supporting the weight of cables. They include four basic units: straight sections, bend sections, branch sections, and transition sections.

2.1.1 Side Rails

Side rails are the longitudinal primary load-bearing members of the ladder tray, located on both sides of the tray and running through the entire tray length. They are equivalent to the main beams of a bridge, determining the overall load-bearing capacity and span limits of the tray.

Cross-section Forms: Common cross-sections include C-type cold-bent sections, U-type sections, rectangular tube sections, and I-type sections. Standard specifications commonly use C-type cold-bent side rails, formed in a single pass from steel plate through roll forming, offering high section moment of inertia and good mechanical performance. For long-span and heavy-load specifications, double-fold-edge reinforced or rectangular tube sections are used to further enhance bending resistance.

Material and Process: High-quality carbon structural steel Q235B cold-rolled steel plate is used as the base material, formed through continuous cold-bend roll forming. The side rails are flat and free from deformation, with passivated edges and no burrs or sharp edges. High-end products use aluminum alloy 6063-T5 or stainless steel 304/316L to suit special environmental requirements.

End Structure: Each tray section has pre-fabricated connection end plates at both ends with standard connection holes. These mate with connection plates for segment splicing. The end plates are fixed to the side rails by welding or riveting to ensure connection strength.

Thickness Specifications: Different plate thicknesses are matched according to tray width and load class. For width ≤200mm, side rail thickness ≥1.2mm; for width 300-500mm, ≥1.5mm; for width 600-800mm, ≥2.0mm; for width ≥900mm, ≥2.5mm. Heavy loads may require additional thickness as needed.

2.1.2 Rungs (Cross Members)

Rungs, also called crossbars or steps, are the transverse load-bearing members of the tray. They are evenly distributed between the two side rails and directly support the cables, equivalent to the steps of a ladder.

Cross-section Forms: Common cross-sections include U-type, C-type, I-type, and round tube types. U-type rungs are the most common form due to their material efficiency and high stiffness. I-type rungs have the best bending performance and are used for heavy-load scenarios. Round tube rungs have smooth surfaces that avoid scratching cable jackets, making them suitable for optical fiber and fine cable laying.

Spacing: The standard rung spacing is 250mm. Spacings of 200mm and 300mm can be customized based on cable diameter and load requirements. Smaller spacing provides more uniform load distribution but increases material usage; excessive spacing can cause small-diameter cables to sag. For computer room scenarios, the 250mm standard spacing is recommended for a balance of load-bearing and economy.

Connection Method: Rung ends are connected to the side rails by gas-shielded welding or riveting. Weld joints are anti-corrosion treated, with full penetration and no false or missed welds. Riveted structures have a smooth appearance without welding deformation, suitable for high-precision applications.

Mechanical Characteristics: Rungs follow a simply supported beam loading mode, fixed at both ends to the side rails and bearing uniformly distributed cable loads in the middle. Their bending strength determines the local load-bearing capacity of the tray.

2.1.3 Straight Sections

Straight sections are the standard linear units of the ladder-type open cable tray, used for straight route laying. They are the most widely used main components.

Standard Lengths: Common standard lengths are 2000mm and 3000mm. Long-span specifications can be manufactured in 6000mm sections, reducing splice points and improving installation efficiency and overall rigidity. Special lengths can be customized according to on-site requirements.

Specification Range: Widths cover 100mm-1200mm, heights cover 50mm-300mm, forming a complete specification matrix to meet the laying requirements of different cable quantities and diameters.

Precision Requirements: Straight section straightness deviation ≤1.5‰, end plate parallelism deviation at both ends ≤0.5mm, and connection hole position deviation ≤0.3mm, ensuring flush and seamless splicing.

2.1.4 Bend Sections

Bend sections are used at turns in the tray route to achieve smooth cable bends, avoiding damage to cables from sharp-angle bends.

Angle Classification: Divided by turn angle into 90° bends, 45° bends, 30° bends, and 15° bends. Special angles can be customized.

Direction Classification: Divided by turning direction into horizontal bends (left/right turns in the horizontal plane), vertical upward bends (upward turns in the vertical plane), vertical downward bends (downward turns in the vertical plane), and combined left/right and up/down bends.

Bending Radius: The inner bending radius of bend sections must be greater than the minimum allowable bending radius of the cables being laid. For conventional power cables, the bend bending radius is ≥300mm. Large cross-section cables can be customized with 500mm or 800mm large-radius bends. The minimum bending radius for cross-linked polyethylene insulated power cables is 15 times the cable outer diameter, so bend design must reserve sufficient allowance.

Reinforcement Design: Bend sections experience more complex forces than straight sections, typically using thickened plates and reinforcement ribs. The side rails transition in an arc at the bend, with no stress concentration points.

2.1.5 Branch Sections

Branch sections are used at bifurcation points in the tray route to achieve cable distribution from the trunk to branches. Common types include tees and crosses.

Horizontal Tee: The trunk extends straight with a branch emerging from the side, forming a “T” structure. This is the most commonly used branch component, used for extending branch routes from the trunk tray to cabinet rows.

Vertical Tee: The trunk extends horizontally with a branch extending in the vertical direction, used for connections between floors or between upper and lower tray levels.

Horizontal Cross: The trunk extends straight with branches emerging on both sides, forming a “+” structure, used at intersection route nodes.

Reducing Tee/Cross: The trunk and branch have different specifications, enabling distribution connections between trays of different widths.

2.1.6 Transition Sections

Transition sections are used for transitional connections between trays of different widths/heights, achieving smooth changes in route specifications and preventing cables from jamming or being compressed at transition points.

Straight Transition: Different widths at both ends with a straight transition, used for scenarios where trunk tray specifications gradually decrease.

Eccentric Transition: One side of the transition section is flush while the other side contracts, mostly used for wall-mounted or alignment-mounted installations to keep the tray side flush and aesthetically pleasing.

Height Transition: Different heights at both ends, used for height transitions where loads change or installation space is limited.

Transition Length: The standard transition section length is 500mm. The transition angle is gradual to avoid excessively small cable bending radii. Large-specification transitions can be extended to 800-1000mm.

2.2 Connection and Fixing Components

Connection and fixing components are used to achieve splicing and fixing between main tray sections, as well as connections between the tray and support structures. They are key to ensuring the overall integrity and stability of the system.

2.2.1 Connection Plates

Connection plates are the core connecting components for splicing tray sections. They fit against the outside or inside of the tray side rails and fasten two tray sections together as one unit via bolts.

Type Classification: Divided into straight connection plates, bend connection plates, tee connection plates, etc., matched to the end shapes of different main components to ensure tight-fitting connections.

Material and Specifications: Made of the same material steel plate as the tray body, with thickness no less than the side rail thickness. Surface treatment is consistent with the tray to ensure uniform anti-corrosion performance.

Hole Design: Standard connection holes are pre-fabricated on the connection plates, corresponding one-to-one with the holes on the tray end plates. Standard specifications have 4-6 connection holes per side; heavy specifications have 8-10 holes to ensure connection strength.

Splicing Effect: After correct installation, the gap at the splice between two tray sections is ≤1mm, with relative offset (top/bottom, left/right) ≤0.5mm, resulting in an overall flat and smooth finish.

2.2.2 Fastener Sets

Fasteners are used for connections between connection plates and trays, and between trays and brackets. They consist of bolts, nuts, flat washers, and spring washers.

Bolt Specifications: Common hex bolts for tray body connections are M6, M8, and M10. Bolt sizes for bracket connections are typically M10, M12, and M16. Length is matched to the connection thickness, ensuring the bolt protrudes 2-3 threads beyond the nut.

Material and Surface Treatment: Galvanized carbon steel bolts are used for standard scenarios, stainless steel bolts for anti-corrosion scenarios, and 8.8-grade high-strength bolts for high-strength scenarios. All fasteners are rust-treated and pass salt spray tests.

Anti-loosening Design: Spring washers or lock nuts are provided to prevent bolt loosening in vibrating environments, ensuring long-term connection reliability. Computer room environments have minimal vibration, so standard spring washers are sufficient to meet anti-loosening requirements.

Installation Specification: Tray connection bolts should be inserted from the inside with nuts on the outside — on one hand to avoid protruding bolts scratching cables, and on the other hand to facilitate tightening operations from the outside.

2.2.3 Tray Clamp Plates

Tray clamp plates are used to fix the tray body to bracket crossbars or support arms, preventing tray displacement, slippage, or shaking.

Structural Forms: Common forms include L-type clamp plates, Ω-type clamp plates, and clip-type clamp plates. The L-type clamp plate has a simple structure, pressing the tray side through bolts. The Ω-type clamp plate provides better wrapping and firmer fixing, suitable for vibrating environments. The clip-type clamp plate requires no bolts — pressing it into place fixes it, offering high installation efficiency.

Material and Specifications: Made of galvanized steel plate by stamping, with 2-3mm thickness, smooth surfaces with no burrs, and anti-corrosion performance consistent with the tray.

Setting Requirements: Each tray section must have at least 2 sets of clamp plates. Additional clamp plates are required at bends, branches, and ends, with spacing of no more than 2m.

2.3 Support and Suspension Components

Support and suspension components are used to fix the cable tray system to the building structure and bear the full weight of the tray and cables. They are the foundation of system safety. Based on installation methods, they are divided into four categories: suspension rack assemblies, bracket arm assemblies, column support assemblies, and seismic support assemblies. All support components adopt a modular design of factory prefabrication and on-site assembly, and can be flexibly selected according to installation height, load class, and building structure type.

2.3.1 Suspension Rack Assemblies

Suspension rack assemblies are suitable for top installation scenarios such as under floor slabs and under beams in computer rooms. They are the most commonly used support form in overhead cabling systems for data centers. The tray is installed overhead by suspension, occupying no floor or wall space, facilitating layered pipeline layouts and later maintenance. According to structural form and load-bearing capacity, they can be divided into four types: full-thread rod suspension racks, angle steel suspension racks, channel steel suspension racks, and prefabricated integrated suspension racks.

##### 2.3.1.1 Full-Thread Rod Suspension Racks

Full-thread rod suspension racks, also known as all-thread hanger suspension racks, are the most commonly used suspension form for light and medium load cable trays. They feature a simple structure, flexible adjustment, and low cost, and are widely used for tray installation in ordinary computer rooms and office buildings.

Structural Composition: Composed of four parts: top fixing fitting, full-thread rod, crossbar, and adjustment nuts. The top fixing fitting is secured to the building floor slab/beam bottom using expansion bolts or chemical anchors. The full-thread rod hangs vertically, with the lower end connected to the crossbar via nuts. The tray is placed on the crossbar, and the installation height can be precisely adjusted through the upper and lower adjustment nuts.

Material and Specifications: Full-thread rods are made of Q235 carbon steel with electro-galvanized or hot-dip galvanized surface treatment. Common diameters are M8, M10, M12, and M16, selected according to load and rod length. Crossbars are made of angle steel or channel steel, with specifications matched to the tray width. A single crossbar can support 1-2 sets of trays.

Applicable Scenarios: Suitable for tray width ≤600mm, uniformly distributed load ≤1.5kN/m, and rod length ≤1500mm in medium and below load scenarios. This is the mainstream suspension solution for horizontal trunk trays in computer rooms.

Installation Requirements: A single suspension rack group must be configured with at least 2 rods, symmetrically distributed on both sides of the tray. Rod verticality deviation ≤1‰, crossbar levelness deviation ≤2mm. When rod length exceeds 1500mm, transverse diagonal bracing must be added to prevent rod sway and instability.

##### 2.3.1.2 Angle Steel Suspension Racks

Angle steel suspension racks are a reinforced suspension structure using angle steel as the primary load-bearing member. Their load-bearing capacity is superior to full-thread rod suspension racks, making them suitable for heavy-load, long-span tray installation scenarios.

Structural Composition: Composed of top fixing angle steel, vertical main suspension members, transverse load-bearing angle steel, and diagonal reinforcing angle steel. The overall structure is connected by welding or bolting to form a rigid truss structure. The top is fixed to the building structure with expansion bolts. The vertical angle steel bears tension and compression forces, the transverse angle steel supports the tray, and the diagonal angle steel enhances overall lateral sway resistance.

Material and Specifications: Typically made of Q235 equal-leg angle steel. Common specifications are ∠40×4, ∠50×5, and ∠63×6, selected according to load class and suspension height. Surface treatment is primarily hot-dip galvanizing to ensure long-term anti-corrosion performance.

Applicable Scenarios: Suitable for tray width 800-1200mm, uniformly distributed load 2-4kN/m, and suspension height 2-4m in heavy-load scenarios. Most commonly used for large cross-section power cable trunk trays leading from the main power distribution room in computer rooms.

Structural Characteristics: Good overall rigidity, strong vibration and deformation resistance, and capable of withstanding certain horizontal loads. The disadvantage is relatively high self-weight and less adjustment flexibility than rod suspension racks, making them suitable for permanent routes with stable loads and no need for frequent adjustment.

##### 2.3.1.3 Channel Steel Suspension Racks

Channel steel suspension racks are a dedicated suspension form for long-span, extra-heavy cable trays. They use hot-rolled channel steel as the primary load-bearing member, offering high section moment of inertia and excellent bending and torsional performance. They can achieve ultra-long-span suspension, reduce the number of suspension racks, and improve the cleanliness of the computer room ceiling space.

Structural Composition: The primary load-bearing beam is made of channel steel, with both ends fixed to the building structure via vertical channel steel suspension members or thick-wall rods. The main crossbeam can be arranged as single-span or multi-span continuous. The tray is directly fixed to the channel steel crossbeam. For long-span scenarios, diagonal tie rods can be added to form a truss structure, further increasing span and load capacity.

Material and Specifications: Common channel steel models are 5#, 8#, 10#, and 12#. For extra-heavy loads, 14# and 16# channel steel may be selected. The material is Q235B carbon structural steel with hot-dip galvanized surface for anti-corrosion.

Applicable Scenarios: Suitable for extra-heavy-load scenarios such as tray width ≥1000mm, multi-layer trays laid side by side, large cross-section high-voltage cable laying, and special building structures in computer rooms such as beamless floor slabs or constrained suspension spacing.

Span Capability: With 10# channel steel as the main crossbeam, the maximum span can reach 6m under a uniformly distributed load of 2kN/m, and 4m under a uniformly distributed load of 4kN/m. This can significantly reduce the number of suspension racks and minimize damage to the building ceiling.

##### 2.3.1.4 Prefabricated Integrated Suspension Racks

Prefabricated integrated suspension racks are an upgraded suspension system introduced for standardized cabling requirements in modern data centers. They use C-channel profiles and standardized clip connectors that require no welding and no drilling, enabling rapid on-site assembly and adapting to flexible and changeable computer room cabling needs.

Structural Composition: Composed of C-channel main crossbeams, C-channel vertical suspension members, universal connectors, clamp plates with clips, and top fixing bases. All components are factory-prefabricated standard parts that can be assembled using only bolts and clips. No on-site cutting or welding is required. Installation efficiency is improved by more than 50% compared to traditional suspension racks.

Material and Process: The profiles are cold-formed from Q235B cold-rolled steel plate with 2.0-3.0mm wall thickness, with hot-dip galvanized or electrostatic powder coating surface treatment. Connectors are stamp-formed with high precision and good interchangeability.

Functional Features: Achieves stepless adjustment in three dimensions — height, width, and angle can all be flexibly adjusted on-site, adapting to complex pipeline crossing scenarios in computer rooms. It is compatible with integrated support and suspension for multiple mechanical and electrical pipelines including trays, air ducts, and water pipes, enabling integrated layout of overhead pipelines in computer rooms.

Applicable Scenarios: Particularly suitable for high-density data centers, modular computer rooms, Tier 3/Tier 4 high-grade computer rooms, and IDC computer room scenarios requiring rapid deployment and frequent later adjustments.

2.3.2 Bracket Arm Assemblies

Bracket arm assemblies are suitable for wall-mounted and column-mounted tray support scenarios. The cantilever structure fixed to the wall or column supports the tray, saving horizontal space and keeping cable routes straight and tidy. They are mostly used for vertical trunk trays around computer rooms and horizontal wall-mounted trays. According to load-bearing capacity and structural form, they can be divided into three types: wall-mounted bracket arms, column-mounted bracket arms, and double/multi-layer bracket arms.

##### 2.3.2.1 Wall-Mounted Bracket Arms

Wall-mounted bracket arms are directly fixed to building walls, presenting a horizontal cantilever state. They are the most commonly used support component for wall-mounted tray installation.

Structural Composition: Composed of three parts: a vertical fixing plate, a horizontal support plate, and diagonal reinforcing ribs, integrally welded or formed in a single bending operation. The vertical fixing plate has elongated installation holes and is fixed to the wall with expansion bolts. The horizontal support plate supports the bottom of the tray. The diagonal reinforcing ribs connect the fixing plate and the end of the support plate to enhance cantilever bending resistance.

Specification Parameters: Bracket arm length (distance protruding from the wall) common specifications are 200mm, 300mm, 400mm, 500mm, and 600mm, matched to different tray widths. Load classes are divided into light, medium, and heavy, with corresponding plate thicknesses of 2.0mm, 2.5mm, and 3.0mm respectively.

Material and Surface Treatment: Made of Q235 steel plate by stamping and bending, with electro-galvanized, hot-dip galvanized, or electrostatic powder coating surface treatment to maintain anti-corrosion performance consistent with the tray body.

Installation Requirements: No fewer than 2 sets of fixing bolts are required; heavy bracket arms require no fewer than 4 sets. Bracket arm levelness deviation ≤2mm, and height deviation of bracket arms on the same route ≤3mm. When the wall is a lightweight partition wall, through-wall bolts or additional backing plates must be used for reinforcement; direct fixing with expansion bolts is prohibited.

##### 2.3.2.2 Column-Mounted Bracket Arms

Column-mounted bracket arms are installed on dedicated support columns rather than directly fixed to building walls. They are mostly used in multi-layer tray systems supported by independent columns in computer rooms, enabling layered support of multi-layer trays.

Structural Form: One end of the bracket arm has a slot or connection holes that can clip or bolt into the C-type slot of the column. The other end extends horizontally to support the tray. The installation height can be arbitrarily adjusted along the vertical slide slot of the column, and the layer spacing is flexibly adjustable.

Specification Matching: Bracket arm length corresponds to tray width. Rated load for a single-layer bracket arm ranges from 0.5kN to 3kN. When arranged in multiple layers, the overall load-bearing capacity of the column must be verified.

Installation Features: Does not rely on building walls; column-based tray channels can be established at any location in the computer room. Level height adjustment is convenient, and when adding new tray layers later, there is no need to re-drill — offering extremely strong expansion capability.

##### 2.3.2.3 Double/Multi-Layer Bracket Arms

Double and multi-layer bracket arms are used for scenarios where multiple layers of trays need to be laid at the same support point. They can simultaneously support 2-4 layers of trays at the same wall-mounting point or column-mounting point, improving space utilization and enabling layered power/communication separation.

Structural Design: 2-4 horizontal support arms are provided in the vertical direction. Layer spacing can be customized according to requirements, with standard layer spacings of 200mm, 250mm, and 300mm. All layers share a common vertical fixing plate, providing uniform overall loading with single-installation completion.

Layering Principle: In computer room scenarios, power cables are typically laid in the upper layer and communication signal cables in the lower layer, with layer spacing of no less than 200mm to meet electromagnetic isolation requirements. Three-layer layouts can also be arranged based on cable type: power layer, optical cable layer, and network layer.

