KITOZER Liquid Cooling CDU (Coolant Distribution Unit) Technical Guide

Table of Contents

KITOZER Liquid Cooling CDU (Coolant Distribution Unit) Technical Guide

Brand: KITOZER Manufacturer: Guangzhou Laian Intelligent System Development Co., Ltd. Category: Data Center Precision Liquid Cooling Equipment Version: V2.0 Updated: October 2026

1. Product Overview

KITOZER liquid cooling CDU system architecture

A Liquid Cooling CDU (Coolant Distribution Unit) is the core heat exchange and distribution device in a data center liquid cooling system. It carries the critical task of stably transporting heat generated on the server side (secondary loop) to the facility side (chiller, dry cooler, or cooling tower). The KITOZER Liquid Cooling CDU is developed and integrated by Guangzhou Laian Intelligent System Development Co., Ltd. It is widely used in high-density server racks, AI computing clusters, high-performance computing (HPC) clusters, GPU training nodes, telecom rooms, edge computing nodes, and energy storage power conversion equipment.

As single-chip power density continues to rise, traditional air cooling has reached its practical limit when facing rack heat loads of tens to hundreds of kilowatts. Liquid cooling, leveraging the much higher specific heat and thermal conductivity of water or glycol-water solutions, removes heat directly from chip surfaces with lower flow, lower power consumption, and quieter operation. The CDU is the energy exchange hub between the end cold plates and the facility cooling source. Its performance, reliability, and control precision directly determine the heat exchange efficiency, PUE, and operational safety of the entire liquid cooling system.

The KITOZER Liquid Cooling CDU uses a plate heat exchanger as the isolation core between the primary and secondary loops. The primary loop connects to chilled water from a chiller or dry cooler, while the secondary loop drives coolant through server cold plates or spray manifolds via circulation pumps. The two fluids exchange heat in counter-flow inside the plate heat exchanger without direct mixing, keeping the server-side water clean and uncontaminated. The CDU also integrates variable-frequency circulation pumps, expansion and pressurization, precision filters, flow and pressure sensors, temperature sensors, leak detection, electrical control cabinet, and a touchscreen HMI, forming a complete skid-mounted heat exchange unit.

Unlike early field-assembled systems, the KITOZER CDU integrates all these components into a standard rack or floor-standing cabinet. Factory-tested piping, pressure tests, electrical wiring, and control logic mean on-site installation only requires connecting primary/secondary water pipes and power cables, dramatically reducing construction time and leak risk.

1.1 Product Positioning

The KITOZER Liquid Cooling CDU targets mid-to-high density data centers and industrial thermal management. Single-unit cooling capacity ranges from 30kW to over 800kW, serving scenarios from single-rack liquid cooling retrofits to full-row deployments and multi-rack data center builds. The product balances plug-and-play convenience with deep customization, adapting to site water quality, supply temperature, rack height, piping routes, noise limits, and redundancy requirements.

1.2 Core Value

The KITOZER CDU delivers value in four dimensions: first, significantly lowering data center PUE through high-efficiency heat exchange and variable-frequency distribution; second, improving equipment reliability via sealed secondary loops and leak monitoring; third, reducing room noise by eliminating rack and room AC fans; fourth, saving floor space because liquid cooling transports far more heat per square meter than air cooling.

2. Working Principle

KITOZER end-to-end direct liquid cooling solution

2.1 Dual-Loop Heat Exchange Architecture

The KITOZER CDU adopts a typical dual-loop architecture. The secondary loop (user-side / equipment-side) connects directly to server cold plates, GPU water blocks, memory liquid cooling modules, or spray manifolds. It circulates purified coolant, usually deionized water or low-concentration glycol-water solution, to absorb heat close to the chips. The primary loop (facility-side) connects to building chillers, dry coolers, cooling towers, or closed-circuit cooling devices, ultimately rejecting the transported heat to the outdoor environment.

The two loops are physically isolated by the plate heat exchanger. Coolant never mixes between sides; heat transfers only through thin stainless steel plates. This isolation ensures the server side only contacts clean, controlled, deaerated, and inhibited secondary coolant, while facility-side water quality fluctuations never contaminate expensive microchannel cold plates inside servers.

2.2 Heat Transfer Path

Heat follows this path: chips (CPU, GPU, memory, power) interface with cold plates via thermal paste/pads; the cold plate base conducts heat; internal microchannels or pin fins convect heat to flowing coolant; heated coolant travels through internal hoses to the rack-side manifold, then to the secondary return main; returning coolant passes through a precision filter before entering the heat exchanger secondary side; in the exchanger, heat transfers to primary-side cold water; cooled coolant is repressurized by variable-frequency pumps and sent back to racks. Primary-side warmed water returns to the chiller or dry cooler to be re-cooled, forming a continuous closed-loop heat transport process.

2.3 Heat Exchange Equation

The plate heat exchanger follows Q = K·A·ΔTm, where Q is heat duty, K is the overall heat transfer coefficient, A is effective area, and ΔTm is the log mean temperature difference. KITOZER brazed or gasketted plate heat exchangers achieve K values of 3000 to 6000 W/(m²·K) due to chevron plate turbulence, far higher than shell-and-tube exchangers, enabling compact designs.

2.4 Variable-Frequency Pumps

Secondary circulation pumps use high-efficiency centrifugal pumps with VFDs. The controller reads secondary supply/return pressure differential, flow, and branch temperatures, adjusting pump speed to maintain target differential pressure or temperature. At low server load, pump speed drops, saving distribution energy; at high load, speed rises. Pump sets use N+1 redundancy with hot standby, switching in seconds on primary pump failure. Pumps must satisfy both flow (determined by heat load and ΔT) and head (overcoming cold plate, hose, manifold, filter, and header losses).

2.5 Pressurization and Expansion

Closed loops expand/contract with temperature. KITOZER CDUs use expansion tanks and automatic makeup pumps to absorb volume changes and maintain system pressure at a slight positive pressure (typically 1.0 to 2.5 bar). This positive-pressure design has a major safety benefit: if a pipe or fitting ruptures, outside air is drawn in rather than coolant spraying out, reducing damage to electronic equipment.

2.6 Filtration and Water Quality

Secondary return lines include 50 to 100 μm basket or Y-type filters, with optional automatic backwash filters on key models. Filters trap welding slag, seal tape fragments, and particulate debris to prevent microchannel blockage. Optional online conductivity monitoring and purification units track conductivity, pH, and dissolved oxygen, triggering alarms when parameters drift.

2.7 Control Logic and HMI

The built-in PLC maintains stable secondary supply temperature (typically 25 to 45°C), stable supply/return differential pressure, and modulates the primary-side control valve based on load. All data displays on a local touchscreen and uploads via Modbus TCP, BACnet/IP, or SNMP to DCIM/BMS for remote monitoring and alarming.

2.8 Quick Disconnects and Leak Safety

Rack-to-main connections use drip-free quick disconnects with integral shutoff valves. KITOZER配套 rack manifolds use stainless or aluminum with supply/return QDs per server node. Combined with under-unit drip pans and rope-type leak sensing, the system localizes and alarms on leaks within seconds.

3. Technical Specifications

KITOZER rack manifold and quick disconnects

The KITOZER CDU is offered in multiple standard models by cooling capacity. The table below lists key parameters for mainstream models; custom configurations are available.

3.1 Mainstream Models

Parameter KC-CDU30 KC-CDU80 KC-CDU150 KC-CDU300 KC-CDU600
Rated capacity (kW) 30 80 150 300 600
Secondary flow (m³/h) 5.2 13.8 25.9 51.7 103.4
Secondary ΔT (°C) 5 5 5 5 5
Supply temp range (°C) 18~50 18~50 18~50 18~50 18~50
Design pressure (bar) 10 10 10 10 16
Heat exchanger Brazed plate Brazed plate Brazed plate Gasketed plate Gasketed plate
Pump configuration 1+1 VFD 1+1 VFD 2+1 VFD 2+1 VFD 3+1 VFD
Pump head (m) 12 15 18 20 24

3.2 Electrical and Control

Parameter Specification
Power supply AC 380V 3-phase 5-wire 50Hz (AC 220V single-phase for small models)
Full-load input power KC-CDU30 ~1.8kW; KC-CDU150 ~6.5kW; KC-CDU600 ~22kW
Control PLC + 7-inch color touchscreen
Communication Modbus TCP, BACnet/IP, SNMP (optional), dry contacts
Temperature accuracy ±0.3°C (PT1000 Class A)
Pressure accuracy ±0.5% FS (4-20 mA transmitter)
Flow measurement Electromagnetic or ultrasonic flowmeter
Leak detection Unit base drip pan + rope sensor
Protection Pump overload, over/under voltage, over temp, filter blockage, leak, comm loss

3.3 Mechanical and Interfaces

Parameter Specification
Dimensions W×D×H KC-CDU30 ~600×800×1800mm; KC-CDU150 ~1200×1000×2000mm; KC-CDU600 ~2200×1200×2000mm
Weight KC-CDU30 ~280kg; KC-CDU150 ~850kg; KC-CDU600 ~2600kg
Primary connection Flanged DN50~DN200
Secondary connection Quick disconnect or flange DN40~DN150
Noise (1m) ≤62 dB(A) full load
Protection Control cabinet IP54; water zone IP20
Coolant Secondary: DI water or 25% glycol; Primary: chilled/cooling water
Ambient 10~35°C, RH ≤85% non-condensing

4. Selection Guide

Correct selection is the prerequisite for long-term stable liquid cooling operation. KITOZER recommends the following steps, with engineering review by Guangzhou Laian.

4.1 Determine Heat Load

Sum TDP of all liquid-cooled components (CPU, GPU, NIC, memory, some PSUs) per rack, then add 15% to 25% redundancy for future expansion and peak conditions. Multiply rack load by rack count and add piping margin. AI training clusters can show several-fold short-term load swings; select CDU to handle peaks without supply temperature spiking into thermal throttling.

4.2 Determine ΔT and Flow

By Q=cmΔT, larger ΔT means smaller flow, pump power, and pipe diameter, but too large a ΔT causes temperature non-uniformity across chips. Engineering practice uses 5 to 10°C ΔT; high-density GPU nodes favor ~5°C for chip temperature uniformity.

4.3 Verify Primary-Side Conditions

Confirm available primary supply temperature, flow, and pressure. If primary supply is warm (e.g., dry cooler at 30°C+ in summer), verify whether the plate exchanger can still deliver target secondary supply temperature. Insufficient approach may require more exchanger area, reduced liquid-cooled fraction, or added chiller.

4.4 Redundancy and Availability

For mission-critical sites, choose N+1 or 2N pump redundancy, dual power, and multi-CDU ring-pipe architectures. KITOZER CDUs support parallel operation; any unit can be isolated for maintenance while others carry load.

4.5 Selection Decision Table

Project Profile Recommended Model Configuration
≤15kW/rack, few racks KC-CDU30 1+1 pump, single unit
20~40kW/rack, 5~10 racks KC-CDU80 1+1 pump, expansion ports
40~80kW/rack, 10~20 racks KC-CDU150 2+1 pump, ring secondary
Full-row GPU cluster KC-CDU300 2+1 pump, dual power, remote monitoring
Whole-floor liquid cooling Multiple KC-CDU600 2N redundancy, chiller sequencing

4.6 Hydronic Balancing

Without balancing, near-CDU racks get excess flow while far racks starve. KITOZER CDUs provide balancing valves on each branch; commissioning measures and tunes each branch. For long-pipe multi-rack projects, model hydronic resistance in design.

5. Installation Requirements

5.1 Civil Conditions

KITOZER CDUs are heavy. KC-CDU150+ approaches one ton; floor loading should be ≥8 kN/m², with channel base or vibration pads. Leave ≥800mm clearance around sides and ≥600mm above for heat exchanger service.搬运通道 width must exceed unit width by 200mm.

5.2 Piping

Use seamless steel or stainless pipe; secondary side prefers 316L. Weld by certified welders, pressure test at 1.5× working pressure for 30 minutes. Install isolation ball valves and balancing valves per rack branch. High-point vents, low-point drains. Use glycol-compatible seals.

5.3 Electrical

Feed CDU from UPS or power distribution cabinet via dedicated circuit with breaker and RCD. Ground to building equipotential grounding at ≤1Ω. Separate communication and power cables. Power PLC/touchscreen from UPS.

5.4 Flushing and Fill

Flush secondary loop with DI water at high flow until clear; drain; fill with formulated coolant. Vent high points. Prime pumps before start. Run 24-48h, sample conductivity and particulate.

5.5 Commissioning and Acceptance

Jog pumps, ramp speed, check leaks, set supply temp and ΔP targets, observe load-following, simulate alarms. Acceptance includes pressure test records, water quality report, 72h run log, alarm test records.

6. Operation and Maintenance

6.1 Daily Inspection

Check secondary supply temp stability, supply/return ΔP, pump current/frequency, expansion tank pressure, filter ΔP trend, and leak alarms daily via touchscreen or remote monitoring.

6.2 Maintenance Schedule

Period Tasks
Weekly Review alarm log; inspect pans/fittings; record ΔT and flow
Monthly Sample coolant conductivity/pH; check filter ΔP; inspect pump sound/vibration
Quarterly Alternate duty/standby pumps; clean cabinet fan filters; tighten terminals; test leak alarm
Half-year Calibrate temp/pressure sensors; check primary ΔP; test UPS switchover
Yearly Replace secondary filter element; lab coolant analysis; check expansion tank precharge; clean outdoor cooler
Two-year Inspect plate exchanger fouling; replace gaskets; cable insulation test

6.3 Coolant Maintenance

Quarterly lab sampling; add inhibitor/biocide or change fluid as needed. Monitor glycol concentration. Do not mix incompatible inhibitor brands.

6.4 Troubleshooting

Symptom Possible Cause Action
High secondary supply temp Warm primary; fouled exchanger; overload Check chiller; clean plates; verify rack load
Fluctuating ΔP Cavitation; valve fault; trapped air Check tank pressure; vent; calibrate valve
Filter ΔP alarm Clogged element Switch or replace
Pump short-cycling Bad deadband; leaking check valve Retune; inspect check valve
Leak alarm Loose fitting; aged hose; pan water Locate leak; tighten/replace; trace source
Rising conductivity Contamination; exhausted DI Change water; inspect purification; check primary leak

7. FAQ

Q: What is the difference between a CDU and a chiller?

A: A chiller produces chilled water via a refrigeration cycle (compressor, evaporator, condenser). A CDU does not cool itself; it is a heat exchange and distribution skid that moves chiller dry-side capacity to server cold plates via the secondary loop. A CDU always needs an external cooling source.

Q: Can I use tap water on the secondary side?

A: Not recommended. Tap water contains chloride, hardness, and microbes that corrode stainless steel and foul microchannels over months. Use DI water or formulated glycol-water and monitor water quality.

Q: How many servers can one CDU support?

A: It depends on per-server heat load and CDU capacity. A KC-CDU150 at 40kW/rack supports ~3-4 full racks, roughly 30-40 2U servers. KITOZER engineers calculate final count with piping margin.

Q: Do servers overheat if the CDU fails?