Load Verification: The total load of multi-layer bracket arms must be calculated, with matching fixing bolts and wall load-bearing capacity. This prevents bracket arm deformation or detachment caused by excessive total load.

2.3.3 Column Support Assemblies

Column support assemblies are suitable for floor-installed cable tray systems, commonly seen in scenarios such as under-floor cabling in computer rooms, overhead laying above cable trenches, and floor-level trough transitions. The floor-standing columns support the tray at a specified height, offering strong load-bearing capacity and good stability.

##### 2.3.3.1 Single-Section Columns

Single-section columns use a single C-channel steel or I-beam as the vertical main column, fixed to the ground at the bottom with bracket arms installed at the top or side to support the tray. They are the common form for light floor-standing support.

Specification Parameters: Common C-channel steel column specifications are 100×50, 120×60, and 150×70, with 2.5-4.0mm wall thickness. Common I-beam columns are 10#, 12#, and 14#, suitable for heavy-load scenarios.

Bottom Fixing: The column bottom is welded to a base plate and fixed to the ground with expansion bolts. The base plate size is no less than 200×200mm to ensure sufficient bearing area. When the floor is an anti-static raised floor, the column must be fixed to the concrete floor beneath the raised floor; fixing directly to the access floor panel is prohibited.

Height Range: Common support heights are 300-2000mm. When exceeding 2000mm, horizontal tie rods and diagonal bracing must be added to ensure column stability.

##### 2.3.3.2 Twin-Section Columns

Twin-section columns are formed by two C-channel steels spliced back-to-back. The section moment of inertia is greatly increased, and load-bearing capacity is more than double that of the same-spec single-section column. They are suitable for floor-standing support of multi-layer and wide trays.

Splicing Method: Two C-channels are clamped and spliced together with bolts, with an adjustment slot reserved in the middle. Bracket arms can be inserted into the slot and adjusted to any height. The splicing bolt spacing is no greater than 500mm to ensure overall rigidity.

Applicable Scenarios: Mostly used in areas with dense cables such as main incoming rooms and power distribution rooms in computer rooms, where multiple layers of trays run in parallel. They can simultaneously support 4-6 layers of trays, achieving layered and classified cable management.

Stability Design: When the column height exceeds 3m, the top must be fixed to the building ceiling slab or beam, with a transverse connecting beam added every 2m in the middle, forming an overall frame structure that significantly improves lateral overturning resistance.

##### 2.3.3.3 Prefabricated Lattice Columns

Prefabricated lattice columns are assembled from modular profiles into a three-dimensional truss structure. They feature light self-weight, high load capacity, and an aesthetically pleasing appearance, and are the preferred support form for under-floor cable trays in high-end data centers.

Structural Composition: Composed of four vertical angle steel main members connected with horizontal and diagonal connecting members by bolting, forming a three-dimensional lattice column. All members are standard prefabricated parts requiring no on-site welding, offering convenient assembly.

Performance Features: Good overall stability, capable of withstanding significant horizontal and eccentric loads. The appearance is neat and uniform, consistent with the visualization and standardization requirements of computer room construction. Installation interfaces for cable troughs, grounding busbars, etc. can be pre-reserved, providing high integration.

Installation Spacing: Standard installation spacings are 1.5m, 2m, and 3m, adjusted according to the total load and the number of tray layers to ensure system deflection meets standard requirements.

2.3.4 Seismic Support Assemblies

According to GB 50981-2014 *Code for Seismic Design of Mechanical and Electrical Equipments in Building*, electrical conduits with inner diameter greater than or equal to 60mm and cable tray systems with gravity load greater than or equal to 150N/m must be equipped with seismic support hangers to resist horizontal and vertical seismic loads, prevent tray detachment and collapse, and ensure the basic functions of power and communication systems after an earthquake. The seismic support assemblies for ladder-type open cable trays mainly include three types: lateral seismic supports, longitudinal seismic supports, and bidirectional seismic supports.

##### 2.3.4.1 Lateral Seismic Supports

Lateral seismic supports are used to resist horizontal lateral seismic forces on the tray system, preventing transverse displacement and detachment of the tray. They are the most basic seismic components.

Structural Composition: Composed of seismic hinge joints, diagonal seismic braces, full-thread rods, seismic clamp blocks, and top fixing seats. The diagonal braces are made of galvanized | set | Includes bolts and nuts, ring-clamping type radial fixing, suitable for vibration and seismic scenarios |

7 Clip-type tray clamp plate Compatible with standard C-type side rails Q235B + flame-retardant engineering plastic Galvanized set Bolt-free press-clip fixing, installation efficiency improved by 50%, suitable for light and medium trays
8 Adjustable clamp plate Adjustment range ±20mm Q235B Galvanized set With elongated adjustment holes, compatible with multiple tray specifications for universal fixing, adapts to on-site installation tolerances
9 Splice gap compensation shim 0.5mm / 1mm / 2mm thick Q235B Galvanized piece Placed between splicing end faces to compensate for section length deviations and installation errors, ensuring tight splices
10 Lateral limit stop plate 50mm high Q235B Galvanized set Installed on the crossbar on both sides of the tray to limit transverse tray displacement and prevent sliding and detachment
11 Expansion bolt set M8 / M10 / M12 / M16 High-quality carbon steel Blue-white zinc / Hot-dip galvanized set Includes expansion sleeve, bolt, nut, flat washer; used for anchoring support hangers to building structures
12 Chemical anchor bolt set M10 / M12 / M16 / M20 Alloy steel rod + epoxy resin agent Hot-dip galvanized set Dedicated anchoring for heavy support hangers; strong anchoring force, suitable for heavy-load scenarios in concrete structures
13 Anti-loosening lock nut M6 / M8 / M10 / M12 Carbon steel Galvanized piece Nylon ring self-locking type, used with connecting bolts; excellent anti-loosening performance in long-term vibration environments
14 Toothed lock washer M6 / M8 / M10 / M12 65Mn spring steel Galvanized piece Dedicated for grounding connections; cuts through metal oxide layers and coatings during tightening to effectively reduce contact resistance
15 Spring washer M6 / M8 / M10 / M12 65Mn spring steel Galvanized piece Standard anti-loosening accessory; provides axial preload to prevent bolt rotation loosening
16 Flat washer M6 / M8 / M10 / M12 Carbon steel Galvanized piece Increases bearing area, protects component surfaces from nut indentation, distributes tightening stress

[TO BE CONTINUED — Part 2 of 4]

4.3 Support and Suspension Component List

The support and suspension components bear the overall load transfer function of the cable tray system, uniformly transmitting the tray’s self-weight and cable loads to the building structure. They are the core load-bearing components ensuring system safety and stability. This series covers all installation scenarios including suspension, wall-mounting, floor-standing, and seismic-resistant mounting. All components are factory-prefabricated standard parts that can be quickly assembled on site. The detailed list is as follows:

No. Component Name Specification/Model Material Surface Treatment Unit Matching Description
1 Full-thread threaded rod M8 / M10 / M12 / M16 Q235B carbon steel Electro-galvanized / Hot-dip galvanized Meter Length can be cut as required; pairs with upper and lower adjustment nuts for stepless height adjustment
2 Rod top fixing base Corresponding to rod diameter Q235B Galvanized Pc Used with expansion bolts for vertical fixation of rods to floor slabs and beam bottoms
3 Rod cross-arm connector Corresponding to rod + cross-arm specification Q235B Galvanized Set For perpendicular orthogonal connection and fixation of rod to cross-arm; features anti-slip teeth to prevent displacement
4 Angle steel cross-arm ∠40×4 / ∠50×5 / ∠63×6 Q235B Hot-dip galvanized Pc Length matches tray width; single unit supports 1-2 sets of parallel trays; suitable for medium loads
5 Channel steel cross-arm 5# / 8# / 10# / 12# Q235B Hot-dip galvanized Pc Specialized for long-span, heavy-load scenarios; large section moment of inertia; excellent bending and torsional resistance
6 C-channel prefabricated beam 41×21 / 41×41 / 62×42 Q235B Hot-dip galvanized / Electrostatic powder coating Meter Specialty profile for prefabricated suspension systems; slotted opening allows stepless adjustment of mounting position; highly adaptable
7 Universal swivel connection base Compatible with 41-series C-channel Q235B Galvanized Pc Top fixing component for prefabricated suspension systems; multi-angle swivel adjustment; adapts to sloped and irregular structures
8 C-channel dedicated connector 2-hole / 4-hole / 8-hole Q235B Galvanized Set Specialized splicing, direction-changing, and reinforcement connectors for C-channel systems; standardized snap-fit installation
9 Wall-mounted bracket arm 200 / 300 / 400 / 500 / 600 mm length Q235B Hot-dip galvanized / Electrostatic powder coating Set Includes fixing bolt set; available in light, medium, and heavy load grades; dedicated for wall mounting
10 Column-mounted bracket arm 300 / 400 / 500 / 600 mm length Q235B Galvanized Set Clip-on installation; compatible with C-channel support columns; height steplessly adjustable along column
11 Double-layer bracket arm Layer spacing 200 / 250 / 300 mm Q235B Galvanized Set Achieves double-layer cable routing at a single support point; dedicated for segregated laying of power and signal cables; uniform overall load distribution
12 Multi-layer bracket arm 3-layer / 4-layer, layer spacing 250 mm Q235B Galvanized Set Layered management of multiple cable routes; suitable for cable-dense areas such as power distribution rooms and cable entry rooms
13 Single C-channel column 100×50 / 120×60 / 150×70 Q235B Hot-dip galvanized Meter Main structural component for floor-standing support; pairs with base plates and various bracket arms; flexible installation
14 Column base plate 200×200 / 300×300 / 400×400 mm Q235B Galvanized Piece Bottom fixing component for columns; increases ground contact area and reduces localized ground pressure
15 Double-column connecting piece Corresponding to column specification Q235B Galvanized Set Specialized fitting for back-to-back splicing of two C-channels; increases column section moment of inertia and load capacity
16 Column horizontal tie beam Corresponding to column specification Q235B Galvanized Pc Horizontal reinforcement member between multiple columns; enhances overall column stability and anti-tilting capability
17 Lateral seismic support Compatible with tray width 100-1200 mm Q235B Hot-dip galvanized Set Includes diagonal brace, seismic hinge, and seismic clamping block; resists lateral horizontal seismic forces
18 Longitudinal seismic support Compatible with tray width 100-1200 mm Q235B Hot-dip galvanized Set Includes diagonal brace, seismic hinge, and seismic clamping block; resists longitudinal horizontal seismic forces
19 Bi-directional seismic support Compatible with tray width 100-1200 mm Q235B Hot-dip galvanized Set Integrates both lateral and longitudinal diagonal brace sets; three-dimensional seismic protection; suitable for critical route reinforcement
20 Seismic clamping block Corresponding to C-channel specification Q235B Galvanized Pc Dedicated clamping component for seismic systems; features anti-slip teeth design; strong slip resistance and reliable force transfer
21 Seismic hinge Corresponding to brace specification Carbon steel Galvanized Pc Hinged component at both ends of diagonal brace; allows flexible adjustment of installation angle; adapts to different installation spaces

4.4 Electrical Grounding Component List

The electrical grounding components ensure continuous electrical conductivity and reliable grounding throughout the cable tray system, eliminating risks of electrostatic induction and fault leakage currents, and meeting the requirements for equipotential bonding and electrical safety codes in data centers. The detailed list is as follows:

No. Component Name Specification/Model Material Surface Treatment Unit Matching Description
1 Copper-core jumper grounding wire 4mm² / 6mm² / 10mm² Stranded bare copper wire Yellow-green dual-color flame-retardant insulation Pc Both ends crimped with OT-type copper lugs; standard length 200 mm; dedicated for splicing between tray sections
2 Copper braided strip jumper wire 4mm² / 6mm² / 10mm² / 16mm² Bare copper braided strip Tinned surface Pc High flexibility; suitable for vibration and large-angle bending scenarios; electrical conductivity superior to insulated copper wire
3 Dedicated grounding bolt M8 / M10 Carbon steel / 304 stainless steel Galvanized / Passivated Set Supplied with toothed lock washers; breaks through oxide layer during tightening; effectively reduces contact resistance
4 Grounding connection plate 100×100×4 / 150×150×5 mm T2 copper / Galvanized steel Tinned / Hot-dip galvanized Piece Transition terminal plate between tray and grounding main; pre-drilled multiple holes for multi-circuit connection
5 Equipotential bonding copper busbar 30×3 / 40×4 / 50×5 mm T2 copper Tinned surface Meter Main equipotential bonding busbar in equipment room; shared by multiple system grounds; stable and reliable conductivity
6 Segmented grounding terminal block 10-position / 20-position / 30-position T2 copper Tinned Pc With insulated base; segmented wiring; convenient for branch grounding connections and future maintenance
7 Yellow-green dual-color grounding main 16mm² / 25mm² / 35mm² Stranded copper core Flame-retardant PVC insulation Meter Main grounding connection wire for tray system; connects tray to equipment room grounding main
8 Grounding insulation boot Corresponding to bolt specification Flame-retardant PVC Yellow-green dual-color Pc Insulation protection at grounding bolt end; prevents accidental short-circuit contact; also identifies grounding points
9 Grounding resistance test terminal Standard M10 interface H62 brass Nickel-plated Pc Reserved dedicated interface for grounding detection; enables periodic grounding resistance testing without dismantling structure
10 Galvanized grounding flat steel -40×4 / -50×5 mm Q235B Hot-dip galvanized Meter Connection component for building grounding main; high fault current discharge capability; long service life

4.5 Functional Expansion Component List

The functional expansion components address differentiated cable routing requirements in equipment rooms, enabling extended functions on the base cable tray system such as physical isolation, protection, cable management, fire prevention, and intelligent monitoring. These can be flexibly selected based on project scenarios. The detailed list is as follows:

No. Component Name Specification/Model Material Surface Treatment Unit Matching Description
1 Fixed metal divider plate Height 100 / 150 / 200 / 250 mm Q235B Same as tray body Meter Bolt-fixed installation; divides tray into independent compartments; achieves physical isolation of power and signal cables
2 Adjustable movable divider plate Height matching tray specification Galvanized steel sheet Galvanized Meter Clip-on installation; divider position flexibly adjustable; suits scenarios with changing cable quantities
3 Flat tray cover plate Width 100-1200 mm Q235B Same as tray body Meter Snap-on installation; dust-proof and falling-object protection; easy removal; suitable for dusty equipment room areas
4 Corrugated reinforced cover plate Width 400-1200 mm Q235B Same as tray body Meter Corrugated cross-section provides high rigidity; resistant to deformation over long spans; suitable for wide trays
5 Snap-type quick-install cover plate Width 100-600 mm Q235B / Flame-retardant ABS Galvanized / Gray Meter Built-in spring clip structure; tool-free one-press installation; high efficiency for O&M access
6 Fire-resistant dedicated cover plate Width 100-1200 mm Inorganic fire-resistant base material Fire-retardant coating Meter Used with fire-resistant cable trays; forms semi-enclosed fireproof channel; enhances overall fire resistance rating
7 Plastic cable fixing clip Compatible with standard rung spacing Flame-retardant PVC UL94-V0 grade Pc Clips onto rungs; fixes single or multiple cables; rounded edges prevent cable abrasion
8 Metal cable fixing clip For large-diameter cables 304 stainless steel Passivated surface Pc Dedicated fixing component for large cross-section power cables; high load capacity; resistant to high temperature and corrosion
9 Toothed cable management strip Compatible with tray width Flame-retardant ABS / Galvanized steel Flame-retardant / Galvanized Pc Cable organization at tray outlets; separates cables individually in sequence; prevents crossing and tangling
10 Stainless steel cable tie 4.6×300 / 7.9×500 mm 304 stainless steel Polished Pc Heavy-duty cable bundling and fixing; self-locking structure; high temperature resistant, corrosion resistant, and anti-aging
11 Flame-retardant nylon cable tie 3×150 / 5×250 / 8×400 mm Nylon PA66 Flame-retardant grade Pc For general cable bundling; UL94-V0 flame-retardant grade used in equipment room scenarios
12 Cable identification card holder Compatible with standard side rail thickness ABS engineering plastic Gray Pc Clips onto tray side rail; secures cable labels and route identification plates; tool-free installation
13 Intumescent firestop pillow 250×120×60 mm Fiberglass + flame-retardant core material Flame-retardant outer bag Bag Fireproof sealing of tray wall-penetration openings; expands upon fire exposure to seal gaps; fire resistance rating ≥ 3h
14 Organic firestop putty 2 kg/block Organic flame-retardant mastic Flame-retardant Block Flexible sealing of openings and gaps; high plasticity; adapts to cable thermal expansion and contraction
15 Inorganic firestop putty 25 kg/bag Inorganic fire-retardant mortar Flame-retardant Bag Sealing of large-area openings; high strength after curing; good load-bearing capacity; non-combustible Class A
16 Firestop partition board 1000×2000×5 mm Inorganic fire-resistant board material Flame-retardant Sheet Lining board for firestop sealing and compartment division; fire resistance rating ≥ 2h
17 Patch-type temperature sensor DS18B20 digital type Semiconductor Waterproof encapsulation Pc Real-time monitoring of cable surface temperature; measurement accuracy ±0.5℃; supports network transmission
18 Distributed temperature sensing fiber Single-mode / Multi-mode Quartz optical fiber Flame-retardant sheath Meter Full-length distributed temperature monitoring; positioning accuracy up to 1 m; enables early fire warning
19 Strain-type load sensor 0-5 kN / 0-10 kN range Alloy steel Hermetically sealed waterproof Pc Installed at support/suspension points; real-time monitoring of tray load changes; automatic overload warning
20 Airflow guide shroud Compatible with tray cross-section dimensions Galvanized steel sheet / Flame-retardant ABS Galvanized / Gray Set Guides cold airflow from equipment room to flow directionally through tray interior; enhances convective heat dissipation

4.6 Protection and Identification Component List

The protection and identification components enhance the physical safety protection level of the system, enabling standardized visual O&M and meeting the requirements for safe production and refined management in equipment rooms. The detailed list is as follows:

No. Component Name Specification/Model Material Surface Treatment Unit Matching Description
1 Tray end cap Matches side rail cross-section dimensions Flame-retardant engineering plastic / Galvanized steel Gray / Galvanized Pc Seals tray end cut; covers sharp metal edges; prevents injury to personnel and cables
2 Edge protection rubber strip Compatible with side rail thickness Flame-retardant rubber / Soft PVC UL94-V0 grade Meter Self-adhesive backing; applied to tray sharp edges; cushioning protection; prevents cable jacket abrasion
3 Rung protection sleeve Matches rung cross-section Flame-retardant silicone Flame-retardant Pc Fitted over rung surface; cushioning and vibration damping; protects delicate cables such as fiber optic and coaxial cables
4 Route identification plate 200×100 / 300×150 mm PVC / Acrylic Double-sided printing Piece Marks cable type, routing direction, origin and destination information; facilitates O&M route identification
5 Safety warning sign 300×200 mm PVC board / Aluminum plate Reflective printing Piece Includes standard warning messages such as “High Voltage Danger,” “No Stepping,” “No Storage”
6 Fire compartment identification plate 200×150 mm Aluminum plate Reflective printing Piece Installed at fire compartment penetration points; marks compartment number, fire resistance rating, and acceptance information
7 Rodent-proof baffle Height 300 / 500 mm Galvanized steel plate Galvanized Piece Installed at tray wall penetration points; smooth surface with no climbing points; prevents rodents traveling along tray
8 Stainless steel rodent-proof mesh 10 mesh / 14 mesh 304 stainless steel Passivated Piece Protection at tray openings and ventilation points; balances air circulation with small animal intrusion prevention
9 Insulation lining board Matching tray width Epoxy resin board Insulating Sheet Laid on rungs; achieves electrical isolation between cables and metal tray
10 Insulation washer M8 / M10 / M12 Nylon 66 Insulating Pc Isolation between dissimilar metal materials; prevents electrochemical corrosion; enhances insulation performance
11 Bolt anti-corrosion protective cap Corresponding to bolt specification Heat-shrink plastic Flame-retardant Pc Fitted over exposed bolt ends; sealed anti-corrosion protection; extends fastener service life
12 Expansion joint compensation device Compatible with tray specification Galvanized steel Galvanized Set Compensates for thermal expansion and contraction displacement in long-distance trays; prevents structural deformation caused by thermal stress

4.7 Typical Data Center Project Configuration Example

To facilitate engineering design and project material estimation, a standard configuration example for a main ladder-type open cable tray system is provided below, based on a typical medium-sized data center equipment room scenario.