A: KITOZER CDUs have N+1 redundant pumps switching within seconds. On whole-unit failure, servers retain thermal mass for minutes, enough for orderly shutdown. Critical sites use parallel ring-pipe CDUs.

Q: Why positive-pressure secondary design?

A: Positive pressure means a rupture draws in air rather than spraying coolant, reducing circuit-board damage. This is a widely adopted data center liquid cooling safety principle.

Q: How to choose glycol concentration?

A: Concentration depends on winter freeze protection. DI water for non-freezing rooms; 25% glycol near 0°C; 30-40% for outdoor piping. Higher concentration improves freeze protection but raises viscosity and pump power.

Q: Does KITOZER CDU support remote monitoring?

A: Yes. Standard Modbus TCP/BACnet/IP integrates with DCIM/BMS for temperature, pressure, flow, pump status, alarms, trends, and email/SMS alerts.

Q: Can primary and secondary share piping?

A: No. They must be isolated by the plate exchanger. Direct connection would contaminate server-side cold plates.

Q: How long does commissioning take?

A: Standard units need 1-2 working days after site hookups, including flushing, filling, venting, tuning, and 72h trial run. Large multi-unit projects need 1-2 weeks.

Q: What is the lead time?

A: Standard units ship in 4-6 weeks after order; custom units 8-12 weeks. Guangzhou Laian provides turnkey design-to-service support.

Q: Does the CDU add noise?

A: Pump noise is controlled by low-RPM centrifugal pumps and vibration isolation; full-load noise ≤62 dB(A), far below equivalent room AC.

Q: Can the CDU scale as server power rises?

A: Yes. Modular design with reserved pump modules, parallel CDU expansion, and additional plate count avoids full replacement.

8. Application Scenarios

The KITOZER Liquid Cooling CDU has been applied across high-heat scenarios:

8.1 AI Computing and GPU Training Clusters

Single-node power reaches several to tens of kW; rack heat exceeds 50-100kW. Cold-plate liquid cooling with CDU is the mainstream choice, enabling dense deployment with controlled PUE.

8.2 High-Performance Computing

Scientific computing, weather, genomics, and engineering simulation run continuously; KITOZER redundant CDUs support 24/7 operation.

8.3 Retrofit of Existing Data Centers

Local CDU+cold plate retrofits raise rack density without full HVAC overhaul, extending room life.

8.4 Energy Storage and Power Conversion

PCS converters, battery racks, and PV inverters benefit from industrial-grade KITOZER CDU temperature control.

8.5 Telecom and Edge Computing

5G edge rooms are space-constrained; compact KITOZER CDUs deploy dense compute in small footprints.

8.6 Industrial and Test

Lasers, accelerators, precision test equipment, and radar amplifiers rely on stable CDU temperature control.

9. Technology Trends

Liquid cooling continues to evolve. Cold plates will move toward higher heat flux and lower flow resistance, complemented by spray and immersion cooling. CDUs themselves are becoming more integrated, efficient, and intelligent. VFD pumps, adaptive ΔP control, predictive maintenance, and sequencing with chillers/dry coolers are becoming standard. Guangzhou Laian tracks industry standards and iterates KITOZER products accordingly.

Higher supply temperatures (toward 35-45°C) extend free-cooling hours. KITOZER CDU control architecture already supports coordination with outdoor dry coolers and cooling towers. CDUs are also becoming data acquisition nodes feeding DCIM for load-following cooling.

10. CDU vs Traditional Air Cooling

Dimension Traditional Air Cooling KITOZER Liquid CDU
Rack capacity ≤8-15kW 50-100kW+
Specific heat Air 1.005 kJ/(kg·K) Water 4.18 kJ/(kg·K)
Typical PUE 1.5-1.8+ 1.1-1.3
Noise Fans + AC loud Pumps quiet; fewer fans
Floor space Large AC and aisle space Compact piping, higher utilization
Reliability AC-dependent Redundant pumps + positive pressure
Capex Lower Higher, but long-term energy savings
Scalability AC capacity-limited Modular parallel CDUs

10.1 Relationship to Immersion and Spray Cooling

Cold-plate is one liquid cooling route. Immersion submerges servers in dielectric fluid; spray directs coolant onto components. The KITOZER CDU serves all three: it handles secondary circulation, isolation, pressurization, and filtration regardless of end form.

11. Coolant Chemistry

11.1 Deionized Water

DI water (conductivity ≤1 μS/cm) has high specific heat and low viscosity, making it the mainstream cold-plate coolant. It is aggressive and must be monitored with inhibitors.

11.2 Glycol-Water

Use formulated inhibited glycol for freeze protection. Balance freeze point against viscosity rise.

11.3 Dielectric Fluids

Special synthetic hydrocarbons or fluorinated fluids are used for immersion or leak-sensitive sites; CDU exchanger area and pump head must be recalculated. KITOZER customizes seals and plates for such media.

11.4 Water Quality Targets

Parameter Target Meaning
Conductivity ≤10 μS/cm Rising = contamination/inhibitor depletion
pH 7.5~9.0 Low = corrosion; high = precipitation
Chloride ≤10 ppm High = stainless pitting
Particulate None visible post-filter Indicates corrosion or filter failure
Glycol concentration Per freeze requirement Affects freeze point and viscosity

12. Core Components

12.1 Plate Heat Exchanger

KITOZER uses brazed plate exchangers on smaller models and gasketed plate exchangers on larger units. Plates are 316L stainless; gaskets EPDM. Approach is typically 2-4°C, balancing capital and operating cost.

12.2 Variable-Frequency Pumps

High-efficiency vertical centrifugal pumps with IE3+ motors and VFDs. Duty/standby alternation equalizes runtime; failure switches over within 3-5 seconds.

12.3 Expansion Tank

Diaphragm-type bladder tank precharged with nitrogen, sized at 5-8% of system water volume. Auto makeup pump maintains pressure.

12.4 Filters

Basket-style 50-100 μm filters with differential pressure switch. Optional duplex filters for online switching.

12.5 Sensors

PT1000 temperature, 4-20mA pressure, electromagnetic/ultrasonic flow, conductivity (optional), leak sensors. Data logged locally for ≥1 year.

12.6 Electrical Cabinet

Floor-standing cabinet with touchscreen window, breakers, contactors, VFDs, PLC, power supply, terminals. Heater for condensation control.

13. Design Calculation Example

Example: 10 liquid-cooled racks at 40kW each. Total Q = 400kW; with 15% margin = 460kW. Secondary ΔT = 5°C. Secondary flow m = 460/(4.18×5) ≈ 22 kg/s ≈ 79 m³/h; with 10% piping margin ≈ 87 m³/h. Select two KC-CDU300 units in parallel (each ~52 m³/h, total 104 m³/h, N+1). Primary ΔT = 6°C; primary flow ≈ 66 m³/h; pipe DN100-DN125 at 1.5-2.5 m/s. Pump head must overcome cold plate (0.5-1.5 bar), hose/QD (0.3 bar), manifold (0.2 bar), headers (0.3 bar), filter (0.2 bar), exchanger (0.3 bar) ≈ 1.8-2.8 bar = 18-28 m; KC-CDU300 head 20m with VFD control. LMTD ≈ 22°C; required area A = 460000/(4000×22) ≈ 5.2 m².

14. Safety

14.1 Electrical

Lockout/tagout before service. Wait for VFD capacitor discharge. Licensed electricians only. Reliable grounding.

14.2 Pressurized Piping

Isolate and depressurize before disconnecting. Beware hot return water (~40°C). Use drip pans under QD disconnection.

14.3 Chemicals

Wear gloves/goggles with glycol and inhibitors. Dispose coolant per local environmental rules.

14.4 Leak Response

On leak alarm, locate the source; isolate the branch; orderly shut down affected servers; dry the area; test insulation before re-energizing.

15. Delivery, Training, After-Sales

15.1 Factory Acceptance

Each CDU undergoes visual, pressure (1.5× WP, 30 min), insulation, PLC download, sensor calibration, touchscreen, pump run, and alarm interlock tests. Reports ship with the unit.

15.2 Site Service

Guangzhou Laian engineers provide rigging supervision, water/electrical hookup inspection, fill/flushing, commissioning, and 72h witness runs.

15.3 Training

Operators receive training on structure, HMI, daily inspection, alarms, filter replacement, coolant sampling, and emergency shutdown.

15.4 Warranty and Spares

Standard warranty 12 months from acceptance (extendable). Recommended spares: filter elements, gaskets, sensors, pump mechanical seals, fuses, QD cartridges, EPDM hoses.

16. Project Workflow

KITOZER projects follow a standard workflow: requirements gathering (rack count, per-rack power, primary conditions, power, redundancy, monitoring, environment); design (selection, hydronic calc, interfaces, layout); manufacturing (sheet metal, welding, assembly, wiring, FAT); shipping and rigging; flushing/fill/commissioning; 72h trial and acceptance. This ensures traceable, quality-controlled delivery.

17. Glossary

Term Meaning
CDU Coolant Distribution Unit
Primary loop Facility side connected to chiller/dry cooler
Secondary loop Equipment side connected to cold plates
Cold plate Metal plate mounted on chips to absorb heat
Manifold Rack supply/return distribution header
QD Drip-free quick disconnect
ΔT Supply-return temperature difference
Free cooling Using outdoor ambient to cool without compressors
PUE Power Usage Effectiveness
TDP Thermal Design Power

18. Common Design Pitfalls

Common pitfalls include: ignoring hydronic balancing (near/far rack flow imbalance); using tap water on secondary; selecting CDU without verifying primary supply temperature; sizing pumps by flow only and neglecting head; omitting leak detection; and not reserving expansion margin. KITOZER engineers flag these during design review.

19. Monitoring Integration

KITOZER CDUs expose data points over Modbus TCP, BACnet/IP, and SNMP: temperatures (secondary supply/return, primary supply/return, optional rack branches), pressures and ΔP, flow, pump status/VFD frequency, control valve position, water quality (conductivity/pH/glycol optional), alarms (E-stop, over temp, low flow, filter ΔP, leak, pump fault, comm loss), and accumulated run time/energy/makeup water. KITOZER recommends three-tier alarming: critical (leak, over temp, pump fault) for immediate response; major (filter ΔP, conductivity, pump switch) for same-shift; advisory (sensor drift, maintenance due) for work orders. Long-term trends reveal seasonal primary temperature, growing rack load, and filter clogging speed.

20. Energy Efficiency Analysis

Traditional air cooling chains rack fans to room AC to chiller to cooling tower, stacking fan/pump energy. Liquid cooling removes heat directly from chips to CDU to primary, eliminating rack fan and room AC fan energy. VFD pump power scales roughly with flow cubed; at 50% load, pump power can drop to ~12.5%. Secondary pump plant typically consumes 1-2% of heat duty. With free cooling, dry coolers bypass compressors in cold seasons. For a 1MW IT site, PUE improvement from 1.6 to 1.2 saves ~3.5 GWh/year; at $0.10/kWh, ~$350k/year, paying back the liquid cooling premium in 4-6 years.

21. Piping Materials

Material Pros Cons Use
316L stainless Corrosion resistant, strong Skilled welding, costly Secondary main, CDU internal
Galvanized steel Cheap Zinc corrosion contaminates Non-critical primary only
Carbon steel seamless Strong Requires corrosion treatment Primary main
EPDM hose Flexible, vibration isolation Finite life Server to manifold
Nylon/PTFE hose Chemical resistant, light Costly Small secondary branches

Flange CDU connections; QD rack connections; threaded/flanged valves; argon-arc welded seams; glycol-compatible seals. Color-code supply (blue) and return (green/red) lines; tag branches by rack.

22. Flushing and Fill Procedure

Replace precision filters with temporary high-flow plates; drain to floor. Flush at 1.5× design flow for 24-48h until return water is clear. Test paper clarity. Flush each branch by opening valves. Drain, then double-displace with DI water before final coolant. Prime pumps; run 24h; sample conductivity and particulate.

23. Acceptance Checklist

Pressure test (1.5× WP, 30 min, ≤0.2 bar drop); electrical (insulation ≥1MΩ, ground ≤1Ω, correct phasing, pump rotation, E-stop); functional (pump switchover, temperature control, alarm simulation); 72-hour continuous run under design load with bi-hourly logged data.

24. Spare Parts List

Spare Stock Replacement
Secondary filter element 2 sets Annual or on ΔP alarm
Plate exchanger gaskets 1 set Biennial inspection
PT1000 sensor 2 pcs On failure
Pressure transmitter 1 pc On failure
Pump mechanical seal 1 set On leak
QD cartridge Several After dozens of cycles
EPDM hose 1 common set Every 3-5 years

25. Shipping and Storage

CDUs ship in wooden crates with moisture and shock protection. Keep upright, tilt ≤15°. Store in dry, -10 to 40°C, RH ≤80% environment. Power monthly during long storage to prevent moisture. Verify packing list, nameplate, and shipping damage on uncrating; remove transport bolts only after leveling.

26. Environmental and Green Data Centers

Liquid cooling lowers electricity and indirect carbon emissions. Closed-loop systems reduce water use; dry cooler integration can achieve near-zero water consumption in suitable climates. Modular serviceability reduces waste; metals and coolants are recyclable. KITOZER CDUs align with green data center lifecycle goals.

27. Operating Procedures

27.1 Pre-Start Check

Verify expansion tank pressure 0.8-1.5 bar; makeup tank level ≥1/2; primary and secondary isolation valves open; branch balancing valves at design position; no active alarms; breakers on.

27.2 Cold Start

Energize control power; jog pump 1 at manual; ramp to 30 Hz; check leaks; open primary control valve to 10%; switch to auto; set supply temp (e.g., 35°C) and ΔP (e.g., 2.0 bar); observe 30 min; open branch valves by rack.

27.3 Normal Shutdown

Coordinate IT workload shutdown; wait for return temp below 30°C; stop secondary pumps; close primary valves; keep control power on for heating.

27.4 Emergency Stop

Press E-stop on leak, fire, or abnormal noise; pumps and valve de-energize; primary valve closes. Resolve hazard, then restart per pre-start checklist.

28. Fault Code Table

Code Meaning Action
E001 Secondary supply over temp Check primary temp and valve
E002 Secondary return over temp Check load and pump flow
E003 Secondary low flow Check VFD, valves, filter
E004 Low ΔP Check pump speed, check valve
E005 High ΔP Check closed branch, blockage
E006 Filter ΔP high Clean/replace element
E007 Pump 1 fault Switch to pump 2; inspect
E008 Pump 2 fault Switch to pump 1; inspect
E009 Tank low pressure Check N2 precharge and makeup
E010 Base leak alarm Investigate on site
E011 Conductivity high Sample and plan change
E012 Primary low flow Check chiller and valves
E013 Comms loss Check Ethernet/switch
E014 E-stop active Reset after hazard resolved

29. Industry Applications Deep Dive

29.1 AI Large Model Training

Thousands of accelerators draw dynamic loads; KITOZER CDUs must stabilize supply temperature within tens of seconds, provide N+1 or 2N redundancy, and stream data to central operations.

29.2 Autonomous Driving Simulation and Render Farms

GPU loads vary with job scheduling; VFD pump savings are prominent. CDU can anticipate load changes from scheduler data.