Project Basic Parameters: Equipment room floor area 500 m², Tier 2+ level, overhead cable routing method, main tray route total length 200 m, main tray specification 600×200 mm, installed using full-thread threaded rod suspension, surface treatment hot-dip galvanized, built-in metal divider plate for power/signal segregation in the same tray, complete grounding and fire protection systems included.

No. Component Category Specification/Model Unit Quantity Remarks
1 Main structural component Ladder-type tray straight section XQJ-T-600×200 Meter 186 Heavy duty load; side rail thickness 2.0 mm; rung spacing 200 mm
2 Main structural component Horizontal 90° bend XQJ-T-W-600×200 Pc 8 Bending radius 500 mm; accommodates large cross-section cable turning requirements
3 Main structural component Horizontal tee XQJ-T-S-600×200 Pc 6 Equal-diameter tee; main route branching to rows
4 Main structural component Reducer section 600→400×200 Pc 4 Specification transition from main route to branches
5 Connection accessory 600H straight-through connection plate Piece 208 2 pieces per splice point; includes bend and tee interfaces
6 Connection accessory M8 connection bolt set Set 1250 Includes nuts, flat washers, spring washers
7 Connection accessory L-type tray hold-down plate Set 400 One support group every 2 m; 2 sets per group
8 Support component M12 full-thread threaded rod Meter 600 Rod length 1.5 m; one group every 2 m; 2 rods per group
9 Support component ∠50×5 angle steel cross-arm Pc 200 Length 800 mm; 1 per support group
10 Support component M12 expansion bolt set Set 200 For top fixation
11 Grounding component 6mm² copper core jumper wire Pc 200 1 per splice point
12 Grounding component Grounding connection plate 150×150×5 Piece 12 1 grounding point every 30 m
13 Grounding component 25mm² yellow-green grounding main Meter 80 Connects tray to equipment room equipotential bonding bar
14 Expansion component 200 mm high metal divider plate Meter 200 Power/signal segregation; continuous full-length installation
15 Protection component End cap Pc 16 Configured at all free ends of tray
16 Protection component Route identification plate Piece 20 Installed every 20 m and at bends/branch points
17 Fire protection component Firestop pillow Bag 120 Sealing at 8 wall-penetration openings
18 Fire protection component Organic firestop putty Block 16 Sealing of opening gaps

Chapter 5 Product Principles

The product design and performance of the ladder-type open cable tray are established upon four core scientific disciplines: structural mechanics, heat transfer, electromagnetic compatibility, and anti-corrosion electrochemistry. Through scientific structural design and material selection, optimal comprehensive performance is achieved across load capacity, heat dissipation efficiency, safety protection, and service life. A thorough understanding of the underlying operating principles facilitates precise selection during the engineering design phase, standard installation during the construction phase, and scientific management during the operation and maintenance phase, thereby fully realizing the product’s technical advantages and lifecycle value.

5.1 Structural Mechanics Principles

The ladder-type open cable tray is a typical flexural member system. Its mechanical essence lies in achieving maximum load capacity with minimal material usage through optimized cross-sectional configurations and load transfer paths, combining structural efficiency with economy. The entire system follows the fundamental laws of mechanics of materials and structural mechanics—from individual rungs and side rails to the overall support system—all based on rigorous mechanical calculations.

5.1.1 Longitudinal Flexural Member Mechanics

The side rails of the cable tray are the primary longitudinal load-bearing members, resisting all bending moments and shear forces generated by cable loads. Their mechanical model can be simplified as a multi-span continuous beam. According to the bending normal stress formula of mechanics of materials:

σ = M·y / I<sub>z</sub>

Where:

  • σ = normal stress on the cross-section
  • M = bending moment on the cross-section
  • y = distance from the computation point to the neutral axis
  • I<sub>z</sub> = moment of inertia of the cross-section about the neutral axis

From the formula, it is evident that the larger the section moment of inertia I<sub>z</sub>, the smaller the normal stress under the same bending moment, and the stronger the load capacity of the member. The ladder-type tray concentrates steel material at the upper and lower edges of the side rails, positioned far from the neutral axis, significantly increasing the section moment of inertia. Compared to flat-plate structures of the same thickness, the flexural efficiency of the section can be improved by 3-5 times. This is the core reason for the high material utilization efficiency and strong load capacity of the ladder-type structure.

Under uniformly distributed load q, the maximum mid-span bending moment of a simply supported beam is:

M<sub>max</sub> = qL² / 8

Where L is the calculated span of the beam. This demonstrates that the bending moment is proportional to the square of the span—doubling the span increases the bending moment by four times. Therefore, span is the critical parameter affecting the load capacity of the cable tray. In engineering applications, the span must be verified against the actual load to ensure that the maximum bending normal stress does not exceed the allowable stress of the material, and that deflection meets the code limits.

Deflection is the core indicator for measuring tray rigidity. Excessive deflection can cause cable sagging, structural fatigue, and even safety hazards. The maximum mid-span deflection formula for a simply supported beam under uniformly distributed load is:

f<sub>max</sub> = 5qL⁴ / (384EI<sub>z</sub>)

Where:

  • E = elastic modulus of the material (for steel, taken as 2.06×10⁵ MPa)

According to JB/T 10216-2013, under the rated uniformly distributed load, the relative deflection of the tray shall not exceed 1/200 of the span. This limit ensures structural safety while balancing engineering economy. The high moment of inertia cross-section of the ladder-type tray effectively controls deflection values. Under identical load and span conditions, the deflection is significantly less than that of trough-type or wire mesh trays, making it more suitable for long-span and heavy-load scenarios.

5.1.2 Transverse Rung Load-Bearing Principles

Rungs are the transverse load-bearing members of the tray, directly supporting the cable weight. Both ends connect to the side rails, and their mechanical model is that of a simply supported beam subjected to localized uniformly distributed loads and concentrated loads. The flexural strength of the rungs determines the localized load capacity of the tray, while their spacing directly affects the flatness of cable laying and overall material cost.

The maximum mid-span bending moment of a rung is directly related to the cable distribution pattern: when cables are uniformly laid across the full width, the rung experiences a uniformly distributed load; when a single large-diameter cable is placed at mid-span, it experiences a concentrated load. Engineering design verifies the most unfavorable condition to ensure that rungs do not undergo plastic deformation or fracture under extreme circumstances.

The rung spacing is established through rigorous mechanical balance and economic calculations: if spacing is too small, the number of rungs increases, raising material costs; if too large, small-diameter cables will exhibit noticeable sagging between two adjacent rungs—both aesthetically undesirable and potentially damaging to cables due to prolonged bending. For the cable diameter range commonly used in equipment room scenarios, the 250 mm standard spacing represents the optimal balance point, ensuring that cables with diameters of 10 mm and above show no noticeable sagging while keeping material usage within a reasonable range. For scenarios with dense small-diameter fiber optic cables and network cables, a 200 mm densified spacing may be selected; for scenarios dominated by large-diameter power cables, a 300 mm spacing may be used to further reduce costs.

5.1.3 Support System Load Transfer Path

The entire ladder-type open cable tray system has a clearly defined load transfer path. All loads are ultimately uniformly transferred to the main building structure, and every node along the path has been strength-verified with no weak links. The specific load transfer path is:

Cable self-weight and superimposed loads → rung transverse members → side longitudinal side rails → splice connection nodes → tray hold-down plates → cross-arm/bracket arm → suspension rod/column → building structure (floor slab, beam, wall, ground)

In suspension systems, the suspension rods primarily bear axial tension, requiring verification of tensile strength and slenderness ratio. When the rod length exceeds a certain proportion of its diameter, instability and swaying can occur. Therefore, code requires the addition of lateral diagonal bracing when rod length exceeds 1.5 m, using triangular stable structures to enhance overall lateral displacement resistance. In floor-standing column systems, columns primarily bear axial compression, requiring verification of axial compression stability while considering additional bending moments from eccentric loads. Taller columns require multiple lateral tie beams to reduce the effective length and enhance stable load capacity.

Connection nodes are the critical links in the load transfer path—their strength often determines the ultimate load capacity of the entire system. Tray splice nodes transfer loads through connection plates and multiple bolt groups, requiring verification of bolt shear strength and hole wall bearing strength of members. Hold-down plate fixation nodes require verification of anti-slip load capacity to ensure the tray does not slip or detach under horizontal forces. The safety factor of all connection nodes is no less than 1.5, ensuring sufficient overall system safety redundancy.

5.1.4 Seismic Structure Load-Bearing Principles

Under seismic action, the tray system experiences not only vertical gravity loads but also horizontal seismic inertial forces. Ordinary vertical suspension rods are axial force members with extremely weak bending resistance; under horizontal loads they are prone to bending deformation or even fracture, causing the tray to detach. The seismic support system converts horizontal inertial forces into axial tension or compression in the diagonal braces through the addition of inclined bracing members, transferring them to the building structure, thereby resisting seismic action.

According to GB 50981-2014, the standard value of horizontal seismic action is calculated as:

F = α · G

Where:

  • F = standard value of horizontal seismic force
  • α = seismic influence coefficient
  • G = representative value of total gravity load of the tray system

The angle between the seismic diagonal brace and the vertical suspension rod should preferably be 45°, at which the ratio of axial force to horizontal force component in the brace is optimal and material utilization is highest. When restricted by spatial constraints, the angle may be adjusted within the range of 30°-60°, with corresponding strength verification of the brace required.

Seismic supports adopt hinged node designs that can accommodate certain angular deviations and displacement deformations, avoiding stress concentration. They are also equipped with dedicated clamping blocks featuring anti-slip teeth, ensuring no relative slip between the tray and cross-arm, and guaranteeing reliable transfer of seismic forces. Through the combined arrangement of lateral and longitudinal seismic supports, seismic protection in both horizontal directions of the tray system is achieved, ensuring the system does not detach or collapse after an earthquake, thereby safeguarding the basic functions of power and communication lines and providing fundamental conditions for post-disaster rescue and recovery.

5.2 Heat Dissipation and Heat Transfer Principles

The ampacity of cables is directly related to operating temperature. The better the heat dissipation conditions, the higher the allowable ampacity for cables of the same cross-section, the slower the insulation aging rate, and the longer the service life. The ladder-type open cable tray, with its unique fully open-work structure, offers the optimal heat dissipation performance among all types of cable trays—one of its irreplaceable core advantages in high-density equipment room scenarios.

5.2.1 Cable Heat Generation and Dissipation Mechanisms

When a power cable is energized, current flowing through the conductor generates Joule heat. The heat generation rate per unit time is:

Q = I²R

Where:

  • I = conductor current
  • R = conductor resistance

Conductor resistance increases with temperature, creating a positive feedback loop. If heat cannot be dissipated promptly, the conductor temperature will continue to rise, ultimately accelerating insulation layer aging and shortening service life. In severe cases, insulation breakdown can occur, causing short circuits and fire accidents. Therefore, the heat dissipation conditions of cables directly determine their safe ampacity and operational reliability.

The cable heat dissipation process consists of three stages: first, heat generated in the conductor transfers through the insulation and sheath layers to the cable outer surface via thermal conduction; second, the cable outer surface transfers heat to the surrounding air through convective and radiative heat transfer; third, the surrounding air carries heat away through air movement. In cable tray installation scenarios, the heat transfer efficiency of the second stage is the key factor determining overall heat dissipation capability. The structural form of the tray directly affects the contact area between cables and air, as well as the air flow velocity.

According to power engineering design codes, the ampacity of cables within cable trays must be corrected based on tray type. The ampacity correction factor for cables in enclosed trough-type trays is typically 0.7-0.8, while that for ladder-type open trays can reach 0.9-1.0. This means that for cables of the same cross-section, the allowable ampacity in ladder-type trays is 15%-30% higher than in trough-type trays, significantly improving cable utilization and reducing engineering cable costs.

5.2.2 Open Structure Convective Heat Dissipation Advantages

Convective heat transfer is the primary mode of cable heat dissipation. The heat transfer formula is:

Q<sub>c</sub> = h · A · Δt

Where:

  • Q<sub>c</sub> = convective heat transfer rate
  • h = convective heat transfer coefficient
  • A = heat transfer area
  • Δt = temperature difference between cable surface and air

The ladder-type open cable tray improves heat dissipation efficiency from two dimensions simultaneously—heat transfer area and heat transfer coefficient:

First, heat transfer area is maximized. The ladder-type tray has no bottom plate or side plates obstructing airflow; cables are in direct contact with air in all four directions (top, bottom, left, right), with effective heat transfer area approaching 100% of the cable surface area. In trough-type trays, however, the cable bottom and sides are obstructed by the trough body, reducing effective heat transfer area to only 40%-60%, with heat tending to accumulate at the bottom.

Second, the convective heat transfer coefficient is higher. In open structures, air circulates freely. Hot air around cables can rise and disperse promptly while cold air continuously replenishes, forming a good natural convection circulation. In contrast, enclosed trays have poor internal air mobility, relying primarily on thermal conduction and natural convection with low heat transfer coefficients. Heat tends to accumulate within the trough, creating localized high-temperature zones.

According to measured data, under identical cable load and ambient temperature conditions, the cable surface temperature in ladder-type open trays is 5-8℃ lower than in trough-type trays and 3-5℃ lower than in tray-type (perforated) trays. Given the rule that insulation life is halved for every 8-10℃ increase in cable operating temperature, the ladder-type tray significantly extends cable service life while reducing energy losses from operating temperature rise, aligning with green and energy-efficient development directions.

5.2.3 Equipment Room Airflow Organization Compatibility

Modern data centers commonly adopt cold aisle/hot aisle containment air conditioning airflow organization. Cold air enters from the cold aisle through the front of racks, absorbs equipment heat, exits from the rear into the hot aisle, and returns to the air conditioning unit through overhead return air. The open-work structure of the ladder-type open cable tray offers minimal obstruction to equipment room airflow organization, perfectly adapting to this layout. Enclosed trays, in contrast, tend to block airflow and create localized heat islands.

When the tray is arranged above the hot aisle, hot air can pass directly through the open-work areas of the tray and rise into the return air ceiling without accumulating beneath the tray. If an enclosed tray were used, hot air would be blocked by the bottom plate and accumulate below the tray, causing elevated rack outlet temperatures and uneven return air temperatures, thereby reducing air conditioning cooling efficiency. When the tray is arranged above the cold aisle, cold air can fully contact the cable surfaces, actively cooling the cables and further reducing cable operating temperatures.

CFD simulation validation shows that in identical equipment room environments, scenarios using ladder-type open trays achieve a 15% improvement in rack inlet air temperature uniformity and approximately 8% improvement in overall air conditioning cooling efficiency compared to scenarios using trough-type trays. Correspondingly, the room PUE can be reduced by 0.03-0.05. For large-scale data centers, this translates to substantial annual cooling energy savings, delivering significant economic benefits and environmental value.

5.3 Electromagnetic Compatibility Principles

Equipment rooms simultaneously contain high-voltage power cables and low-voltage signal cables. The alternating electromagnetic fields generated by power cables can induce electromagnetic interference in signal cables, degrading signal transmission quality, increasing bit error rates, and in severe cases causing system failures. The ladder-type open cable tray effectively suppresses electromagnetic interference through three methods: layered routing, metal divider plate isolation, and reliable grounding, meeting the electromagnetic compatibility requirements of structured cabling systems.

5.3.1 Electromagnetic Interference Generation Mechanism

When alternating current flows through a conductor, it generates an alternating magnetic field in the surrounding space. Other conductors within this magnetic field experience induced electromotive force—this is electromagnetic induction interference. The magnitude of the interference voltage is proportional to the interfering source current and the parallel routing length, and inversely proportional to the square of the cable spacing. For sensitive circuits such as analog signals and high-frequency communication signals, even minute interference voltages can disrupt normal operation.

Common interference sources in equipment rooms include low-voltage power cables, UPS power supply cables, and variable frequency drive supply cables. Sensitive circuits include network cables, fiber optic cables, control cables, and security signal lines. According to GB 50311-2016 “Code for Engineering Design of Generic Cabling System,” minimum separation distances must be maintained when generic cabling cables are routed parallel to power cables. When spacing falls below the specified values, shielding and isolation measures must be implemented.

5.3.2 Layering and Segregation Isolation Principles

The first method by which the ladder-type open cable tray achieves electromagnetic compatibility is layered routing—placing power cables and signal cables on different tray layers and attenuating interference through spatial distance. When layer spacing reaches 300 mm, electromagnetic interference attenuation exceeds 30 dB, satisfying the anti-interference requirements of the vast majority of low-voltage systems. When layer spacing reaches 500 mm, attenuation exceeds 40 dB, suitable for high-frequency, high-sensitivity signal circuits.

The second method is the installation of metal divider plates on the same layer, utilizing the electromagnetic shielding effect of metal plates to attenuate interference. The shielding principle of metal divider plates is based on eddy current effects and reflection losses. The alternating magnetic field induces eddy currents in the metal plate, and the reverse magnetic field generated by these eddy currents partially cancels the original magnetic field. Simultaneously, electromagnetic waves experience reflection loss at the metal surface. When a continuous metal divider plate of the same height as the tray is used, shielding effectiveness can reach 20-25 dB—equivalent to doubling the spatial separation—enabling power and signal cables to be routed in the same tray in space-constrained scenarios, significantly saving routing space.

It is important to note that the metal divider plate must be fully continuous and reliably grounded to provide shielding effectiveness. If the plate is discontinuous or improperly grounded, shielding performance degrades substantially and may even aggravate interference through coupling effects. Therefore, construction must ensure tight plate splicing and good grounding continuity.

5.3.3 Grounding Discharge and Equipotential Principles

A reliably grounded metal tray itself can serve as a common shielding body, further reducing electromagnetic interference. When the tray is fully conductive and grounded at multiple points, induced electromagnetic noise can be discharged to earth through the grounding system, preventing charge accumulation that could form secondary interference sources. Additionally, a fully equipotential tray system eliminates potential differences between different sections, avoiding interference coupling caused by ground potential differences.

For low-voltage systems, the equipotential grounding of the tray also provides a uniform reference ground for the shielding layers of shielded cables, enhancing the overall shielding effectiveness of shielded cables. When shielded cables are routed in a properly grounded ladder-type tray, comprehensive shielding effectiveness can be improved by 10-15 dB, further ensuring signal transmission quality.

5.4 Anti-Corrosion Protection Principles

Steel cable trays undergo corrosion when exposed to environmental media, progressively weakening member cross-sections and reducing structural strength and service life. The ladder-type open cable tray achieves different grades of corrosion resistance through multiple surface treatment processes, utilizing electrochemical protection and physical isolation principles, suitable for environments ranging from dry indoor spaces to highly corrosive outdoor locations.