29.3 Scientific Computing and Weather

Multi-week continuous runs demand uninterrupted cooling; redundant KITOZER CDUs meet 24/7 needs.

29.4 Energy Storage

Battery clusters need 25-35°C control within ±2°C. Outdoor-rated KITOZER CDUs handle vibration and wide ambient.

29.5 5G Edge

Small KITOZER CDUs pack more compute into edge rooms with remote monitoring.

30. Compatibility with Servers and Cabinets

KITOZER CDUs follow industry-standard interfaces. Rack manifolds mount vertically with supply/return QDs; servers connect via hoses. KITOZER engineers confirm QD form factors with server vendors and provide adapters when needed. Primary flanges mate to standard chiller outlets; control valves sequence with chiller plant via BMS.

31. Plate Exchanger Fouling and Cleaning

Primary-side water treatment prevents calcium scaling; secondary-side water quality controls corrosion products. Monitor exchanger ΔP and approach. Light fouling can be cleaned by chemical circulation; heavy fouling requires gasketed plate disassembly and individual brushing. Replace aged gaskets on reassembly.

32. Investment Payback

For a 1MW IT site, incremental liquid cooling investment includes CDU units (~$85k-130k equivalent per 100kW class), rack cold plates and manifolds, secondary piping and QDs, monitoring integration. Annual energy savings from PUE 1.6 to 1.2 (~3.5 GWh) at $0.10/kWh ≈ $350k. Plus reduced HVAC capacity and higher rack density, simple payback typically 4-6 years.

33. Standards

KITOZER CDUs are designed with reference to data center design codes, plate exchanger safety, industrial pump efficiency, electrical safety, seismic anchoring, and noise control standards. Export projects can be supported for CE/UL documentation per destination requirements.

34. KITOZER Service System

Guangzhou Laian Intelligent System Development Co., Ltd. is based at Chaotian Park, Zhongrun Industrial Zone, No. 5 Huashan Road, Shilou, Panyu, Guangzhou. KITOZER offers end-to-end service from design, manufacturing, FAT, site commissioning to O&M training. Reach us at +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140. Chinese customers: www.lain.com.cn; international customers: www.gdlain.com. Technical response within 2 business hours; preliminary proposal within 2 business days.

35. Additional FAQ

Q: Does the secondary pressure fluctuate?

A: Small fluctuations occur during QD plug/unplug; expansion tank and VFD absorb them to within ±0.2 bar steady state.

Q: Does secondary piping need insulation?

A: Insulate if supply temperature could drop below room dew point to prevent condensation.

Q: Can CDUs run in parallel?

A: Yes. Multiple KITOZER CDUs share a secondary ring with group control for load sharing and maintenance isolation.

Q: Do servers need special room flooring?

A: Verify floor loading for CDU weight; route secondary piping under raised floor or overhead.

Q: What about server replacement?

A: QD shutoffs let you disconnect hoses and slide servers out without shutting the row.

Q: Can KITOZER CDU be remotely upgraded?

A: PLC firmware upgrades over Ethernet; touchscreen firmware via USB or network. Backup parameters first.

Q: Winter freeze protection?

A: Glycol concentration handles it; for DI water systems in unheated rooms, drain or trace-heat on shutdown.

Q: Is annual inspection required?

A: Recommended yearly preventive maintenance by KITOZER or authorized service: filter, calibration, exchanger, terminals, seals.

Q: Can primary use closed-circuit cooling tower?

A: Yes, if its capacity exceeds CDU duty. KITOZER interfaces are compatible.

Q: Can electrical switchgear sit next to a CDU?

A: Keep distance or add a drip curb; CDU cabinets are IP54 but water proximity requires care.

36. Future Evolution

Higher supply temperatures (35-45°C) extend free cooling; KITOZER supports 18-50°C. Deeper server-cold-plate integration will standardize rack interfaces. Predictive maintenance, edge analytics on pump health and filter life, and integrated CDU+power cabinets are on the KITOZER roadmap.

37. Selection Checklist

Category Data Needed
Heat load Rack count, per-rack power, component list, expansion plan
Secondary Target supply temp, allowable ΔT, cold plate resistance, hose length
Primary Supply/return temp, available flow, pressure, interface location
Site Room size, floor loading, pipe entry, power capacity
Redundancy Availability target, N+1 or 2N, dual power
Monitoring DCIM/BMS protocol, points, alarm routing
Environment Ambient range, noise limits, indoor/outdoor
Water quality Primary water report, preferred secondary medium

38. Field Scenarios

Scenario A: New AI center with 20 racks at 80kW each; three KC-CDU300 in parallel ring; primary from chillers plus dry coolers; 32°C supply, 8°C ΔT; PUE ~1.18. Scenario B: Retrofit of an existing room adding a KC-CDU150 for GPU nodes, tying into existing chilled water, with business continuity. Scenario C: Outdoor energy storage station using an outdoor-rated CDU with closed-circuit cooling tower.

39. Commissioning Pitfalls

Common commissioning issues: pump cavitation from trapped air; unstable ΔP from unbalanced valves; high branch temperature from low branch flow or poor cold plate mounting; intermittent comms from loose Ethernet. KITOZER commissioning checklists resolve these systematically.

40. KITOZER Differentiation

KITOZER differentiates via fast local service from the Guangzhou factory, modular customization, competitive pricing with brand-name core components, and the ability to deliver CDU, cold plates, manifolds, and monitoring as one integrated package.

41. About This Guide

This guide is prepared by the KITOZER Engineering Team for engineers, procurement, and O&M staff. It reflects KITOZER KC-CDU series design and field experience. Specifications may change; refer to the latest publication by Guangzhou Laian Intelligent System Development Co., Ltd. Reference prices are budgetary only. Contact us for formal proposals.

42. Detailed Component Engineering

The overall performance of a liquid cooling CDU depends on the careful selection and integration of every component. This section expands on the engineering rationale behind the major parts inside a KITOZER CDU, helping specifiers and maintenance engineers understand what they are buying and what to inspect during acceptance and service.

42.1 Plate Heat Exchanger Details

Plate heat exchangers are made by stacking thin corrugated metal plates between frame plates. The chevron pattern on each plate promotes turbulence even at low Reynolds numbers, which both raises the heat transfer coefficient and discourages fouling. KITOZER uses brazed plate heat exchangers on smaller skids because they are hermetically sealed, compact, and require almost no maintenance. On larger skids, gasketed plate exchangers allow the frame to be unbolted so plates can be lifted out for inspection, washing, or replacement. The plate material is uniformly 316L stainless steel, which resists chloride pitting better than 304 in chilled water loops. The EPDM gasket is rated for continuous service up to about one hundred twenty degrees Celsius and is compatible with both water and inhibited ethylene glycol.

The design of a plate exchanger is a trade-off between approach temperature and pressure drop. A smaller approach means the secondary supply can be cooler relative to the primary return, which is good for chip temperature, but it requires more plates and therefore a larger, more expensive exchanger. KITOZER engineering typically selects an approach of two to four degrees Celsius as the balance point for most data center projects. The number of plates can be increased later by opening the frame, so the skid has some headroom if future loads grow.

42.2 Pump Hydraulics

The secondary circulation pump is the only continuously running rotating machine in the CDU. KITOZER specifies high-efficiency vertical inline centrifugal pumps with IE3 premium efficiency motors and variable frequency drives. The pump curve is selected so the design operating point sits near the best efficiency point, which extends mechanical seal life and minimizes vibration. Each pump is isolated from the skid frame by flexible stainless steel bellows on suction and discharge sides, and a spring check valve on discharge prevents reverse rotation of the standby pump when the duty pump runs. Pressure gauges on both sides of each pump give operators an immediate visual check of pump health.