5.4.1 Steel Electrochemical Corrosion Mechanism

Steel in humid air undergoes oxygen-absorption corrosion, the essence of which is an electrochemical galvanic cell reaction: iron acts as the anode, losing electrons and oxidizing to ferrous ions; oxygen at the cathode gains electrons and reacts with water to form hydroxide ions; the final products are ferrous hydroxide, further oxidized to hydrated ferric oxide—rust. During the reaction, moisture and oxygen are necessary conditions; therefore, the higher the environmental humidity and oxygen content, the faster the corrosion rate. If corrosive media such as chloride ions or sulfur dioxide are present in the environment, the corrosion process is further accelerated. For example, in coastal salt-spray environments and chemical corrosive environments, the steel corrosion rate is 5-20 times that of ordinary indoor environments.

The damage from corrosion to the tray system is progressive and irreversible: the initial stage manifests as surface rust spots, affecting appearance; the middle stage sees increased corrosion depth, reduced effective member cross-sections, and decreased load capacity; severe cases can lead to weld rust-through and bolt rust fracture, causing structural safety accidents. Therefore, selecting the appropriate anti-corrosion treatment based on environmental classification is the key to ensuring long-term reliable operation of the tray.

5.4.2 Zinc Coating Cathodic Protection Principle

Electro-galvanizing and hot-dip galvanizing are the most commonly used anti-corrosion processes for cable trays. Their anti-corrosion principle belongs to the sacrificial anode cathodic protection method. Zinc has higher chemical activity than iron and a lower electrode potential. In corrosive environments, the zinc layer preferentially corrodes as the anode, while the internal steel substrate is protected as the cathode. Even if the zinc layer is locally damaged exposing the steel, the surrounding zinc continues to provide cathodic protection—no localized accelerated corrosion occurs.

Simultaneously, the zinc layer gradually oxidizes in air, forming a dense passivation film of zinc oxide and basic zinc carbonate that prevents further penetration of oxygen and moisture, slowing the corrosion rate of the zinc layer itself and creating a self-protection effect. Hot-dip galvanized coatings achieve thicknesses of 65 μm or more and form metallurgical bonds with the steel substrate, providing exceptional adhesion and resistance to peeling. In ordinary indoor environments, anti-corrosion service life can exceed 30 years; in outdoor environments, 15-20 years—making it the most cost-effective anti-corrosion solution.

Electro-galvanized coatings are relatively thin, typically only 8-15 μm, with shorter anti-corrosion service life, suitable only for dry indoor environments. However, their coatings are uniform, with smooth appearance and high dimensional precision, making them suitable for indoor scenarios with high appearance requirements.

5.4.3 Powder Coating Physical Isolation Principle

The electrostatic powder coating process involves uniformly spraying plastic powder onto the steel surface, which forms a dense plastic coating after high-temperature curing. Its anti-corrosion principle belongs to the physical isolation method—completely isolating the steel substrate from external air, moisture, and corrosive media, interrupting the electrochemical corrosion circuit to achieve corrosion protection.

Powder coatings possess good insulation and corrosion resistance, customizable colors, smooth and aesthetically pleasing appearance, and certain impact and abrasion resistance. Since plastic is non-metallic and does not undergo electrochemical corrosion, its anti-corrosion performance in weak acid and weak alkali environments is superior to zinc coatings. However, once the powder coating is chipped or damaged, localized corrosion occurs on the exposed steel substrate at the damage site. Due to obstruction by the surrounding coating, the corrosion is not easily detected and may spread internally. Therefore, powder-coated trays are more suitable for dry indoor environments with minimal impact and mild corrosion.

To remedy this deficiency, high-end powder-coated trays typically employ a “galvanizing + powder coating” dual treatment—first applying an electro-galvanized or hot-dip galvanized base layer, then powder coating the surface. This preserves the cathodic protection effect of the zinc layer while providing the physical isolation and decorative effects of the powder coating, delivering excellent corrosion resistance and appearance—the mainstream surface treatment solution for high-end equipment room scenarios.

Chapter 6 Product Technical Parameters

This chapter systematically lists the core technical parameters of the ladder-type open cable tray, covering six dimensions: dimensional specifications, mechanical performance, electrical performance, anti-corrosion performance, fire protection performance, and environmental adaptability. All parameters are established based on relevant national standards and third-party test results, and may serve as technical basis for engineering design, selection verification, and acceptance inspection. Our company can provide customized parameter specifications upon special project requirements.

6.1 Basic Dimensional Parameters

The ladder-type open cable tray adopts a standardized specification system. Width ranges from 100 mm to 1200 mm, and height ranges from 50 mm to 300 mm, forming a complete product matrix suitable for different cable capacity and load grade requirements. The standard dimensional parameters of conventional steel ladder trays are shown in the following table:

Specification (W×H) mm Side Rail Thickness mm Rung Thickness mm Standard Rung Spacing mm Standard Section Length mm Theoretical Weight kg/m Rated Uniform Load kN/m Allowable Span mm Max Deflection at Rated Load mm
100×50 1.2 1.0 300 2000 2.1 0.5 1500 7.5
200×100 1.5 1.2 250 2000 4.2 1.0 2000 10.0
300×100 1.5 1.2 250 2000 5.3 1.2 2000 10.0
300×150 1.5 1.5 250 2000 6.5 1.5 2000 10.0
400×100 1.5 1.5 250 2000 6.8 1.2 2000 10.0
400×150 2.0 1.5 250 2000 8.7 1.8 2000 10.0
400×200 2.0 1.5 250 2000 9.8 2.0 2000 10.0
500×150 2.0 1.5 250 2000 10.2 1.8 2000 10.0
500×200 2.0 2.0 200 2000 12.1 2.5 2000 10.0
600×150 2.0 2.0 250 2000 12.5 2.0 2000 10.0
600×200 2.0 2.0 200 2000 14.3 3.0 2000 10.0
800×200 2.5 2.0 200 3000 19.7 3.5 2000 10.0
1000×250 2.5 2.5 200 3000 26.8 4.0 2000 10.0
1200×300 3.0 2.5 200 3000 35.2 5.0 2000 10.0

Parameter Notes:

  • Theoretical weight is the tray body weight only, excluding cover plates, divider plates, and accessories;
  • Rated uniform load is the maximum uniform load at which deflection ≤ 1/200 of span is satisfied;
  • Long-span custom specifications can achieve load requirements at 3-6 m spans through thickened side rails and reinforced cross-sections;
  • Aluminum alloy trays of the same specification weigh approximately 40%-50% of steel trays, with rated load approximately 60%-70% of steel trays.

6.2 Mechanical Performance Parameters

Performance Item Parameter Value Remarks
Base material yield strength Q235B ≥ 235 MPa; Q355B ≥ 355 MPa Compliant with GB/T 700
Base material tensile strength Q235B 375-500 MPa Compliant with GB/T 700
Material elastic modulus 2.06×10⁵ MPa Steel elastic modulus at room temperature
Relative deflection at rated load ≤ 1/200 of span JB/T 10216 standard limit
Ultimate load safety factor ≥ 1.5 Ratio of ultimate load to rated load
Weld tensile strength ≥ 95% of base material standard value Gas shielded welding process
Connection bolt shear strength Grade 4.8 ≥ 140 MPa; Grade 8.8 ≥ 320 MPa Compliant with GB/T 3098.1
Hold-down plate anti-slip coefficient ≥ 0.3 Galvanized surface contact
Suspension rod tensile strength ≥ 375 MPa Q235 material rod
Column axial compression stability coefficient Calculated per GB 50017 Slenderness ratio λ ≤ 150

6.3 Electrical Performance Parameters

Performance Item Parameter Value Remarks
Inter-section contact resistance ≤ 0.001 Ω After standard connection plate bolt tightening
Full-length continuity resistance ≤ 0.1 Ω/100m Resistance between two ends of a complete 100 m spliced tray
System grounding resistance ≤ 1 Ω (combined grounding); ≤ 4 Ω (independent grounding) Compliant with GB 50303
Equipotential bonding continuity resistance ≤ 0.1 Ω Between tray and equipotential bonding bar
Powder coating insulation resistance ≥ 100 MΩ Tested with 500 V megger
Electromagnetic shielding effectiveness with divider plate ≥ 20 dB Continuous metal divider plate; 10 MHz – 1 GHz frequency band
Fault current withstand capability ≥ 10 kA/1s Complete tray grounding system

6.4 Anti-Corrosion Performance Parameters

Surface Treatment Method Average Coating Thickness Neutral Salt Spray Test Pass Time Indoor Expected Service Life Outdoor Expected Service Life
Electro-galvanizing 8-15 μm ≥ 72 h 5-8 years 2-3 years
Hot-dip galvanizing 65-85 μm ≥ 720 h 30+ years 15-20 years
Electrostatic powder coating 60-100 μm ≥ 500 h 15-20 years 8-10 years
Galvanizing + powder coating (dual-layer) Zinc layer ≥ 40 μm + powder layer ≥ 60 μm ≥ 1000 h 25+ years 12-15 years
304 stainless steel Base material body ≥ 2000 h 50+ years 30+ years
316L stainless steel Base material body ≥ 5000 h 50+ years 40+ years

6.5 Fire Protection Performance Parameters

Performance Item Standard Steel Tray Fire-Resistant Tray Remarks
Base material fire performance Non-combustible Class A Non-combustible Class A Metal base materials are all non-combustible
Structural fire resistance rating ≥ 15 min ≥ 60 min (90 min customizable) Time maintaining structural integrity
Fire-retardant coating oxygen index – ≥ 35% Oxygen index of fire-retardant coating
Smoke density rating – ≤ 15 Meets low-smoke requirements
Combustion toxicity – ZA1 grade Quasi-safe grade
Matching seal fire resistance rating – ≥ 3 h At fire compartment penetrations

6.6 Environmental Adaptability Parameters

Performance Item Parameter Value Remarks
Operating ambient temperature -40℃ ~ +120℃ Applicable range for standard steel trays
Storage ambient temperature -50℃ ~ +150℃ No long-term high-temperature deformation
Relative humidity ≤ 95% (non-condensing) Hot-dip galvanized treatment
Seismic fortification intensity ≤ 9 degrees Satisfied with matching seismic supports
Wind load resistance (outdoor) ≤ 0.55 kN/m² Corresponds to Beaufort scale 10 wind
Installation altitude ≤ 4000 m Derating required above 4000 m
Chemical corrosion resistance grade C1-C5 grades Corresponds to different grades based on material and surface treatment

Chapter 7 Product Functions and Characteristics

As the core load-bearing component of the computer room cabling system, the ladder-type open cable tray combines basic physical load-bearing functions with multiple scenario-specific optimization features, offering irreplaceable comprehensive advantages in main trunk cabling scenarios within computer rooms. This chapter provides a comprehensive elaboration from three dimensions — core functions, general characteristics, and computer room-specific optimizations — to offer users a clear reference for product selection and application.

7.1 Core Basic Functions

7.1.1 Cable Load-Bearing and Laying Function

Load-bearing is the most fundamental and core function of the cable tray. Through its high-strength side rails and rung structure, the ladder-type open cable tray provides stable and reliable mechanical support for various power cables, control cables, communication optical cables, and network cables, evenly transmitting cable weight to the building structure. This prevents excessive stretching and sagging of cables due to their own weight, ensuring cable structural integrity and stable electrical performance.

The cable tray system provides a standardized, planned laying path for cables, keeping cable arrangement neat and orderly, avoiding the clutter, tangling, and uneven stress caused by random laying. It also facilitates batch laying during the construction phase and route identification during later maintenance, significantly improving the standardization and management efficiency of cabling projects.

7.1.2 Cable Classification Management Function

The ladder-type open cable tray can achieve physical separation and classified management of different types, voltage levels, and functions of cables through layered laying and the installation of separators. Classified laying of strong-current and weak-current cables, power and signal cables, and primary and backup cables within the computer room not only reduces electromagnetic interference and improves system reliability, but also facilitates rapid cable location by maintenance personnel, reducing fault troubleshooting time and preventing accidental contact with other circuits during maintenance operations.

For special scenarios such as classified (secure) computer rooms, physical isolation between classified and non-classified cables can be achieved through independent cable tray compartments, meeting confidentiality management requirements. For multi-tenant IDC computer rooms, independent management of different tenants’ cables can be achieved through separation, ensuring tenant data security.

7.1.3 Mechanical Protection Function

Although of open structure, the ladder-type cable tray still provides basic mechanical protection for cables: the regular tray structure prevents cables from being punctured by sharp objects or directly crushed by heavy items, reducing the risk of external force damage; the supporting effect of the rungs keeps cables off the ground or ceiling, away from accumulated water, dust, and rodent activity areas, reducing environmental erosion and damage to cables; the cable tray at vertical riser sections can secure cables, preventing the cable’s self-weight tension from acting on end connectors, protecting terminal blocks from tensile damage.

By optionally adding accessories such as covers and protective rubber strips, the protection level can be further enhanced to meet advanced protection requirements such as dust prevention, falling object prevention, and scratch prevention, flexibly adapting to protection requirements of different scenarios.

7.1.4 Heat Dissipation Optimization Function

Heat dissipation is the core functional advantage that distinguishes the ladder-type open cable tray from enclosed cable trays. The fully openwork structure provides comprehensive natural convection heat dissipation conditions for cables, effectively reducing cable operating temperature, increasing allowable cable ampacity, and extending cable insulation life. In high-density, high-ampacity computer room scenarios, excellent heat dissipation capability avoids overload risks caused by heat accumulation in cables, improving power supply system reliability.

From a systemic perspective, good cable heat dissipation reduces additional cooling load in the computer room, lowers air conditioning energy consumption, aligns with the energy-saving development direction of green data centers, and delivers significant long-term economic benefits.

7.1.5 Electrical Safety and Grounding Function

Once continuously conductive throughout, the metal ladder-type cable tray can serve as a grounding conductor, providing a discharge path for cable fault leakage current. When cable insulation damage or phase-to-enclosure faults occur, the fault current can flow back to the power source neutral point through the cable tray grounding system, triggering circuit breaker or residual current device tripping, promptly cutting off the power supply, preventing personal electric shock and equipment damage, and ensuring electrical safety.

Additionally, a reliably grounded cable tray system eliminates static charge accumulation, preventing electrostatic discharge from causing interference and damage to sensitive electronic equipment, ensuring stable operation of computer room equipment; equipotential bonding design eliminates potential differences between different metal components, further enhancing electrical safety.

7.2 General Product Characteristics

7.2.1 Strong Load-Bearing Capacity with Significant Span Advantage

The ladder structure offers high cross-sectional stress efficiency. Under the same material usage, its load-bearing capacity far exceeds that of trough-type and wire mesh cable trays, capable of withstanding heavy loads from large-cross-section power cables. At the standard 2m span, heavy-duty specifications can withstand a uniform load of 3kN/m, and extra-heavy-duty specifications can reach 5kN/m or above, meeting load requirements of the vast majority of industrial and computer room scenarios.

Through reinforced side rail design, large spans of 3-6m can be achieved, significantly reducing the number of supports and hangers, lowering installation costs, reducing drilling damage to building structures, while avoiding other pipelines such as air ducts and water pipes, improving space utilization. This is particularly suitable for large-space computer rooms with complex piping.

7.2.2 High Heat Dissipation Efficiency, Increasing Cable Ampacity

The fully open openwork structure achieves 360° air circulation with unobstructed cable heat dissipation. Compared to trough-type cable trays, cable temperature rise can be reduced by 5-8°C, correspondingly increasing ampacity by 15%-30%. In engineering design, adopting ladder-type cable trays allows for appropriately reduced cable cross-sections, lowering cable procurement costs; in existing computer room expansion scenarios, power supply capacity can be increased without replacing cables, with low retrofit costs and short cycles.

Over long-term operation, lower operating temperatures delay cable insulation aging, extending cable service life by more than 30%, reducing maintenance costs for cable replacement and the risk of business interruption.

7.2.3 Modular Design for Convenient Installation and Construction

The ladder-type open cable tray adopts a fully modular design. All main components — straight sections, elbows, tees, reducers — are factory-prefabricated standard parts. On-site assembly requires only bolting together, with no welding or on-site cutting required. Construction efficiency is high, the working environment is clean, and it is suitable for scenarios with cleanliness requirements such as computer rooms.

Standardized connection interfaces and a universal accessory system reduce technical requirements for construction personnel and facilitate installation quality control; the weight is lighter than trough-type trays, facilitating on-site handling and overhead installation, reducing construction labor intensity and safety risks.

7.2.4 Flexible Maintenance, Convenient Expansion and Retrofit

The open structure allows direct visual inspection of all cable conditions without removing covers. Maintenance personnel can quickly locate fault points, shortening fault handling time; new cables can be laid directly without extensive cover removal or disturbance to existing cables, with minimal impact on operating systems. This is particularly suitable for high-grade computer rooms where business interruption is not permitted.

The modular structure supports flexible later expansion — cable tray sections, new branch routes, separators, and accessories can be added at any time, adapting to cabling requirement changes from business growth, with strong full-lifecycle adaptability and avoiding one-time excessive investment.

7.2.5 Outstanding Cost-Effectiveness with Low Full Lifecycle Cost

The ladder-type cable tray has high material utilization efficiency. Under the same load-bearing capacity, material consumption is less than trough-type trays, resulting in lower procurement costs; convenient installation brings lower construction costs; excellent heat dissipation brings lower cable and energy costs; convenient maintenance brings lower labor costs. Comprehensive calculations show that over a 20-year full lifecycle, the comprehensive cost of ladder-type open cable trays is 20%-30% lower than trough-type trays, offering extremely high cost-effectiveness.

7.2.6 Broad Adaptability with Full Multi-Scenario Coverage

The product range is complete, with full width coverage from 100mm to 1200mm, load ratings from light to extra-heavy, and materials and surface treatments from ordinary galvanized to stainless steel and FRP, adapting to scenarios ranging from ordinary office computer rooms to heavy industrial plants, and from dry indoor environments to strongly corrosive outdoor environments. A rich range of supporting accessories enables expanded functions such as protection, fire resistance, seismic resistance, and intelligent monitoring through optional configuration — one system can meet diverse requirements.

7.3 Computer Room Scenario-Specific Optimized Features

7.3.1 Adaptation to Hot/Cold Aisle Airflow Organization

The ladder-type openwork structure does not obstruct computer room air conditioning airflow, perfectly adapting to enclosed hot/cold aisle layouts without affecting return air and supply air efficiency, avoiding localized heat island effects, and helping maintain a uniform and stable temperature field in the computer room. CFD verification shows that compared to trough-type trays, ladder-type trays can improve computer room cooling efficiency by approximately 8%, helping reduce PUE and meeting green data center construction requirements.

7.3.2 Flexible Implementation of Strong/Weak Current Separation

Both multi-layer hanger layered laying and same-layer separator installation are supported. Implementation solutions can be flexibly selected based on computer room space conditions and interference protection levels, achieving standardized separation of strong and weak currents within limited computer room space, meeting electromagnetic compatibility standard requirements, and ensuring communication signal quality and stable equipment operation.

7.3.3 Compatibility with Various Computer Room Cabling Accessories

Compatible with cable managers, optical fiber troughs, cable runway racks, cabinet top entry devices, and other computer room-specific cabling accessories. Seamless transition with mesh cable trays and trough-type cable trays can be achieved, forming a layered cabling system of “open main trunk, enclosed branches,” adapting to refined computer room cabling management requirements.

7.3.4 Neat Appearance Suitable for Visualized Computer Rooms

Factory-standardized production ensures high dimensional accuracy, small joint gaps, and a uniform overall layout; electrostatic powder coating provides uniform color and an attractive appearance, meeting visualized and standardized construction requirements for computer rooms; a supporting standardized labeling system enables transparent management of the cabling system, enhancing the overall image of the computer room.

7.3.5 Equipotential Grounding Design Ensuring Equipment Safety

Prefabricated dedicated grounding terminals and standardized grounding accessories make grounding construction standardized and convenient, easily achieving full-route reliable grounding and computer room equipotential bonding, effectively eliminating induced electricity and fault voltage, protecting precision electronic equipment such as servers and switches from surge and potential difference damage, and improving computer room equipment operational reliability.

Chapter 8 Product Application Scenarios

With its comprehensive advantages of strong load-bearing capacity, excellent heat dissipation, and convenient maintenance, the ladder-type open cable tray is applied across numerous fields including data communications, industrial manufacturing, commercial buildings, and public facilities — with computer room cabling being its core advantageous application field. This chapter provides detailed explanations of various typical application scenarios, clarifying selection key points and considerations for different scenarios.

8.1 Data Center and IDC Computer Room Scenarios

Data centers and IDC computer rooms are the most widely applied and demand-intensive scenarios for ladder-type open cable trays. Such computer rooms have high cable density, high ampacity, and high reliability requirements, placing elevated demands on cable tray load-bearing, heat dissipation, maintenance, and expandability — characteristics with which the ladder-type cable tray is highly aligned.

8.1.1 Main Trunk Power Cable Laying

Low-voltage power main trunk cables from power distribution rooms and UPS rooms to each cabinet column head cabinet (RPP) typically have large cross-sections, large quantities, high ampacity, and high heat generation, serving as the aorta of the computer room power supply system. The high load-bearing capacity of the ladder-type open cable tray can support the weight of large-cross-section cables, and its excellent heat dissipation performance reduces cable temperature rise, improving power supply reliability and ampacity utilization rate — making it the preferred solution for main trunk power cable laying.

Selection Key Points: Heavy-duty load rating, width 600-1200mm, height 200-300mm, hot-dip galvanized or galvanized + powder coating surface treatment, with large-radius elbows, support hanger spacing of 1.5-2m, and full-route reliable grounding.

8.1.2 Main Trunk Optical Cable and Large-Pair Cable Laying

Main trunk optical cables and large-pair copper cables from the data center core switching area to each regional wiring closet are numerous with long routes, placing high demands on laying flatness, bending radius control, and maintenance convenience. The open structure of the ladder-type cable tray facilitates optical cable laying and later splicing maintenance; uniform rung support prevents excessive sagging of optical cables, ensuring transmission performance.

Selection Key Points: Medium load rating, width 300-600mm, height 100-150mm, rung spacing 250mm, optional protective rubber strips to protect optical cable jackets, layered laying or separator isolation from strong-current cable trays.

8.1.3 Column Head Cabinet Power Supply Circuit Laying

Power branch cables from column head cabinets to each equipment cabinet are numerous and densely arranged, requiring clear route management and flexible branch interfaces. The ladder-type cable tray, combined with branching components such as tees and crosses, conveniently achieves branch power supply from the main trunk to each cabinet. The open structure facilitates later circuit adjustment and expansion.

Selection Key Points: Medium load rating, width 200-400mm, arranged along the top of the cabinet row, seamlessly interfacing with cabinet entry devices.

8.1.4 Hot/Cold Aisle Overhead Routing

Data centers with enclosed hot/cold aisles commonly adopt overhead routing, with cable trays arranged above the aisles. The openwork structure of the ladder-type open cable tray does not obstruct airflow, does not affect hot/cold air circulation, and avoids localized heat accumulation problems caused by enclosed trays — making it the optimal choice for overhead-routing data centers.

Selection Key Points: Select appropriate specifications based on cable type; hot-dip galvanized anti-corrosion treatment recommended above hot aisles, powder-coated appearance models can be selected above cold aisles; support hangers should avoid the opening range of aisle enclosure doors.

8.2 Communication Room and Operator Room Scenarios

Communication rooms include operator core rooms, base station rooms, and transmission node rooms. These rooms are primarily equipped with communication equipment, have dense weak-current cables, and are simultaneously equipped with power supply systems — placing high demands on cable tray lightweight design, maintenance convenience, and reliability.

8.2.1 Base Station Room Transmission Cable Laying

Optical cables, feeders, and power cables for transmission equipment and base station equipment within base station rooms are not numerous but have complex routes, requiring flexible cabling solutions. The ladder-type cable tray’s light weight and convenient installation adapt well to the characteristics of confined base station room spaces and constrained installation conditions.

Selection Key Points: Light to medium load rating, width 200-300mm, hot-dip galvanized anti-corrosion treatment, adapted to semi-outdoor base station environments.

8.2.2 Core Room Switching Equipment Cabling

Operator core rooms have large switching capacity, extremely large quantities of optical and electrical cables, and intersecting routes in multiple directions, requiring large-scale layered cabling. Multi-layer arrangement of ladder-type cable trays achieves classified management of cables from different systems and directions, and the open structure facilitates laying and maintenance of massive cable quantities.

Selection Key Points: Medium to heavy load rating, multi-layer column or hanger support, full range of elbow and branch fittings, and a complete labeling system.

8.2.3 Access Network Room Integrated Cabling

Access network rooms have high equipment density and mixed cable types, with power supply, transmission, and data cables laid together. The ladder-type cable tray with separator solution achieves same-rack laying of multiple cable types within limited space, improving space utilization.

Selection Key Points: Medium load rating, with metal separators, layered and classified cabling.

8.3 Enterprise and Institution Computer Room Scenarios

Small and medium-sized computer rooms in enterprises, government agencies, campuses, and hospitals have moderate scale and comprehensive functions, balancing reliability and economy while having certain requirements for appearance and maintenance convenience.

8.3.1 Enterprise Information Technology Computer Rooms

Enterprise computer rooms carry comprehensive services including office networks, business systems, and security surveillance, with mixed strong and weak currents and moderate cable quantities. The ladder-type cable tray offers high cost-effectiveness and simple installation and maintenance, meeting the integrated cabling needs of enterprise computer rooms.

Selection Key Points: Medium load rating, electrostatic powder coating appearance, strong/weak current layered or separated laying.

8.3.2 Government Data Computer Rooms

Government computer rooms have high requirements for security and standardization, with cabling systems required to meet confidentiality and classified protection requirements. The ladder-type cable tray achieves physical isolation and reliable grounding, meeting security standards while facilitating auditing and maintenance management.

Selection Key Points: All-metal structure, reliable grounding, physical separation of classified and non-classified cables, and complete acceptance documentation.

8.3.3 Campus and Hospital Computer Rooms

Campus and hospital computer rooms have dispersed point locations, numerous branches, wide coverage, and complex cable tray routes. The ladder-type cable tray’s rich branching accessories flexibly achieve multi-route branching, and the open structure facilitates later point expansion and adjustment.

Selection Key Points: Primarily medium load rating, with main trunk and branch specifications progressively decreasing, arranged along corridors and cable shafts.

8.4 Industrial Control and Power Distribution Scenarios

Industrial scenarios have complex environments, heavy loads, and greatly varying environmental conditions, placing high demands on cable tray strength, corrosion resistance, and reliability. With its high strength and flexible corrosion protection options, the ladder-type cable tray is widely used in various industrial power distribution and control scenarios.

8.4.1 Factory Power Distribution Room Power Cable Laying

Power cables from factory power distribution rooms to each workshop have large cross-sections and high ampacity, with some environments containing dust and moisture. The ladder-type cable tray’s strong load-bearing capacity and excellent heat dissipation, combined with hot-dip galvanized anti-corrosion treatment, adapt to industrial environments and represent the standard selection for industrial power distribution main trunks.

Selection Key Points: Heavy load rating, hot-dip galvanized surface treatment, large-span design to reduce support points.

8.4.2 Industrial Automation Control Cable Laying

Control cables and instrument signal cables for automated production lines are numerous with long routes and require separation from power cables. Layered arrangement of ladder-type cable trays achieves isolation between power and control cables, and the open structure facilitates on-site wiring and fault troubleshooting.

Selection Key Points: Medium load rating, strong/weak current layering, stainless steel or FRP materials for corrosive environments.

8.4.3 Explosion-Proof and Corrosion-Resistant Scenarios in Mines and Petrochemical Plants

Mines and petrochemical scenarios contain explosive gases and strongly corrosive media, placing extremely high demands on cable tray corrosion resistance and explosion-proof performance. Ladder-type cable trays in stainless steel or FRP materials adapt to strongly corrosive environments, while the open structure does not readily accumulate combustible gases, adapting to explosion-proof requirements.

Selection Key Points: 316L stainless steel or FRP materials, explosion-proof grounding accessories, full-route reliable equipotential bonding.

8.5 Commercial Building and Public Facility Scenarios

In office buildings, shopping malls, hotels, rail transit systems, airports, and other commercial and public buildings, cable trays serve as infrastructure for building electrical systems, with large quantities and wide distribution, balancing functionality and aesthetics.

8.5.1 Office Building Integrated Cabling

Office buildings have numerous weak-current systems, including networks, telephones, security surveillance, and building automation, with large quantities of vertical main trunk and horizontal branch cabling. The ladder-type cable tray is used for vertical shafts and main trunk routes, offering strong load-bearing capacity and high cabling efficiency.

Selection Key Points: Medium load rating, electrostatic powder coating appearance, adapted to decoration style, vertical installation within shafts.

8.5.2 Shopping Mall and Hotel Weak-Current System Cabling

Shopping malls and hotels have numerous point locations and winding routes, requiring cable trays to flexibly turn and branch in coordination with architectural forms. The ladder-type cable tray’s complete range of elbow and branch fittings adapt to complex building layouts, and the open structure facilitates later cabling adjustments by tenants.

Selection Key Points: Light to medium load rating, concealed installation above suspended ceilings, hot-dip galvanized anti-corrosion and moisture protection.

8.5.3 Rail Transit and Airport Terminal Cabling

Rail transit and airports are large public buildings with long cable tray routes, multiple systems, and high reliability requirements. The large-span, high-load-bearing characteristics of the ladder-type cable tray adapt to large-space buildings, reducing support points and maintaining building aesthetics.

Selection Key Points: Heavy load rating, hot-dip galvanized anti-corrosion, seismic reinforcement, compliant with public building fire protection and safety standards.

8.6 Special Environment Application Scenarios

8.6.1 High Humidity and High Temperature Environments

Scenarios such as underground computer rooms, humid southern regions, and areas around boiler rooms feature high temperature and high humidity, with rapid corrosion rates and high corrosion protection requirements.

Selection Recommendations: Use hot-dip galvanized or stainless steel materials, increase coating thickness, avoid electro-galvanized and ordinary powder coating; enhance ventilation to reduce ambient humidity.

8.6.2 Coastal Salt Spray Environments

Coastal areas have high salt content in the air, and chloride ions accelerate metal corrosion, resulting in short service life for ordinary galvanized layers.

Selection Recommendations: Use thickened hot-dip galvanized treatment or 304/316L stainless steel materials; install rainproof covers for outdoor scenarios to reduce direct salt spray contact.

8.6.3 Chemical Corrosion Environments

Chemical plant areas contain corrosive gases and liquids such as acids and alkalis, with high corrosion intensity.

Selection Recommendations: Select FRP cable trays or 316L stainless steel cable trays based on the type of corrosive medium; use stainless steel materials for connection bolts to avoid galvanic corrosion between dissimilar metals.

8.6.4 Severe Cold and High Altitude Environments

In severely cold northern regions and high-altitude areas, low temperatures increase material brittleness while ultraviolet radiation is strong.

Selection Recommendations: Select steel with good low-temperature toughness; use hot-dip galvanizing with strong weather resistance for surface treatment; select low-temperature-resistant and weather-resistant materials for plastic accessories to avoid low-temperature brittle cracking.

Chapter 9 Product Installation

The installation quality of the ladder-type open cable tray directly determines the system’s structural safety, electrical performance, and service life. National specifications and product technical requirements must be strictly followed, and construction must proceed according to standardized processes. This chapter provides a full-process detailed explanation from construction preparation, general procedures, detailed rules for different installation methods, special node treatment, to quality control, providing construction units with implementable technical guidance.

9.1 Pre-Construction Preparation

Adequate advance preparation is the prerequisite for ensuring installation quality, construction progress, and construction safety. Preparations in five areas — technical, materials, tools, site, and personnel — must be completed before site entry.

9.1.1 Technical Preparation

Drawing Review and Detailed Design: Before commencement, organize technical personnel to familiarize themselves with construction drawings, verify cable tray routes, specifications, and elevations, perform clash detection with other professional pipelines (HVAC, water supply/drainage, fire protection), optimize route layouts to avoid cross conflicts. Perform detailed design for complex nodes and issue detailed installation large-scale drawings.

Construction Plan Preparation: Prepare a dedicated construction plan detailing installation process flow, quality standards, safety measures, schedule, personnel allocation, and tool plans; prepare dedicated operation instruction documents for special processes such as large spans, high-altitude work, and seismic installation.

Technical Disclosure: Before construction, conduct technical and safety disclosure for all construction personnel, clarifying quality requirements, operational specifications, and safety precautions. Disclosure requires signed confirmation and retained records.

Standard and Specification Study: Organize construction personnel to study relevant specifications including GB 50303, T/CECS 31, and this product’s technical requirements, and master acceptance standards.

9.1.2 Material Preparation

Incoming Inspection: Upon arrival of cable trays and accessories, verify quality documents including product certificates, factory inspection reports, and material certificates; inspect appearance quality, confirming no deformation, corrosion, coating detachment, weld cracks, or other defects; spot-check dimensional specifications, verifying consistency with drawing requirements. Non-conforming products are strictly prohibited from site use.

Quantity Verification: Count various components and accessories according to the material list, verify model and specification, ensuring sufficient quantity and complete accessories; conduct focused verification of direction and angle for special-shaped parts such as elbows and tees.

Storage and Preservation: Classify and store incoming materials with proper labeling; store in dry, ventilated locations to avoid rain exposure and moisture corrosion; maintain moderate stacking height to prevent compression damage; protect plastic accessories from direct sunlight to prevent aging.

9.1.3 Tool and Equipment Preparation

Configure corresponding construction tools and equipment according to the construction plan, and perform calibration and maintenance in advance to ensure proper performance. Main construction tools include:

Measuring Tools: Laser level, infrared line marker, steel tape measure, vernier caliper, torque wrench, ground resistance tester.

Drilling Tools: Rotary hammer drill, electric hammer, core drill, matching drill bits.

Cutting Tools: Profile cutting machine, angle grinder, hacksaw.

Fastening Tools: Wrenches, sockets, electric screwdrivers.

Auxiliary Tools: Scaffolding, lifting platforms, safety belts, safety helmets, gloves, and other protective equipment.

9.1.4 Site Preparation

Site Clearance: Clear debris and obstacles from the construction area, ensuring adequate working space; verify that the building structure at the work surface has reached the required installation strength — concrete strength must reach 75% of design strength before expansion bolt installation.

Positioning and Layout: According to construction drawings, use an infrared line marker to project the cable tray centerline, elevation line, and support hanger positioning lines onto the ceiling slab, wall, or floor, clearly marking support hanger points, turns, branches, and reducer positions. Layout error shall be controlled within ±5mm.

Condition Confirmation: Verify building structural dimensions and beam/column positions match drawings; confirm reserved openings are correctly positioned and sized; confirm the construction progress and positions of other professional pipelines to avoid cross-operation conflicts.

9.1.5 Personnel Preparation

Qualification Requirements: Construction personnel must possess corresponding electrician or electrical installation work qualifications; high-altitude workers must hold high-altitude operation certificates. Working without certification is strictly prohibited.

Safety Training: Conduct three-level safety education and special safety training before site entry; personnel may only commence work after passing assessment; conduct special training for high-altitude work, electrical safety, and hot work operations.

Personnel Allocation: Based on project volume and schedule requirements, reasonably allocate positions such as construction team leader, technical personnel, installation workers, and safety officer, with clearly defined division of responsibilities.

9.2 General Installation Process Flow

Ladder-type open cable tray installation follows the sequence of bottom-to-top and main trunk-to-branch. The general process flow is as follows:

Positioning and layout → Support hanger fabrication and installation → Cable tray body assembly and laying → Cable tray fixing and leveling/alignment → Grounding system installation → Functional accessory installation → Fire sealing work → Self-inspection and rectification → Inspection and acceptance

During construction, the principle of “main trunk before branch, large specification before small specification, fixing before adjustment” must be followed. Each process step may proceed to the next only after acceptance inspection.

9.3 Detailed Steps for Suspended Installation

Suspended installation is the most common installation method for overhead routing in computer rooms, including types such as full-thread rod suspension and channel steel suspension. The following details the installation steps using the most common full-thread rod suspension as an example.

9.3.1 Positioning and Drilling

  • According to the support hanger points marked during layout, mark drilling positions on the floor slab or beam bottom;
  • Select impact drill bits of corresponding specifications for drilling, with hole depth meeting expansion bolt installation requirements, typically anchor tube length + 10mm;
  • After drilling, clean dust from the holes and check hole diameter and depth. Non-conforming holes must be re-drilled and must not be filled with cement mortar.

9.3.2 Top Fixing Bracket and Hanger Rod Installation

  • Combine the expansion bolt with the rod top fixing seat, insert into the drilled hole, tighten the expansion nut to ensure secure anchoring;
  • Cut full-thread rods to corresponding lengths, screw into the top fixing seats, and initially tighten;
  • Keep the two hanger rods of the same support vertical, initially adjust height so that the lower ends of the rods are approximately at the same elevation.

9.3.3 Crossarm Installation and Elevation Calibration

  • Fix the crossarm to the lower ends of the two hanger rods through connecting components, initially tightening the adjustment nuts;
  • Use a laser level to calibrate crossarm levelness, precisely adjusting elevation through the upper and lower adjustment nuts to ensure the crossarm is level, with elevation deviation ≤ ±2mm;
  • Adjust all crossarms on the same route to the same elevation, with overall straightness deviation ≤ 5mm/10m;
  • After confirming elevation is correct, tighten the upper and lower locking nuts to fix the crossarm position.

9.3.4 Cable Tray Assembly and Lifting into Position

Ground Pre-Assembly: Connect two cable tray straight sections using connecting plates and bolts, initially tightening bolts. During assembly, ensure the two tray sections are flush, with misalignment ≤ 0.5mm and gap ≤ 1mm;

  • Lift the pre-assembled tray sections onto the crossarms, extending forward section by section;
  • During section-to-section connection, align connection holes, insert connecting bolts from the inner side of the tray toward the outer side, and initially tighten nuts;
  • Connect special-shaped parts such as elbows, tees, and reducers according to drawing positions, ensuring smooth and straight routes.

9.3.5 Cable Tray Fixing and Overall Adjustment

  • After the cable tray is laid in position, secure the tray to the crossarms using pressure plates, with at least 2 sets of pressure plates per crossarm, pressing the side rails on both sides respectively;
  • Adjust tray levelness and straightness section by section to ensure the overall tray is straight, without twisting or tilting;
  • Thoroughly tighten all connection bolts to the required torque: M8 bolts 8-10N·m, M10 bolts 12-15N·m;
  • Check all joint gaps and misalignment amounts; rectify positions exceeding tolerances.