Pump redundancy is arranged as duty and standby with automatic rotation. The PLC alternates which pump is duty based on cumulative runtime, so both units wear evenly. If the duty pump reports an overload, underload, or drive fault, the PLC stops the faulty pump and starts the standby within three to five seconds. A small diaphragm accumulator on the discharge line absorbs the brief pressure transient during switchover so servers do not see a flow interruption.

42.3 Expansion and Makeup

The expansion tank is a diaphragm type with a nitrogen-precharged side. The precharge pressure is set slightly below the minimum operating pressure of the system so the bladder separates gas from liquid under normal conditions. When the secondary fluid warms and expands, excess volume enters the bladder side and compresses the nitrogen. When the fluid cools or a small leak develops, the nitrogen pushes fluid back into the loop. KITOZER also includes a small automatic makeup pump drawing from a dedicated makeup tank. If system pressure falls below the low setpoint, the makeup pump starts and tops up the loop; a solenoid and check valve prevent backflow into the building water supply.

42.4 Filtration Strategy

Secondary loop filtration is staged. The primary protection is a basket strainer with fifty to one hundred micrometer mesh located in the secondary return upstream of the pumps. A differential pressure switch across the strainer triggers a local light and remote alarm when the mesh loads up. For mission-critical sites, KITOZER offers a duplex strainer arrangement where two baskets are plumbed in parallel with three-way valves, allowing operators to isolate one basket for cleaning while the other remains online. This avoids shutdown during filter service.

42.5 Instrumentation Philosophy

Every temperature point uses a PT1000 Class A element housed in a thermowell for replaceability without draining the loop. Pressure transmitters are four to twenty milliamp devices with stainless steel diaphragms, installed with isolation valves so they can be swapped without shutdown. The secondary main flow is measured by either an electromagnetic flowmeter (for conductive water/glycol) or an ultrasonic clamp-on meter as a non-invasive option. Conductivity and pH probes are optional accessories mounted in a small bypass loop so they can be isolated and calibrated without disturbing main flow.

42.6 Electrical Architecture

The control cabinet is a floor-standing IP54 enclosure with a glazed door for touchscreen visibility. Inside, power and control circuits are separated: main contactors and VFDs occupy the lower cable alley, while PLC, power supply, and terminal blocks occupy the upper section. A small fan with filter vents the cabinet, and a dew-point heater prevents internal condensation in cold climates. All external cables enter through bottom cable glands and are numbered to match the wiring diagram. The PLC program is backed up to a removable SD card so it can be restored quickly after a CPU replacement.

43. Detailed Design Calculations

This chapter walks through a more complete worked example so readers can mirror the approach on their own projects. The sample project is a new AI compute hall with twelve liquid-cooled racks. Each rack is designed for sixty kilowatts of heat, of which fifty kilowatts is removed by cold plates and the remaining ten kilowatts is handled by rear-door air cooling. The secondary supply target is thirty-five degrees Celsius, and the return target is forty-two degrees Celsius, giving a seven degree Celsius delta T. The primary side is supplied by a central chiller at twelve degrees Celsius with a permitted return of nineteen degrees Celsius.

43.1 Secondary Flow

The total liquid-cooled heat load is twelve racks times fifty kilowatts, or six hundred kilowatts. Adding twenty percent redundancy gives a design duty of seven hundred twenty kilowatts. Using Q equals m c delta T, with c equal to four point one eight kilojoule per kilogram per Kelvin and delta T equal to seven Kelvin, the required mass flow is seven hundred twenty divided by four point one eight times seven, which is about twenty-four point six kilograms per second. At water density, this is roughly eighty eight point five cubic meters per hour. Accounting for piping margin, the selected secondary flow is about one hundred cubic meters per hour. Two KITOZER KC-CDU300 skids in parallel, each rated at about fifty two cubic meters per hour, deliver the required flow with one unit on standby.

43.2 Primary Flow

The primary delta T is seven degrees Celsius as well, from twelve to nineteen. Primary mass flow is seven hundred twenty divided by four point one eight times seven, again about twenty four point six kilograms per second, or about eighty eight cubic meters per hour. Primary piping is sized for one point eight to two point five meters per second, which lands near DN one hundred twenty five.

43.3 Pump Head Budget

The secondary pump must overcome: cold plate resistance per node at roughly zero point eight to one bar; hose and quick disconnect losses around zero point three bar; rack manifold losses around zero point two bar; header friction estimated at zero point three bar over the loop; filter loss around zero point two bar; and heat exchanger secondary channel loss around zero point three bar. The sum is roughly two point one to two point three bar, or twenty one to twenty three meters of head. The KC-CDU300 pump at twenty meters of head is adequate when running under variable pressure differential control; the VFD automatically trims speed to maintain the target differential.

43.4 Exchanger Sizing

The log mean temperature difference is calculated from the four corner temperatures: secondary return forty two versus primary supply twelve gives thirty degrees; secondary supply thirty five versus primary return nineteen gives sixteen degrees. The log mean temperature difference is about twenty two degrees. With a typical overall heat transfer coefficient of four thousand watts per square meter per Kelvin, required area is seven hundred twenty thousand divided by four thousand times twenty two, which is about eight point two square meters. KITOZER supplies the KC-CDU300 with an exchanger area above this number, leaving margin for future fouling and load growth.

44. Primary Cooling Source Selection

The CDU does not produce cooling on its own; it relies on a primary source. The choice of primary source has a major effect on annual energy use and water consumption.

44.1 Centrifugal Chillers

Large data centers use centrifugal chillers producing seven to twelve degree Celsius chilled water. The low supply temperature maximizes the approach inside the CDU and supports high-density cold plate cooling. The trade-off is compressor energy, especially in warm months.

44.2 Dry Coolers

Dry coolers reject heat directly to ambient air without a compressor. In cool seasons they carry the entire load; in warm seasons chillers top up. Dry cooler plants have high annual free-cooling hours but require outdoor footprint and fan power.

44.3 Closed Circuit Cooling Towers

In closed circuit towers, process water stays inside coils while spray water evaporates outside. This keeps process water clean while leveraging evaporative cooling. They use less water than open towers but more than dry coolers.

44.4 Matching Strategy

KITOZER engineering models the annual operating curve of each candidate source against the CDU secondary requirement. The result is a recommended combination, for example dry coolers for nine months and chillers for three months, which minimizes annual energy and water use.

45. Noise and Vibration Control

Even though liquid cooling is quieter than air cooling, the CDU itself contains pumps and fans and must be treated carefully. KITOZER mounts pumps on a common base with spring isolators, uses flexible bellows at pump connections, and installs the skid on spring isolation pads. The control cabinet cooling fan uses a low-speed EC fan with a vent silencer. For noise-sensitive rooms, KITOZER offers an optional acoustic enclosure that reduces sound pressure level by another five to eight decibels. Piping supports use spring hangers that do not transmit vibration to the building structure.

46. Electrical and Power Coordination

Liquid cooling retrofits often raise rack power density, which forces a re-evaluation of the electrical distribution. The CDU itself draws relatively little power compared with the chillers and dry coolers it serves, but its control power and standby pumps must ride through brief mains interruptions. KITOZER recommends feeding the control cabinet from UPS and arranging pump feeds so that at least one pump remains available on the UPS-backed bus. The electrical contractor coordinates breaker sizes, cable sizes, and grounding with the one-line diagram KITOZER provides.

47. More FAQ

Q: Can the secondary loop use tap water after flushing?

A: No. Tap water contains chloride and hardness that will corrode stainless steel and foul microchannels over months. Always use deionized water or inhibited glycol and monitor water quality.

Q: What happens if primary water is lost?

A: The secondary supply temperature rises. KITOZER CDUs alarm at user-configured thresholds and coordinate with the chiller plant via BMS. A primary flow switch is recommended for automatic interlock.

Q: Can the CDU be installed outdoors?

A: Standard units are indoor only. Outdoor-rated variants include weather canopy, insulation, winter trace heating, and sun shading for ambient minus twenty to plus forty five degrees Celsius.

Q: How often should secondary fluid be changed?

A: DI water systems typically change every one to two years; inhibited glycol systems are sampled quarterly and topped up. Follow lab results.

Q: How does the CDU sequence with the chiller?

A: Through the BMS. The CDU modulates its primary-side control valve, changing the return temperature seen by the chiller, which then loads or unloads automatically.

Q: Can one CDU serve both cold plate and immersion racks?

A: Yes, as long as temperature and flow requirements are compatible. Each end uses its own balancing valve.

Q: How is noise measured?

At one meter from the unit and one point two meters above floor, under full load. KITOZER CDUs are around sixty two decibels A-weighted; detailed spectra are available on request.

Q: Can liquid cooling coexist with fresh air or air-side economization?

A: Yes. Liquid handles the main heat load; the air system backs up and cools components without cold plates.

Q: Can customers visit KITOZER?

A: Yes. The Guangzhou Panyu facility welcomes scheduled visits. Contact +86 13922289957 to arrange.

Q: The touchscreen shows comms fault, what now?

A: Check Ethernet cables, switch port LEDs, and whether the BMS is online. Physical links usually restore communication automatically; if not, cycle control power.

Q: Is the secondary pressurized positive or negative?

A: Slightly positive relative to atmosphere so that a breach draws in air rather than spraying coolant.

Q: What glycol concentration for freeze protection?

A: Twenty five percent for near-zero environments; thirty to forty percent for outdoor or unheated spaces. Higher concentration raises viscosity and pump power.

Q: Can filter elements be changed online?

A: Standard basket strainers require isolation; duplex strainers allow online switchover.

Q: Does KITOZER offer turnkey liquid cooling?

A: Yes, Guangzhou Laian supplies CDU, cold plates, manifolds, hoses, QDs, and monitoring as one package.

48. Extended Monitoring Points

Beyond the basic points already listed, KITOZER CDUs can be equipped with optional sensors that add diagnostic depth. A differential pressure sensor across each rack manifold can detect a partially blocked branch early. A vibration sensor on each pump alerts to bearing wear before failure. A motor winding temperature sensor on each pump provides early warning of overload. A humidity sensor in the electrical cabinet flags condensation risk. A digital power meter on the main feed logs energy use for PUE reporting. All optional points map into the same Modbus or BACnet address table, so the DCIM sees one coherent data model.

49. Commissioning Deep Dive

Commissioning is where design meets reality. KITOZER commissioning engineers follow a structured sequence. First, they verify that all field piping is complete, pressure tested, and flushed. Second, they fill the secondary loop with the specified coolant and vent every high point. Third, they start one pump at low speed and watch for leaks, unusual noise, and pressure response. Fourth, they ramp to normal operating pressure and set the automatic controls. Fifth, they balance each rack branch by measuring flow and adjusting balancing valves. Sixth, they exercise all alarms by simulating sensor inputs. Finally, they run the skid under realistic load for seventy two hours and hand over a signed commissioning report.

The most common commissioning issues are trapped air causing pump noise, unbalanced valves causing hot racks, and over-tightened QDs causing slow flow. KITOZER checklists call out these items explicitly so they are resolved during the punch list rather than after handover.

50. Long-Term Operations Strategy

Once a liquid cooling system is in service, the O&M strategy shifts from reactive repair to preventive and predictive maintenance. KITOZER recommends quarterly coolant sampling, annual filter replacement, biennial plate exchanger inspection, and continuous monitoring of pressure, temperature, and flow trends. Trend analysis reveals fouling before it becomes a trip, and reveals load growth before it becomes a capacity problem. For multi-tenant or multi-hall data centers, KITOZER can aggregate CDU data into a central dashboard so operators compare performance across halls and benchmark energy use.

51. Sustainability and Water Use

Water use is increasingly scrutinized in data center siting. Closed secondary loops lose almost no water; the only evaporation occurs at the outdoor cooling source. By choosing dry coolers for most of the year and cooling towers only on peak days, KITOZER-supported projects can achieve very low water use per IT kilowatt. In water-stressed regions, an all-dry-cooler arrangement with modest chiller backup is often the preferred strategy. The KITOZER CDU architecture supports either approach without modification.

52. Conclusion

The KITOZER Liquid Cooling CDU is a carefully engineered package that combines plate heat exchange, variable pumping, water treatment, control, and monitoring into a single skid. By isolating the server side from the facility side, pressurizing the loop for leak safety, and modulating pumps for energy efficiency, it enables the high rack densities that modern AI and HPC workloads demand. Guangzhou Laian Intelligent System Development Co., Ltd. stands behind every unit with local engineering support, spare parts, and training. For selection, quotation, or site survey, contact KITOZER Engineering at +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140, or visit www.gdlain.com and www.lain.com.cn.

53. Secondary Loop Hydronic Design Deep Dive

The secondary loop is the vascular system between the CDU and the servers. This chapter goes deeper into hydronic design choices that determine whether the system performs as modeled.

53.1 Setpoint Location

The pressure maintenance point should be on the secondary return main, near the pump suction. Keeping the setpoint there ensures the entire loop sees positive pressure under all load conditions, avoiding cavitation at the pump and air ingestion at high points. KITOZER connects the expansion tank and makeup pump to the return main by default.

53.2 Air Removal

Air in a closed loop causes noise, flow instability, and localized corrosion. Automatic air vents are installed at every high point, and the CDU itself has a vent on top of the heat exchanger. During initial fill, operators manually vent each rack riser. After stabilization, the automatic vents handle small amounts of entrained air.

53.3 Water Hammer

Rapid pump trips or fast valve closures generate pressure transients. KITOZER uses slow-closing check valves on pump discharge, modulating control valves with travel times above thirty seconds, and optional water hammer arrestors on long mains.

53.4 Loop Volume and Expansion

Total secondary loop volume includes the CDU, mains, rack manifolds, cold plates, and hoses. Thermal expansion from twenty to forty degrees Celsius is roughly zero point five to one percent of volume. The expansion tank is sized to absorb this plus operating pressure margin. KITOZER recalculates tank size based on the actual loop volume provided by the customer.

54. Coolant Chemistry in Practice

Coolant selection is not just about anti-freeze. The secondary fluid contacts copper cold plates, stainless steel tubes, EPDM seals, and aluminum manifolds simultaneously, so it must be compatible with all of them.

54.1 Deionized Water

DI water has excellent heat transfer but is aggressively corrosive because it seeks ions. A properly designed DI loop includes corrosion inhibitors and continuous conductivity monitoring. If conductivity rises above ten microsiemens per centimeter, the fluid is suspect.

54.2 Inhibited Glycol

Automotive antifreeze is not the same as industrial inhibited glycol. Automotive products contain silicates that foul microchannels; KITOZER specifies industrial-grade inhibited glycol formulated for aluminum and copper systems. Concentration is measured by refractive index each quarter.

54.3 Dielectric Fluids

For immersion or leak-sensitive sites, dielectric fluids such as synthetic hydrocarbons or engineered fluorinated fluids are used. They cost more and have lower specific heat, so KITOZER resizes pumps and exchangers accordingly.

54.4 Monitoring Regime

Quarterly lab analysis covers conductivity, pH, chloride, glycol concentration, and visual particulate. Annually, a fuller analysis includes metals, bacteria, and inhibitor residual. Results drive either top-up or full change-out.