9.3.6 Hanger Rod Reinforcement

  • When hanger rod length exceeds 1500mm, add lateral diagonal braces or lateral connecting rods to connect adjacent hanger rods into an integrated unit, preventing sway;
  • At positions with complex force conditions such as turns and branches, add reinforcing hanger rods to avoid excessive single-point loading.

9.4 Detailed Steps for Wall-Mounted Bracket Arm Installation

Wall-mounted installation is suitable for cable trays laid along walls and columns. The installation steps are as follows:

9.4.1 Wall Positioning and Marking

  • According to drawing elevations, project the cable tray bottom horizontal line and bracket arm installation position lines on the wall, marking the fixing holes of each bracket arm; bracket arm heights on the same route shall remain consistent, with uniform spacing.

9.4.2 Bracket Arm Drilling and Fixing

  • Drill holes according to the marked positions and clean dust from the holes;
  • Position the bracket arm, insert expansion bolts, and initially tighten;
  • Use a level to calibrate bracket arm levelness, ensuring the outer end does not tilt downward, with levelness deviation ≤ 2mm;
  • Tighten bracket arm fixing bolts one by one to ensure secure installation.

9.4.3 Cable Tray Laying and Fixing

  • Place cable tray sections onto bracket arms section by section, connecting section interfaces;
  • Secure the tray to bracket arms using pressure plates, with at least 2 sets of pressure plates per bracket arm;
  • Adjust tray straightness and wall clearance, achieving overall straightness and attractive appearance;
  • Densely arrange bracket arms at vertical riser sections, with spacing not exceeding 1.5m, ensuring secure tray fixing.

9.5 Detailed Steps for Floor-Standing Column Installation

Floor-standing column installation is suitable for under-floor routing and raised floor laying scenarios. The installation steps are as follows:

9.5.1 Floor Positioning and Foundation Treatment

  • Mark column centerlines and installation points on the floor, verifying floor levelness;
  • When the floor is a raised access floor, lift the floor panels and fix columns to the original concrete floor — fixing directly to movable floor panels is prohibited;
  • When the floor is uneven, use shims for leveling to ensure the column base plate is stable.

9.5.2 Column Base Plate Fixing

  • Position the column base plate on the marked points and mark drilling positions;
  • After drilling, fix the base plate to the floor using expansion bolts and tighten the bolts;
  • Check column base plate levelness to ensure verticality after column installation.

9.5.3 Column Installation and Verticality Calibration

  • Connect and fix the column to the base plate;
  • Use a plumb bob or theodolite to calibrate column verticality, with verticality deviation ≤ 1‰;
  • After verticality adjustment passes, tighten all connection bolts.

9.5.4 Bracket Arm and Crossarm Installation

  • According to design elevations, mark bracket arm installation positions on the columns;
  • Install bracket arms, calibrate levelness, keeping bracket arms on the same layer at the same elevation;
  • Install multi-layer bracket arms from bottom to top in sequence, with uniform layer spacing.

9.5.5 Cable Tray Laying and Overall Reinforcement

  • Lay cable trays layer by layer from bottom to top, connecting and fixing;
  • When column spacing exceeds 3m or column height exceeds 3m, add horizontal connecting beams to connect adjacent columns into an integrated unit, improving stability;
  • For long-distance column-mounted cable trays, install diagonal bracing at intervals of 10-15m to prevent lateral tilting.

9.6 Special Node Installation Techniques

9.6.1 Elbow, Tee, and Reducer Section Installation

  • During elbow installation, ensure the bending direction matches the route direction, with the inner bending radius meeting the minimum cable bending radius requirement;
  • Support hangers must be installed at both ends of the elbow, within no more than 500mm from the elbow end face; large-specification elbows require additional support at the turning midpoint;
  • During tee and cross installation, ensure accurate branch directions, flush interfaces, and tight joints;
  • Reducer section installation must ensure smooth transition without steps or protrusions to avoid scratching cables; for eccentric reducers, pay attention to the flush side direction per design requirements.

9.6.2 Installation at Wall and Floor Slab Penetration Nodes

  • When the cable tray passes through walls or floor slabs, the penetration opening shall be 50-100mm larger than the tray’s outer edge; the tray must not directly contact the wall or floor slab;
  • No joints are permitted at penetration points; joints shall be located ≥ 500mm from the opening edge;
  • After installation, perform fire sealing per specification requirements, with dense and flat sealing.

9.6.3 Installation at Settlement Joints and Expansion Joints

  • When the cable tray passes through building settlement joints or expansion joints, expansion compensation devices must be installed, disconnecting the tray and reserving 10-20mm of expansion gap;
  • Cable trays on both sides shall be independently supported and must not share support hangers;
  • Use flexible jumper cables for grounding connections, reserving sufficient length to accommodate structural displacement;
  • Install labels documenting the expansion joint position and compensation amount.

9.6.4 Crossing Treatment with Other Pipelines

  • When crossing other pipelines, follow the principle of “weak current yields to strong current, small pipe yields to large pipe, pressurized yields to non-pressurized,” adjusting cable tray elevation or position to avoid conflicts;
  • When running parallel to heating pipes, maintain spacing ≥ 1m; when crossing, ≥ 0.5m; heating pipes with higher temperatures require thermal insulation measures;
  • When running parallel to water pipes, maintain spacing ≥ 0.5m; the cable tray should preferably be positioned above the water pipes to prevent water leakage from dripping onto the tray and cables.

9.6.5 Installation at Cabinet and Distribution Box Entry Nodes

  • Align the cable tray end with cabinet and distribution box cable entry openings, with deviation not exceeding 10mm;
  • Maintain 50-100mm distance from the tray end to the cabinet panel to facilitate cable entry;
  • For vertical entry, ensure proper transition between tray bottom and cabinet top, with cable bending radius meeting requirements;
  • Make equipotential connections between the tray and cabinet metal enclosure to ensure grounding continuity.

9.6.6 Vertical Riser Section Installation

  • Support bracket spacing for vertical tray sections shall not exceed 1.5m, with at least 2 support points per tray section;
  • Fixed supports must be installed at both the upper and lower ends of vertical sections, with an additional anti-sway support every 3m in between;
  • After cable laying, install fixing clamps every 2m on vertical sections to prevent cables from sliding down under their own weight.

9.7 Seismic Support Installation Techniques

9.7.1 Seismic Support Positioning Principles

  • Lateral support spacing on straight sections ≤ 12m, longitudinal support spacing ≤ 24m;
  • Seismic supports must be added at tray start points, end points, turns, reducers, and fire compartment penetrations;
  • Seismic supports at turns shall be no more than 1m from the turning end face;
  • Seismic supports must not be installed at joint nodes, with distance from joints ≥ 500mm.

9.7.2 Lateral Support Installation Steps

  • Install top fixing seats and vertical hanger rods according to positioning points;
  • Install lateral diagonal brace rods, connecting one end to the crossarm and the other end to the building structure above, with diagonal brace angles of 30°-60°;
  • Adjust diagonal brace angle and tension to ensure uniform force distribution;
  • Install seismic clamping blocks to securely lock the cable tray to the crossarm, preventing sliding;
  • Tighten all bolts to specification; hinged nodes shall rotate freely without binding.

9.7.3 Longitudinal Support Installation Key Points

  • Longitudinal diagonal braces are arranged along the cable tray length direction, with both ends connecting to crossarms and structure respectively;
  • They may share vertical hanger rods with lateral supports to form combined bidirectional supports;
  • Install one set every 24m on long-distance cable trays to ensure overall longitudinal stability.

9.7.4 Installation Quality Requirements

  • All components of seismic supports must be factory-made finished products; on-site welding modification is strictly prohibited;
  • Diagonal brace connections to structure must be anchored to the main structure; fixing to non-load-bearing structures such as suspended ceiling framing is strictly prohibited;
  • After installation, supports shall be firm, without looseness, and diagonal braces without bending deformation;
  • Maintain installation records, documenting the position, specification, and installer of each seismic support.

9.8 Installation Quality Control Standards

9.8.1 Support Hanger Installation Quality Standards

  • Support hanger spacing meets design and load requirements, with deviation ≤ 100mm;
  • Hanger rod verticality deviation ≤ 1‰, column verticality deviation ≤ 1‰;
  • Crossarm and bracket arm levelness deviation ≤ 2mm;
  • Expansion bolts are securely anchored, without looseness or tilting, with 2-3 threads of the nut exposed;
  • Support hangers are neatly arranged with uniform spacing and intact anti-corrosion coating.

9.8.2 Cable Tray Body Installation Quality Standards

  • Straight section straightness deviation ≤ 5mm/10m, full-length deviation ≤ 20mm;
  • Horizontal tray levelness deviation ≤ 2‰;
  • Vertical tray verticality deviation ≤ 2‰;
  • Joint gap ≤ 1mm, vertical and horizontal misalignment ≤ 0.5mm;
  • No twisting, deformation, burrs, or sharp edges on the tray; anti-corrosion coating intact without damage;
  • Elbows and tees transition smoothly without sharp angles.

9.8.3 Safety Clearance Standards

  • Distance from tray top to floor slab or beam bottom ≥ 150mm, facilitating inspection and maintenance;
  • Distance from tray side to wall ≥ 50mm;
  • When strong-current and weak-current cable trays are laid in parallel, spacing ≥ 300mm;
  • Minimum clearances between the cable tray and various pipelines comply with specification requirements.

Chapter 10 Product Wiring (Cable Laying)

The “wiring” of the ladder-type open cable tray refers to operations related to cable laying, bundling, fixing, and termination within the cable tray system — the core stage where the cable tray system’s functions are realized. Cable laying quality directly affects electrical performance, transmission quality, and system safety, and must strictly comply with corresponding construction specifications and process requirements. This chapter details the laying techniques and quality standards for common power cables, optical cables, and weak-current cables in computer rooms.

10.1 Pre-Laying Preparation

10.1.1 Cable Incoming Inspection

  • Upon cable arrival, verify that model, specification, and quantity match design drawings; inspect quality documents including product certificates, test reports, and 3C certification;
  • Appearance inspection: cable jackets are complete, without damage, crushing, cracking, oil contamination, or other defects; ends are properly sealed;
  • Electrical performance testing: power cables — insulation resistance test; optical cables — attenuation and length test; weak-current cables — continuity and impedance test; non-conforming cables are strictly prohibited from use;
  • Cable storage: drummed cables shall be placed in dry, ventilated areas, protected from sun and rain exposure, with moderate stacking height to prevent drum deformation.

10.1.2 Laying Plan Development

  • Based on cable tray routes and cable lists, prepare a laying schedule table specifying the start/end points, numbers, specifications, and laying sequence of each cable;
  • Determine the laying method: manual laying for short-distance, small-cross-section cables; mechanical pulling for long-distance, large-cross-section cables;
  • Plan personnel allocation and command/communication methods, with dedicated personnel stationed at key positions;
  • Calculate pulling tension and side pressure in advance to ensure they do not exceed cable allowable values.

10.1.3 Cable Tray Interior Inspection and Cleaning

  • Before laying cables, comprehensively inspect cable tray installation quality, confirming secure supports, level joints, and absence of burrs and sharp edges;
  • Clean debris, dust, and metal shavings from the tray interior to avoid scratching cables;
  • For trays with protective rubber strips installed on edges and rungs, check that strips are firmly adhered and not detached;
  • Verify that tray separators and layering configurations comply with strong/weak current separation requirements.

10.2 General Cable Laying Principles

Strong/Weak Current Separation Principle: Strong-current power cables and weak-current signal cables shall be laid in separate compartments or layers; mixed placement is strictly prohibited, with spacing meeting electromagnetic compatibility requirements; cables of different voltage levels and different circuits shall be separated per specification.

Neat Arrangement Principle: Cables shall be arranged in parallel in sequence, minimizing crossings, with smooth bends at turns, without compression or twisting.

Bending Radius Control Principle: Cable bending radius shall not be less than the specification minimum: power cable bending radius ≥ 10-15 times cable outer diameter; optical cable bending radius ≥ 15-20 times optical cable outer diameter.

Tension Control Principle: During laying, pulling tension shall not exceed the cable’s maximum allowable tension, pulling at uniform speed, avoiding sudden jerks and hard pulling to prevent cable tensile deformation and internal damage.

Labeling Clarity Principle: Labels shall be affixed at both cable ends and key nodes, with clear and accurate numbers consistent with drawings.

10.3 Power Cable Laying Techniques

10.3.1 Large-Cross-Section Power Cable Laying Methods

Manual Laying: Suitable for short-distance, small-to-medium cross-section cables. Multiple workers cooperatively carry and lay cables section by section along the tray, with unified command and synchronized pace to avoid cable dragging and friction on the ground.

Mechanical Pulling: Suitable for long-distance, large-cross-section cables. Use electric winches for pulling, with a steel mesh pulling head installed at the leading end; pulling speed controlled at 6-10m/min; pulling tension monitored via a dynamometer, not exceeding cable allowable values.

During laying, assign dedicated personnel to monitor turns, ensuring cables hug the inner side of elbows, bending radius meets requirements, and preventing cables from springing out and causing injury; install anti-slip clamps at vertical sections to prevent cable slippage.

10.3.2 Cable Arrangement and Bundling Requirements

  • Cables shall be arranged in single layer in circuit sequence, neat and flat, minimizing crossings; when quantities are large, layered arrangement is permissible with large-cross-section cables at the bottom layer and small-cross-section cables above.
  • For horizontal laying, set fixing points at both cable ends, both sides of turns, and both sides of joints, with bundling/tying every 2-3 rungs in between.
  • For vertical laying, fix every 1.5m, with both upper and lower ends securely fixed using dedicated cable clamps, avoiding long-term tension on cable ties that could cause fracture.

10.3.3 Force Control at Turns and Vertical Sections

  • Cable bending radius at turns meets requirements; when multiple cables turn simultaneously, maintain consistent curvature, neat arrangement, without compressing inner cables;
  • The self-weight tension of cables at vertical sections shall be borne by fixing clamps; tension must not be applied to end terminal blocks;
  • For large-cross-section vertical cables, add a load-bearing fixing point every 5m to distribute tension.

10.4 Communication Optical Cable and Weak Current Cable Laying Techniques

10.4.1 Optical Cable Laying Tension Control

  • Optical cables have low allowable pulling force. During laying, tension shall be controlled throughout the entire process. The maximum pulling force shall not exceed 80% of the allowable cable tension, and the instantaneous maximum pulling force shall not exceed 100%.
  • The pulling speed shall be slow and uniform, preferably controlled at 5-10 m/min. Sudden acceleration is prohibited.
  • Personnel shall be assigned to provide guidance at turns, entry and exit points to avoid bending or compression of the optical cable.

10.4.2 Optical Cable Protection Requirements

  • Optical cables shall not come into direct contact with sharp objects. Protective rubber strips or soft pads are recommended at ladder rung locations.
  • Sharp bends in optical cables are strictly prohibited. The bending radius shall not be less than the specified value: dynamic bending radius ≥ 20 times the outer diameter, static bending radius ≥ 15 times.
  • Sufficient separation shall be maintained between optical cables and power cables to avoid electromagnetic interference. When installed on the same support, optical cables shall be placed in independent compartments.

10.4.3 Large-Pair Cable and Network Cable Laying

  • When laying large-pair copper cables and Cat-6/Cat-7 network cables, excessive stretching shall be avoided. The stretching rate shall not exceed 1%.
  • Cables shall be arranged in parallel. Bundling shall be of appropriate tightness to avoid compression deformation affecting transmission performance.
  • Network cables shall avoid long-distance parallel runs in close proximity to power cables. When crossing is necessary, perpendicular crossing is preferred.

10.5 Cable Bundling and Fixing

10.5.1 Bundling Spacing Requirements

Cable Type Installation Orientation Bundling Spacing
Power cables Horizontal 1.0-1.5 m
Power cables Vertical 1.0-1.5 m, both top and bottom ends must be secured
Control cables and weak current cables Horizontal 0.8-1.0 m
Optical cables Horizontal 0.5-0.8 m, avoid excessive force
  • Bundling shall be densified at turns, entry and exit points.

10.5.2 Bundling Process Standards

  • Bundling shall use flame-retardant nylon cable ties or stainless steel cable ties. Flame-retardant ties are preferred inside equipment rooms; stainless steel ties shall be used outdoors and in high-temperature environments.
  • Bundling force shall be moderate. Cables shall not be deformed or loose. The tie buckle shall face outward, with excess tail trimmed. The cut shall be smooth and free of burrs.
  • Tie direction shall be consistent within the same area for a neat and tidy appearance.
  • Large cross-section cables shall use dedicated fixing clamps. Single cable ties shall not be used to bundle heavy cables.

10.6 Cable Labeling and Records

  • Label positions: Identification tags shall be installed at both ends of cables, at turns, branch points, through-wall/floor penetration points, and at both ends of cable trays.
  • Label content: Shall include cable number, model and specification, starting point, end point, length and other information. Text shall be legible and resistant to fading.
  • Label fixing: Tags shall be securely tied, uniformly positioned, and easy to view.
  • Laying records: Cable laying records shall be maintained, documenting the actual length, laying date, and construction personnel for each cable. As-built routing diagrams shall be drawn and filed for retention.

10.7 Cable Laying Quality Acceptance Requirements

  • Cables shall be neatly arranged, free of crossing, twisting, and compression, with secure and tidy bundling.
  • Cable jackets shall be intact and undamaged, free of scratches, cracks, and flattening.
  • Bending radii shall comply with specification requirements, with no kinks or reverse bends.
  • Labels shall be complete and legible, with accurate numbering consistent with drawings.
  • Separation of power and weak current cables shall comply with design requirements, with spacing meeting standards.
  • Electrical performance tests shall pass, with insulation resistance, continuity, and transmission performance meeting standards.

Commissioning of the ladder-type open cable tray system is a critical step to verify installation quality, validate system performance, and eliminate potential safety hazards. It mainly includes four parts: structural stability commissioning, electrical grounding system commissioning, functional accessory commissioning, and comprehensive operational verification. Commissioning shall be performed after installation is complete and cables are laid. The system may only be put into formal operation after passing commissioning.

11.1 Commissioning Overview

11.1.1 Commissioning Objectives

  • Verify the structural strength and stability of the cable tray system, confirming compliance with design load requirements.
  • Verify the continuity of the grounding system and grounding resistance to ensure electrical safety.
  • Inspect the installation quality and working condition of various functional accessories to ensure proper operation.
  • Identify installation and material defects for timely rectification, avoiding failures after commissioning.

11.1.2 Commissioning Basis

  • JB/T 10216-2013 “Cable Tray for Electric Control and Distribution”
  • GB 50303-2015 “Acceptance Standard for Construction Quality of Building Electrical Engineering”
  • GB 50981-2014 “Code for Seismic Design of Mechanical and Electrical Equipments in Buildings”
  • Design drawings and technical requirements
  • Product technical parameter standards of this manual

11.1.3 Commissioning Preparation

  • Prepare a commissioning plan, specifying the commissioning items, methods, standards, personnel, and instruments.
  • Prepare commissioning instruments: torque wrench, ground resistance tester, continuity resistance tester, steel ruler, feeler gauge, deflection measuring instrument, tension gauge, etc.
  • Confirm before commissioning that all installation work is complete, self-inspection has passed, and the site has been cleaned up.
  • Organize training for commissioning personnel to familiarize them with the commissioning process and safety precautions.

11.2 Structural Stability Commissioning

11.2.1 Load Test Commissioning

Load testing is the core commissioning item to verify the load-bearing capacity of the cable tray. It is performed in three steps: no-load inspection, load application test, and unloading rebound check.

No-load inspection: Under no-load conditions, measure the initial mid-span deflection of the cable tray and record baseline data; check support hangers and connection nodes for deformation or loosening.

Uniformly distributed load test: Apply the rated uniformly distributed load evenly within the tray. Loads may use sandbags, standard weights, etc., evenly distributed to avoid concentrated stacking. Loading shall be performed in three stages. After each stage, allow the system to rest for 10 minutes, observe deformation, and record mid-span deflection.

Deflection measurement: After loading to the rated load, allow the system to rest for 30 minutes, measure the maximum mid-span deflection, calculate the relative deflection, and verify compliance with the standard requirement of ≤ 1/200 of the span.

Unloading rebound check: Unload in stages. After complete unloading, allow the system to rest for 1 hour and measure residual deflection. Residual deflection not exceeding 20% of total deflection with no permanent plastic deformation is considered acceptable.

Critical node inspection: Throughout the loading process, continuously observe side rails, ladder rungs, welds, connecting bolts, and support hangers for deformation, cracking, or slipping. Stop the test immediately if any abnormality occurs.

Sampling principle: For main routes, test 1 span per 50 m. All critical nodes such as bends and branches shall be inspected. Large-span and heavy-load sections shall be prioritized for sampling.

11.2.2 Connection Node Fastening Commissioning

  • Use a calibrated torque wrench to sample-check the fastening torque of connecting bolts at a rate of 5%, with no fewer than 2 groups per section.
  • Check bolts for missing installation or loosening. Spring washers and flat washers shall be properly configured.
  • Check the pressing condition of cable tray hold-down plates. Plates shall fit tightly against side rails without looseness or tilting.
  • Support hanger connecting bolts shall be sample-checked simultaneously to ensure secure anchoring and connection.

11.2.3 Support Hanger Stability Commissioning

  • Verticality check of hanger rods: Measure with a plumb bob or theodolite. Adjust promptly if deviation exceeds limits.
  • Lateral sway test: Apply a slight horizontal push to the cable tray and observe the sway of support hangers. No obvious sway is considered acceptable. Add diagonal bracing to reinforce sections with obvious sway.
  • Column stability check: Check columns for tilting and base plates for loosening. Perform lateral thrust tests on tall columns to ensure overall stability.

11.3 Electrical Grounding System Commissioning

11.3.1 Continuity Test

  • Segmented continuity test: Use a milliohm meter to measure the contact resistance between two adjacent cable tray sections. Contact resistance ≤ 0.001 Ω is considered acceptable.
  • Full-length continuity test: Measure the total continuity resistance from the head end to the tail end of the cable tray system. Continuity resistance ≤ 0.1 Ω per 100 m is considered acceptable.
  • Cross-bonding wire inspection: Check that each cross-bonding wire is securely installed, with terminals firmly crimped, free of loosening and corrosion.
  • For nodes failing the continuity test, grind the contact surfaces, tighten bolts, or replace cross-bonding wires until compliance is achieved.

11.3.2 Ground Resistance Test

  • Use a ground resistance tester, tested by the three-probe or four-probe method.
  • Test point selection: Test at the head end, tail end, and at every 30 m interval in the middle of the cable tray. Additional test points shall be added where passing through fire compartments.
  • Acceptance criteria: For combined grounding systems, ground resistance ≤ 1 Ω; for independent grounding systems, ≤ 4 Ω.
  • When ground resistance exceeds limits, inspect the ground main conductor connections, add grounding points, or investigate grounding grid issues until compliance is achieved.

11.3.3 Equipotential Bonding Test

  • Measure the continuity resistance between the cable tray and the equipment room equipotential copper bar. ≤ 0.1 Ω is considered acceptable.
  • Measure the potential difference between cable trays at different locations. Under normal operating conditions, the potential difference shall be ≤ 0.5 V.
  • Check equipotential bonding between the cable tray and other metal components such as cabinets and metal piping to ensure reliable connections.

11.4 Functional Expansion Component Commissioning

11.4.1 Intelligent Monitoring System Commissioning

  • Temperature sensor calibration: Perform zero-point calibration and accuracy verification for each temperature sensor. Compare with a standard thermometer; error shall be within ±0.5°C.
  • Load sensor zeroing: Zero the load sensors under no-load conditions and set the range and alarm thresholds.
  • Data transmission test: Commission the communication network to ensure monitoring data can be stably uploaded to the environmental monitoring system (DCIM) with normal data refresh.
  • Alarm linkage test: Simulate over-temperature and overload conditions to verify normal alarm functionality and accurate alarm informationpush notification (push notification).

11.4.2 Fire Stopping System Inspection

  • Check that all fire stopping through wall and floor openings is dense and free of gaps and holes.
  • Check that fire barrier bags and fire-stop putty are fully filled, with no cracking in inorganic putty and no shedding in organic putty.
  • Stopping surfaces shall be smooth and compliant with fire protection acceptance requirements.

11.4.3 Seismic System Commissioning

  • Check that seismic supports are securely installed, diagonal brace angles meet requirements, and hinged nodes are flexible.
  • Check that seismic hold-down blocks are pressed firmly in place with no slip gaps.
  • Check that seismic supports are reliably connected to the structure with anchor bolts tightened.

11.5 System Joint Commissioning and Trial Operation

  • Full-load simulated operation: After all cables are connected, operate with load and observe the cable tray system for abnormal deformation or noise. The grounding system shall show no abnormal heating.
  • Temperature rise test: After 4 hours of full-load operation, test the cable surface temperature and cable tray temperature. Temperature rise shall be within normal range with no localized overheating.
  • 72-hour trial operation: Energize the system for continuous 72-hour trial operation. Conduct regular inspections of cable trays, grounding, and accessory status throughout the period. No abnormalities are considered acceptable.
  • Commissioning report: After commissioning is complete, compile all test data and issue a formal commissioning report recording commissioning items, test data, rectification status, and final conclusions. Relevant personnel shall sign and file the report.

12.1 Installation and Construction Precautions

  • Safety belts must be worn forhigh-altitude (high-altitude) operations. Qualified scaffolding or working platforms shall be erected. Climbing on cable trays is strictly prohibited. Warning zones shall be set up below construction areas, and personnel passage is prohibited.
  • Power tools shall be connected in compliance with temporary power usage regulations. Insulated gloves shall be worn. In humid environments, insulation protection shall be enhanced. Hot work operations require a hot work permit, fire extinguishing equipment, and dedicated supervision.
  • Cutting or welding load-bearing side rails and support hangers of cable trays without authorization is strictly prohibited. Where on-site cutting is necessary, anti-corrosion treatment shall be applied promptly after cutting, and reinforcement measures shall be taken where necessary.
  • Use tools of the corresponding specification for bolt tightening. Using extension bars to forcibly over-torque bolts is prohibited to prevent thread stripping and component deformation. Connecting bolts must be equipped with flat washers and spring washers for reliable loosening prevention.
  • Expansion bolts must be installed in solid concrete structures. Installation into plaster layers, lightweight partition walls, or ceiling suspension systems is strictly prohibited. Drilling depth shall meet requirements to avoid anchoring failure due to insufficient hole depth.
  • Compensation and fire stopping must be provided in accordance with specifications when crossing fire compartments and settlement joints. Relevant processes shall not be omitted. After installation, debris around openings shall be cleaned promptly to ensure stopping quality.
  • Protect the anti-corrosion coating during installation. Scratches or damage shall be promptly repaired with matching anti-corrosion paint to prevent corrosion from spreading from damaged areas.
  • Finished product protection: Avoid stacking heavy objects on or stepping on installed cable trays. Protective measures shall be taken when other trades are working nearby to prevent impact deformation.

12.2 Cable Laying Precautions

  • Laying cables exceeding the rated load of the cable tray is strictly prohibited. Concentrated stacking of cables causing localized overload is prohibited. Calculate the total load before laying to ensure it is within the rated range.
  • Cable laying shall proceed at a uniform speed. Forceful pulling is prohibited to prevent damage to internal conductors and insulation. For large cross-section cables, take protective measures during pulling to avoid abrasion of the outer jacket.
  • Strictly implement the separation of power and weak current cables. Mixing cables of different voltage levels and types in disorganized piles is strictly prohibited. When installed on the same support, a continuous metal separator must be installed and reliably grounded.
  • Manual guidance shall be provided at cable turns to ensure the bending radius meets requirements. Sharp-angle bends are strictly prohibited. Optical cables and network cables must never be kinked to prevent transmission performance degradation.
  • Vertically laid cables must be secured at specified intervals to prevent self-weight from pulling down and damaging terminal connections. Fixing clamps shall be of appropriate tightness to avoid pinching cables.
  • Avoid cables dragging on the ground during laying. Cables contaminated with mud or oil shall be wiped clean before placement on the tray to maintain internal cleanliness.

12.3 Operation and Usage Precautions

  • Stepping on or walking on cable trays is strictly prohibited. Cable trays are cable support components, not walkways, and shall not be used as maintenance platforms.
  • Hanging heavy objects on cable trays or installing other equipment or piping is strictly prohibited. Adding loads to cable trays at will is prohibited. When new cables are truly necessary, implement after load verification.
  • Regularly inspect load changes on cable trays. Beforeequipment room (equipment room) expansion with new cables, verify the load-bearing capacity of the cable tray. When overloaded, reinforce support hangers or replace with higher-capacity trays.
  • Maintain a dry and ventilated equipment room environment to avoid accelerated corrosion from long-term humidity. Address air conditioning or fire sprinkler leaks promptly to prevent prolonged water immersion of cable trays.
  • Cover plates are non-load-bearing structures. Stacking objects on cover plates is strictly prohibited. Tools, parts, and debris are prohibited on open cable trays to prevent falling and injury.

12.4 Special Environment Precautions

  • Corrosive environments: Increase inspection frequency to quarterly checks of anti-corrosion status, promptly treating rust spots. In coastal salt-spray environments, perform anti-corrosion maintenance semi-annually.
  • Vibration environments: Regularly check bolt loosening prevention. Re-tighten connecting bolts every six months, replacing with self-locking nuts where necessary. Focus on complex stress points such as bends and branches.
  • Outdoor cable trays: Regularly clear snow and standing water to avoid overload and prolonged immersion. Check end closures are intact to prevent rainwater and small animals from entering.
  • Low-temperature environments: Avoid impacting cable trays. Steel brittleness increases at low temperatures, and impact can cause cracking. Plastic accessories shall be protected from external impact.

12.5 Fire Safety Precautions

  • Flammable and explosive materials are strictly prohibited in the vicinity of cable trays. Fire access routes around cable trays shall be kept clear.
  • Regularly inspect the integrity of fire stopping. Repair cracks and detachment promptly. After O&M expansion, re-seal fire stopping. Destroying original fire stopping is strictly prohibited.
  • Monitor cable operating temperatures to avoid fires from long-term overload operation. Increase inspection frequency during high-temperature seasons, focusing on cable-dense sections.
  • Heat pipelines and flammable/explosive media pipelines are strictly prohibited inside cable trays. Safe spacing from other pipelines shall be maintained.

Establishing a standardized maintenance and repair system is a necessary measure to ensure the long-term safe and reliable operation of ladder-type open cable trays and to extend service life. This chapter defines the maintenance grading system, maintenance contents at each level, common damage repair methods, and maintenance record management requirements.

13.1 Full Lifecycle Maintenance System

13.1.1 Maintenance Grading System

A four-level maintenance system of “daily inspection, quarterly maintenance, annual overhaul, and five-year major repair” shall be implemented. Different levels correspond to different maintenance contents and depths, balancing reliability and economy.

Maintenance Level Executed By Frequency Main Content
Daily inspection Equipment room O&M personnel No less than once per month Visual and macroscopic inspection
Quarterly maintenance Dedicated maintenance personnel Once per quarter Fastening, cleaning, minor repairs
Annual overhaul Professional technical personnel Once per year Comprehensive structural and electrical performance testing, safety assessment
Five-year major repair Professional team Every 5 years Systematic overhaul, comprehensive anti-corrosion, reinforcement, replacement of aged components, system performance restoration

13.1.2 Maintenance Responsibility and Process

  • Designate maintenance responsible persons, establish maintenance management systems, and develop maintenance plans.
  • Record each maintenance activity. Address problems promptly when found. Report major issues and develop rectification plans.
  • After maintenance completion, acceptance and signature shall be performed, records filed, forming a closed-loop management system.

13.2 Daily Inspection Contents and Requirements

  • Overall visual inspection: Patrol along the cable tray route to check for obvious deformation, tilting, or displacement. Check for large-area corrosion or peeling of the anti-corrosion coating.
  • Connection node inspection: Sample-check bolts for looseness or loss, welds for cracking, and joints for obvious misalignment or gaps.
  • Support hanger inspection: Check hanger rods and columns for bending deformation, expansion bolts for looseness or loss, and support arms for downward bending.
  • Grounding system inspection: Check cross-bonding wires for detachment or breakage, grounding terminals for corrosion, and labels for integrity.
  • Accessory completeness inspection: Check cover plates, end caps, identification tags, fire stopping, and other accessories for missing or damaged items.
  • Load and cable inspection: Check for new cables added, overload conditions, neat cable arrangement, and signs of abnormal heating.
  • Minor problems found during inspection shall be handled on-site. Major problems shall be documented and reported for dedicated repair arrangements.

13.3 Quarterly Maintenance Contents

  • Full bolt re-tightening: Tighten all connecting bolts and support hanger bolts. Replace stripped or damaged bolts.
  • Anti-corrosion coating repair: Remove rust and repaint/re-zinc coat damaged areas of the anti-corrosion coating caused by impacts and abrasion to prevent corrosion expansion.
  • Grounding system maintenance: Grind the oxide layer on grounding terminal contact surfaces, tighten grounding bolts, measure continuity resistance, and ensure proper grounding.
  • Cleaning and dust removal: Clean surface dust and debris from cable trays to maintain cleanliness. Clean drainage holes to prevent water accumulation.
  • Label completion: Replace detached or illegible identification tags and warning signs to ensure clear and complete labeling.
  • Accessory inspection: Inspect cover plates, separators, and protective rubber strips. Replace damaged or aged plastic accessories.

13.4 Annual Overhaul Contents

  • Comprehensive structural safety inspection: Inspect the structural condition of the cable tray body, support hangers, and connection nodes section by section. Assess corrosion depth and residual strength.
  • Load and deflection re-measurement: Perform deflection measurements on critical sections to assess deformation under actual loads and verify load-bearing safety margins.
  • Comprehensive ground resistance testing: Test ground resistance at all grounding points. Issue test reports. Rectify non-compliant points promptly.
  • Seismic system special inspection: Inspect the firmness and integrity of all seismic supports. Re-tighten bolts. Replace damaged components.
  • Fire stopping special inspection: Comprehensively inspect all fire stopping points. Repair damaged stopping to ensure fire resistance performance meets standards.
  • Safety assessment and recommendations: Based on inspection results, issue an annual safety assessment report with recommendations for the next year’s maintenance and renovation.

13.5 Common Damage Repair Methods

13.5.1 Anti-Corrosion Coating Damage Repair

  • Small-area damage: Use sandpaper to grind the damaged area and surroundings, removing rust and loose coating. Clean thoroughly, then apply matching anti-corrosion paint/zinc-rich primer, followed by topcoat. Apply in 2-3 coats to ensure coating thickness.
  • For damaged galvanized layers, cold galvanizing spray may be used for repair, with zinc content ≥ 96%, ensuring cathodic protection effect.
  • For large-area corrosion, complete rust removal and overall surface treatment, or replace the corresponding components.

13.5.2 Bolt Thread Stripping Replacement

  • Remove stripped bolts and clean residual threads from the threaded holes.
  • If threaded holes are damaged, re-tap to a larger size and use a larger bolt, or install a thread insert for repair.
  • When replacing bolts, replace flat washers and spring washers simultaneously and tighten to the specified torque.

13.5.3 Side Rail Minor Deformation Correction

  • Minor bending deformation may be corrected slowly with jacks or clamps after unloading. Violent striking is prohibited to avoid cracking.
  • After correction, add reinforcement plates to restore load-bearing capacity.
  • Side rails with severe deformation or plastic deformation shall not be corrected. Replace the entire tray section directly.

13.5.4 Ladder Rung Damage Replacement

  • Remove cables above the damaged ladder rung and unload the load.
  • Cut out the damaged rung, grind the interface, and weld or rivet a new rung.
  • Grind and de-rust the weld area, then apply anti-corrosion treatment.
  • When multiple rungs are damaged, reduce support hanger spacing to lower the single-span load.

13.5.5 Support Hanger Tilt Correction

  • Loosen the support hanger fixing bolts, adjust the hanger rod length or column position to correct verticality.
  • Re-tighten bolts after correction. Add diagonal bracing where necessary.
  • For tilting caused by structural settlement, assess settlement impact and develop a dedicated reinforcement plan.

13.6 Long-Term Idle Maintenance

  • Before long-term idle of the cable tray system, perform a comprehensive cleaning and anti-corrosion repair.
  • Seal the ends and openings of cable trays to prevent dust, moisture, and small animals from entering.
  • Perform inspections every three months to check anti-corrosion and structural conditions.
  • Before re-commissioning, perform a comprehensive inspection and grounding test. The system may only be put back into service after passing.

13.7 Maintenance Records and Archive Management

  • Establish a “one unit, one file” system, recording the cable tray system’s specifications, routing, installation date, and initial parameters.
  • Detailed records of each inspection, maintenance, overhaul, and repair shall include time, personnel, contents, problems, handling results, and replaced components.
  • Test reports, assessment reports, and acceptance records shall be categorized and archived, with retention period not less than the system’s design service life.
  • Maintenance archives serve as the basis for system safety assessment, renovation and upgrade, and fault tracing, and shall be properly maintained.
No. Fault Phenomenon Possible Causes Solutions
1 Misalignment at tray joints Connection plate hole position deviation; end plate deformation during transport; inaccurate installation alignment Adjust connection plate position; correct deformed end plates; use clamps to hold alignment before tightening bolts
2 Excessive joint gaps Section length dimension deviation; cumulative installation error; no allowance for thermal expansion Install gap compensation shims; adjust inter-section spacing; provide expansion joints on long routes
3 Poor overall tray levelness Uneven hanger rod lengths; uneven building ceiling surface; installation without point-by-point calibration Re-adjust hanger rod nuts; calibrate elevation point-by-point with level; replace hanger rods where elevation difference is excessive
4 Lateral displacement and sway Hold-down plates not tightened; excessive support hanger spacing; overly long hanger rods without reinforcement Tighten hold-down plate bolts; add support hangers; install lateral diagonal bracing for long hanger rods
5 Side rail bending deformation Overload usage; excessive span; localized concentrated loads Reduce load; add support hangers to reduce span; disperse concentrated loads; replace if severely deformed
6 Ladder rung bending and sagging Excessive rung spacing; localized load concentration; insufficient rung thickness Increase rung density; disperse localized loads; replace with thicker rungs
7 Ground resistance non-compliant Coating or oxidation on contact surfaces; loose cross-bonding wires; grounding main conductor fault Grind grounding contact surfaces to expose bare metal; tighten cross-bonding wires and grounding bolts; investigate grounding main conductor
8 High inter-section continuity resistance Poor connection plate contact; missing cross-bonding wires; loose bolts Install cross-bonding wires; grind contact surfaces; tighten connecting bolts
9 Rust spots on surface Anti-corrosion coating damaged by impact; excessive ambient humidity; insufficient coating thickness Remove rust and reapply anti-corrosion paint; improve ventilation; upgrade corrosion protection level for severe corrosion
10 Bolt corrosion and seizure Humid environment; insufficient bolt corrosion protection grade; long-term lack of maintenance Spray rust remover/lubricant before removal; replace with stainless steel or hot-dip galvanized bolts; apply anti-rust grease regularly
11 Obvious cable sagging Large rung spacing; insufficient cable tension; too few bundling points Increase rung density; add bundling and fixing points; adjust cable tension
12 Cable jacket scratches Burrs and sharp edges on tray; dragging friction during laying; protective rubber strips detached Grind burrs and sharp edges; install protective rubber strips; standardize laying process to avoid dragging
13 Support hanger loosening and detachment Expansion bolt failure; insufficient wall/slab strength; long-term bolt loosening Replace with chemical anchors; reinforce base structure; regularly re-tighten bolts
14 Severe hanger rod sway Excessive slenderness ratio of hanger rods; no lateral support Add lateral tie rods and diagonal bracing; shorten hanger rod spacing; use larger diameter rods
15 Fire stopping leaking smoke and dust Incomplete sealing; material aging and cracking; not restored after O&M expansion Re-seal with full filling; replace aged stopping materials; restore stopping promptly after expansion
16 Cable jamming at bends Insufficient bending radius; sharp edges on inner side of bend Replace with larger radius bends; grind inner sharp edges; provide manual guidance during laying
17 Water accumulation in tray No drainage holes outdoors; gaps in cover plate seams Drill drainage holes in the bottom; replace cover plates with better sealing; provide proper end waterproofing
18 Cover plate detachment Cover plate deformation; damaged clips; high wind loads Correct or replace cover plates; replace clips; add fixing bolts in high-wind areas
19 Severe electromagnetic interference Insufficient separation between power and weak current cables; separator not grounded; poor grounding Increase separation distance; ensure continuous separator with reliable grounding; improve grounding system
20 Condensation in winter High ambient humidity; large temperature fluctuations Enhance ventilation and dehumidification; apply moisture protection to cables; keep trays ventilated and avoid sealing

15.1 Basic Knowledge

Q1: What is the difference between ladder-type open cable trays and trough-type cable trays? How should they be selected for equipment rooms?

A: The core difference lies in structure and performance. Ladder-type trays are open-frame with a lattice structure, offering good heat dissipation, strong load capacity, easy maintenance, and low cost, but weaker protection. Trough-type trays have fully enclosed structures, providing dust protection and interference shielding, but poorer heat dissipation, heavier weight, higher cost, and more difficult maintenance.

Selection recommendations for equipment rooms: For main routes with large quantities and high current-carrying capacity (main power cables, main optical cables), select ladder-type open cable trays to leverage their heat dissipation and maintenance advantages. For branch control cables, signal cables to cabinets, or areas with high dust protection/interference shielding requirements, select trough-type trays, forming a combined solution of “open main routes + enclosed branches.”

Q2: Can cover plates be added to ladder-type open cable trays? Will heat dissipation be affected after adding covers?

A: Yes, cover plates are optional. Ladder-type trays have dedicated matching cover plates, installed by clip or lap joint, and can be easily removed at any time.

Adding cover plates will somewhat affect top air convection, slightly reducing heat dissipation performance. However, the sides and bottom remain ventilated, and overall heat dissipation is still far superior to fully enclosed trough-type trays. It is recommended to add cover plates only in local areas with high dust or falling object risks, without covering the entire route, balancing protection and heat dissipation.

Q3: What is the standard section length of ladder-type cable trays? Can custom lengths be made?

A: The conventional standard section length is 2000 mm. Large-specification heavy-duty trays commonly use 3000 mm sections. Large-span dedicated trays can be made in 6000 mm sections.

Custom lengths are supported. Non-standard section lengths can be customized according to actual on-site dimensions, reducing on-site cutting and improving installation accuracy and efficiency.

15.2 Selection

Q1: What specification of main route cable tray should be selected for an equipment room? How to calculate?

A: The cable tray specification is calculated based on the total cross-sectional area of cables, following the fill rate principle: power cable fill rate shall not exceed 40%, control cable fill rate shall not exceed 50%, and 10%-15% expansion margin shall be reserved.

Calculation method: Sum the outer diameter cross-sectional areas of all cables and divide by the fill rate to obtain the required net cross-sectional area of the tray. Then select the corresponding tray width and height. For example, if the total cable cross-sectional area is 36,000 mm², at a 40% fill rate, the required net tray area is 90,000 mm². A 600×150 mm (net area 90,000 mm²) or 500×200 mm specification may be selected.

Q2: How to select the load rating? How to know if it will be overloaded?

A: First estimate the total weight of cables in the tray: power cables approximately 8-12 kg/m per cable, optical cables and network cables approximately 2-5 kg/m per cable. Sum to obtain the total uniformly distributed load, then multiply by a 1.5 safety factor and select a load rating greater than this value.

For example, if a tray contains 10 cables of YJV-4×120 type, each approximately 4.5 kg/m, the total weight is 45 kg/m ≈ 0.45 kN/m. After applying the safety factor, it becomes 0.675 kN/m. Select the 1.0 kN/m medium load rating.

Q3: How to select different surface treatments? Which is best for equipment rooms?

A: Surface treatment selection is based on the environment and appearance requirements:

Surface Treatment Characteristics Recommended Use
Electro-galvanized Low cost but poor corrosion resistance Dry temporary equipment rooms only; not recommended for long-term use
Hot-dip galvanized Good corrosion resistance, high cost-effectiveness Suitable for all indoor/outdoor equipment rooms; most common universal solution
Electrostatic powder coating Aesthetic appearance, color options, medium corrosion resistance Indoor equipment rooms with high aesthetic requirements
Galvanized + powder coating Dual-layer protection, excellent corrosion resistance and appearance High-end data centers
Stainless steel / FRP For severely corrosive environments Not required for ordinary equipment rooms

Recommendation: Hot-dip galvanized for ordinary equipment rooms; galvanized + powder coating for high-end equipment rooms.

15.3 Installation

Q1: What is the general spacing for cable tray support hangers?

A: Support hanger spacing is determined by the tray load rating:

Load Rating Spacing
Light-duty 1.5-2 m
Medium-duty 1.5-2 m
Heavy-duty 1.2-1.5 m
Extra-heavy-duty 1-1.2 m
  • Vertical sections, both ends of bends, branch points, and ends require densified spacing ≤ 0.5 m.
  • Specific spacing shall be verified by deflection calculation based on actual loads, ensuring deflection does not exceed 1/200 of the span.

Q2: Can power and weak current cables be placed in the same ladder-type tray?

A: Yes, but specification requirements must be met: install a continuous metal separator of equal height to the tray, separating power and weak current cables into different compartments, with the separator reliably grounded throughout. Under these conditions, electromagnetic shielding effectiveness is approximately 20 dB, sufficient for general weak current system interference requirements.

For high-frequency, high-sensitivity signal circuits, or where reliable grounding is unavailable, same-support installation is not recommended. Layering is recommended instead, with a layer spacing ≥ 300 mm.

Q3: Can cable trays be fixed directly to ceiling suspension system (ceiling suspension system)?

A: Absolutely not. The self-weight of the tray plus cables is very heavy. Ceiling suspension members cannot bear this load, which would cause suspension member deformation, ceiling collapse, and safety accidents.

Cable tray support hangers must be fixed to the building’s main structure (slabs, beams, load-bearing walls, columns). Fixing to ceiling suspension systems, lightweight partition walls, decorative panels, or other non-load-bearing structures is strictly prohibited.

15.4 Operation and Maintenance

Q1: Does the cable tray require regular ground resistance testing? How often?

A: Yes. Ground resistance is a core indicator for electrical safety and must be regularly tested.

Ordinary equipment rooms: test once per year, with an additional test recommended before the thunderstorm season. High-humidity and corrosive environments: test every six months. Test records shall be archived. Promptly rectify any resistance exceeding limits.

Q2: Is it allowed to stand on cable trays for maintenance work?

A: Standing or walking on cable trays is strictly prohibited. Ladder-type trays are designed for uniformly distributed cable loads, not pedestrian loads. Localized concentrated stepping can cause rung deformation, side rail instability, and even collapse or falling accidents, which are extremely dangerous.

High-altitude maintenance must use scaffolding, aerial work platforms, or dedicated maintenance ladders. Stepping on cable trays is prohibited.

Q3: Can new cables be added to cable trays? What precautions are needed?

A: Yes, but the following precautions apply:

  • First verify the total load to confirm it does not exceed the rated load of the tray.
  • Place power and weak current cables in separate compartments; do not mix compartments.
  • Avoid dragging that damages existing cables during placement.
  • After adding, ensure proper bundling, fixing, and labeling.
  • Re-seal fire stopping points densely after adding new cables.

15.5 Safety Specifications

Q1: Must cross-bonding wires be installed at every joint of the cable tray?

A: According to GB 50303 specifications, for galvanized cable trays, if both ends of the connection plate have no fewer than 2 connecting bolts with lock nuts or lock washers, cross-bonding wires may be omitted in non-explosion-proof scenarios.

However, equipment rooms are high-reliability scenarios. It is recommended to install cross-bonding wires at every joint to ensure reliable full-length continuity and reduced ground resistance. Especially for powder-coated trays, the coating is insulating, and cross-bonding wires are mandatory.

Q2: Is fire stopping mandatory when cable trays pass through fire compartments?

A: Yes, mandatory. According to GB/T 51410 and fire protection regulations, when cable trays pass through fire walls or fire-rated floors, the openings must be densely sealed with fire-stop materials. The fire resistance rating shall not be lower than that of the wall/floor.

This is a mandatory fire protection requirement and shall never be omitted. After O&M expansion, fire stopping must also be restored promptly.

Q3: Are seismic supports required for cable trays? Under what conditions?

A: According to GB 50981 specifications, cable tray systems with a gravity load ≥ 150 N/m shall be equipped with seismic support hangers, and this requirement is mandatory in regions with seismic fortification intensity of 6 degrees or above.

Equipment room cable trays essentially all meet the weight requirement. Therefore, formal projects must design and install seismic supports in accordance with specifications to ensure seismic safety.

16.1 Acceptance Basis and Standards

Category Standards
National standards GB 50303-2015 “Acceptance Standard for Construction Quality of Building Electrical Engineering”; GB 50311-2016 “Code for Engineering Design of Generic Cabling System for Building and District”; GB 50981-2014 “Code for Seismic Design of Mechanical and Electrical Equipments in Buildings”; GB/T 51410-2020 “Technical Standard for Application of Building Fire-stop”
Industry standards JB/T 10216-2013 “Cable Tray for Electric Control and Distribution”; T/CECS 31-2017 “Technical Specification for Steel Cable Tray Engineering”
Design documents Construction drawings, design changes, technical consultation documents
Contract requirements Quality and performance requirements in supply contracts and technical agreements

16.2 Acceptance Classification and Process

Acceptance of the ladder-type open cable tray system is divided into four stages: incoming material acceptance, concealed work acceptance, subdivisional work acceptance, and completion acceptance. Each stage proceeds sequentially; the next stage may only commence after the previous stage has passed acceptance.

16.2.1 Incoming Material Acceptance

Upon material arrival, the construction unit, supervision unit, and construction organization shall jointly inspect product quality and documentation. Materials may only be stored and used after passing inspection.

16.2.2 Concealed Work Acceptance

Items that will be concealed after completion — such as support hanger anchoring, grounding main conductors, and fire stopping — must undergo concealed work acceptance before concealment. Only after passing may they be concealed, with photographic records retained.

16.2.3 Subdivisional Work Acceptance

After cable tray installation and cable laying are fully complete, subdivisional work acceptance shall be performed to comprehensively check installation quality and performance indicators. This is the core acceptance stage.

16.2.4 Completion Acceptance

After the overall project is complete, completion acceptance shall be conducted in conjunction with system integrated trial operation, providing final confirmation of the cable tray system and handing over as-built documentation.

16.3 Incoming Acceptance Contents and Methods

16.3.1 Quality Documentation Inspection

Check product certificates, factory inspection reports, material certificates, third-party test reports, and fire-retardant test reports. Documents shall be complete, information consistent, and stamped with the manufacturer’s official seal.

16.3.2 Appearance and Dimension Inspection

  • Appearance inspection: Surface shall be smooth and flat, with uniform plating/coating, free of bubbles, peeling, and runs. No deformation, twisting, or cracks. Welds shall be full and smooth, free of false welding, missed welding, and weld bumps.
  • Dimension sampling: Use steel tape measures and calipers to sample-check width, height, plate thickness, and ladder rung spacing. Deviations shall comply with standard requirements.
  • Accessory inspection: Accessories shall be complete, with matching specifications, free of damage and corrosion.

16.3.3 Sampling and Third-Party Testing Requirements

For items with quality disputes or important projects, samples may be sent to third-party testing institutions for testing of mechanical properties, anti-corrosion performance, fire performance, and other indicators. Non-conforming products shall be removed from the site.

16.4 Concealed Work Acceptance

  • Support hanger anchoring acceptance: Check the embedment depth, specification, and spacing of expansion bolts/chemical anchors. Perform pull-out tests on sampled anchors. Anchoring force shall meet design requirements.
  • Grounding system concealed acceptance: Check the specification, routing path, and connection method of grounding main conductors. Test continuity resistance and ground resistance.
  • Fire stopping concealed acceptance: Before sealing, check opening treatment and fire-stop material filling. Sealing density shall meet requirements. Retain before-and-after construction photos.
  • Records: Concealed work acceptance records shall be completed with signatures from all parties.

16.5 Subdivisional Work Acceptance Items and Acceptance Criteria

16.5.1 Main Control Items

Item Acceptance Criteria
Grounding Reliable grounding, ground resistance meets design requirements, full-length continuity good
Specification and material Tray specification, model, and material meet design requirements; load capacity satisfies load requirements
Support hanger anchoring Firm anchoring, pull-out test passed, no loosening or detachment risk
Fire stopping Compliant with specifications, fire resistance rating meets requirements
Seismic supports Configuration compliant with specifications, securely installed

16.5.2 General Items

Item Acceptance Criteria
Installation straightness Aligned and flat, with levelness, verticality, and straightness deviations within specification limits
Joint quality Gaps and misalignment meet requirements, joints flat
Support hanger arrangement Uniform spacing, neat arrangement, verticality and levelness compliant
Safety spacing Clearances between tray and various pipelines comply with specifications
Deformation and coating Deformation and coating damage repaired properly, overall anti-corrosion intact
Labels and accessories Complete and legible labels, fully installed accessories

16.5.3 Measured Test Items

Test Item Allowable Deviation Test Method
Tray straightness ≤ 5 mm/10 m, ≤ 20 mm/full length Steel tape measure, string line measurement
Horizontal tray levelness ≤ 2‰ Spirit level measurement
Vertical tray verticality ≤ 2‰ Plumb bob, theodolite measurement
Joint gap ≤ 1 mm Feeler gauge measurement
Joint misalignment ≤ 0.5 mm Straightedge, feeler gauge measurement
Support hanger spacing ±100 mm Steel tape measure

16.6 Completion Acceptance Documentation List

  • Cable tray system as-built drawings, design changes, and technical consultation documents.
  • Material factory certificates, test reports, and material certificates.
  • Concealed work acceptance records and photographic documentation.
  • Installation records, commissioning records, and ground resistance test records.
  • Load test reports and seismic installation acceptance records.
  • Subdivisional work acceptance records and completion acceptance records.
  • Product user manuals and maintenance manuals.

16.7 Non-Compliance Rectification Process

  • For problems found during acceptance, issue a rectification notice specifying the rectification content, deadline, and responsible person.
  • The construction organization shall rectify as required and apply for re-inspection after completion.
  • After re-inspection passes, acceptance is granted. If re-inspection fails, continue rectification until compliance is achieved.
  • All rectification records shall be filed in the completion archives.

1. Search Keyword Classification

1. Core Primary Keywords

Ladder-type open cable tray, ladder-type cable tray, open cable tray, equipment room ladder tray, cable ladder

2. High-Conversion Long-Tail Keywords

Ladder-type open cable tray installation, ladder tray specification parameter table, equipment room cabling tray selection, hot-dip galvanized ladder tray, heavy-duty ladder-type cable tray, ladder tray support hanger spacing, power and weak current tray layering standard, open cable tray heat dissipation advantages

3. Industry Traffic Keywords

Data center cable tray selection, equipment room integrated cabling tray, weak current engineering cable tray, electrical installation cable tray, substation cable tray, overhead cabling equipment room tray, cold aisle tray, IDC equipment room cabling tray

4. Brand-Specific Keywords

Guangdong Lain ladder tray, Lain equipment room cable tray, Lain smart equipment room cabling, Guangzhou ladder tray manufacturer, Lain cable tray

5. Dropdown/Related Search Keywords

Ladder tray vs trough tray difference, ladder tray specification model list, ladder tray installation specification, open cable tray advantages and disadvantages, ladder tray grounding specification, ladder tray fill rate calculation, ladder tray elbow fabrication, ladder tray weight per meter

2. SEO Optimization Tag System

1. Page Core Optimization Tags

  • Page topic: Ladder-type open cable tray installation wiring commissioning manual_Equipment room cabling dedicated cable tray
  • Core keyword density: Core keywords evenly distributed, naturally embedded in the text body, appearing in both opening and closing paragraphs
  • Content length: Long-form technical documentation covering full lifecycle product knowledge, meeting in-depth search needs

2. Title Tag

Ladder-type Open Cable Tray Installation Wiring Commissioning Manual_Equipment Room Ladder Cable Tray Parameters_Guangdong Lain Smart Equipment Room Equipment

3. Meta Keywords

Ladder-type open cable tray, ladder-type cable tray, equipment room cabling cable tray, ladder tray installation, cable ladder parameters, open cable tray manual, Guangdong Lain cable tray

4. Meta Description

Guangdong Lain Smart Equipment Room Equipment professionally provides ladder-type open cable trays. This manual details product introduction, composition, classification, technical parameters, installation, wiring, commissioning, maintenance, common problems, and acceptance standards for ladder-type cable trays. Suitable for main route cabling in data centers, communication equipment rooms, and similar scenarios. High load capacity, excellent heat dissipation, convenient maintenance.

5. H1 Tag

Ladder-type Open Cable Tray Installation Wiring Commissioning Manual

6. H2 Tags

Product Introduction, Product Composition, Product Classification, Product List, Product Principles, Product Technical Parameters, Product Functions and Features, Product Application Scenarios, Product Installation, Product Wiring, Product Commissioning, Product Precautions, Product Maintenance and Repair, Common Product Problems and Solutions, Product QA, Product Acceptance

7. Internal Link Optimization Tags (Anchored Text – Naturally Embedded)

  • Core anchor text: Ladder-type open cable tray, ladder-type cable tray, equipment room cabling cable tray
  • Long-tail anchor text: Ladder tray installation process, cable tray grounding specification, equipment room power/weak current separation tray, hot-dip galvanized ladder tray parameters
  • Related anchor text: Trough-type cable tray, wire mesh cable tray, seismic support hanger, integrated cabling system, data center equipment room construction

This document is copyrighted by Guangdong Lain Smart Equipment Room Equipment Co., Ltd. and is protected by national copyright law.

No organization or individual may reproduce, reprint, excerpt, or alter this document in whole or in part without written authorization from the Company, nor use it for commercial dissemination.

For reprinting or citation of this document, the source must be acknowledged as “Source: Guangdong Lain Smart Equipment Room Equipment Co., Ltd.,” and content integrity must be maintained without deletion or modification of original meaning.

Unauthorized infringing use will be pursued by the Company in accordance with the law.

If the content of this document is updated, no separate notice will be provided. The latest version shall prevail.