55. Rack Manifolds and Quick Disconnects

The rack manifold is the vertical supply and return header inside each rack. KITOZER manifolds are typically stainless steel or anodized aluminum, with one pair of supply and return QDs per server slot. QDs are flat-face dry-break style: when disconnected, poppets close on both sides so only a few drops spill. The manifold is mounted at the rear or side of the rack, and color-coded hoses connect to server cold plates.

Manifolds are pressure tested at the factory and shipped with protective caps. On site, they mount to the rack rail and connect to the room-level secondary loop via flexible hoses with isolation ball valves. Each branch includes a balancing valve and optional flow indicator for commissioning and troubleshooting.

56. Retrofit Strategy for Existing Rooms

Many data centers want to add liquid cooling without shutting down IT. KITOZER supports a phased retrofit: first install the CDU and secondary main during a planned maintenance window; then convert one rack at a time, balancing load between air and liquid; finally retire room CRAC units as liquid coverage grows. The key is to size the new primary water take-off carefully so the existing chiller plant can absorb the additional load without compromising cooling for the air-cooled halls.

57. Project Delivery Artifacts

KITOZER ships each CDU with a documented set of artifacts: factory acceptance test report, nameplate certificate, operation and maintenance manual, electrical schematic, hydraulic P&ID, recommended spares list, PLC point list for integration, and foundation drawing. These documents are also provided electronically for inclusion in the project handover package.

58. Warranty and Spare Parts Strategy

Standard warranty is twelve months from acceptance. KITOZER recommends customers stock consumables locally: filter elements, gaskets, PT1000 sensors, pressure transmitters, pump mechanical seals, fuses, QD cartridges, and common EPDM hoses. Long-lead items such as VFDs and PLCs are held at the Guangzhou factory and shipped within forty eight hours on demand. Annual preventive maintenance visits keep the system in warranty condition and catch small issues before they become outages.

59. More Engineering FAQ

Q: Does the secondary loop need insulation?

A: Insulate only if supply temperature may drop below room dew point to prevent condensation on pipe surfaces.

Q: Can multiple CDUs share a secondary ring?

A: Yes. KITOZER group control allows parallel units to share load and isolate for maintenance.

Q: How much coolant does a typical project need?

A: A ten-rack installation needs roughly five hundred to one thousand liters of secondary fluid; KITOZER calculates the exact volume during design.

Q: Can the touchscreen be accessed remotely?

A: Via the local network with a secure VPN; web or client access mirrors the local HMI.

Q: Is online water quality monitoring available?

A: Yes, optional conductivity and pH probes transmit to DCIM.

Q: Can seawater be used on the primary side?

A: No, chloride attacks 316L. Use treated fresh water or dedicated industrial coolant.

Q: Can customers request non-standard dimensions?

A: Yes; custom footprint, ports, color, and nameplate are supported with a lead time extension.

Q: Is fire protection compatible?

A: Yes. Liquid-cooled racks still follow data center gas or water mist suppression codes. Leak detection is independent.

Q: How long does a typical project take?

A: A medium project takes three to four months; a large hall takes six to twelve months.

Q: Does KITOZER provide factory witness testing?

A: Yes, customers may witness FAT at the Guangzhou factory before shipment.

60. Final Notes

The KITOZER Liquid Cooling CDU is more than a metal box with pumps; it is the thermal heart of a modern liquid-cooled data center. Selecting the right capacity, arranging proper redundancy, designing a clean secondary loop, and maintaining water discipline over years of operation are what separate a trouble-free liquid cooling installation from one plagued by leaks, fouling, and unexpected downtime. Guangzhou Laian Intelligent System Development Co., Ltd. brings decades of data center engineering experience to every KITOZER project. We invite engineers, procurement teams, and facility managers to engage with our technical team early in design so that the CDU, manifolds, cold plates, and plant are optimized as a single system rather than as disconnected components. Contact KITOZER today at +86 13922289957 or via www.gdlain.com to discuss your project.

61. KITOZER CDU Product Family

Beyond the standard KC-CDU30 to KC-CDU600 line, KITOZER offers several derivative models for specialized needs.

61.1 Compact Rack-Mounted CDU

For edge rooms and small HPC labs, KITOZER builds CDUs that fit inside a standard nineteen-inch rack, delivering five to twenty kilowatts of cooling in four to eight rack units. These compact units integrate pump, exchanger, and controller and are ideal for single-rack liquid cooling retrofits where floor space is unavailable.

61.2 High-Head CDU

When the CDU sits far from the racks or when cold plates are particularly restrictive, KITOZER supplies a high-head variant with pump heads above thirty meters. This keeps secondary flow within design targets even across long hose runs.

61.3 Dual-Temperature CDU

Some facilities need both high-temperature return for free cooling and low-temperature supply for high-density chips. The dual-temperature CDU uses two plate exchangers to serve two secondary loops at different setpoints from one skid.

61.4 Outdoor-Rated CDU

For energy storage stations and outdoor base stations, the outdoor CDU adds weather canopy, insulation, and winter trace heating, rated for minus twenty to plus forty five degrees Celsius ambient.

62. Selection Mistakes to Avoid

KITOZER engineering sees the same selection mistakes repeat across projects. Listing them here helps specifiers avoid expensive rework.

62.1 Sizing by Current Load Only

Buying a CDU sized exactly to today’s IT load leaves no room for server refreshes. Chips gain power with each generation; reserve at least fifteen to twenty five percent.

62.2 Ignoring Primary Conditions

Specifying a CDU without checking primary supply temperature leads to impossible target temperatures. Always model the approach with the actual primary curve.

62.3 Underestimating Head

Cold plate microchannels, long hoses, and many QDs add up. Undersized pumps deliver low flow and hot chips.

62.4 Skipping Leak Detection

Leak detection is cheap insurance. Rope sensors under manifolds and a pan in the CDU catch small leaks before they become floods.

62.5 No Water Quality Plan

Filling the loop and forgetting about water quality leads to corrosion and fouling years later. Build in quarterly sampling from day one.

62.6 No Expansion Margin

Headers, exchanger area, and pump spares should all carry margin for future growth.

63. Transport, Rigging, and Unpacking

KITOZER CDUs ship in plywood crates with foam and desiccant. They must remain upright during transport; tilt beyond fifteen degrees can damage pump alignment. On site, riggers use the top lifting lugs only; lifting by piping is forbidden. After placement, the unit is leveled, spring isolators are seated, and shipping restraints on pumps and exchangers are removed. KITOZER commissioning engineers verify these steps before first fill.

64. Reading CDU Operating Data

Operators should know what the touchscreen numbers mean. Secondary supply temperature should hold within plus or minus one degree Celsius of setpoint. Supply-return delta T reflects current IT load; a rising delta T means rising load. Supply-return differential pressure should hold near setpoint; a falling pressure can indicate a stuck-open branch or a leak. Pump frequency trends upward if the loop is becoming restrictive. Filter differential rises gradually with normal loading but spikes suddenly if a release of debris occurs. Tank pressure that slowly decays signals a small leak the makeup pump is compensating for.

65. Green and Low-Carbon Operations

Liquid cooling reduces electricity-related carbon emissions by cutting cooling load. Closed loops also reduce water use. KITOZER supports customers reporting carbon and water metrics by providing energy and water consumption data points through the standard monitoring interface. Over the equipment lifecycle, modular serviceability also reduces replacement waste.

66. KITOZER Support Resources

KITOZER offers pre-sales design support, selection calculations, and site survey coordination. During the project, we provide factory documentation, installation guidance, and commissioning. After handover, we provide seven by twenty four phone support, remote diagnostics, on-site repair, and spare parts. The engineering team spans HVAC, electrical, controls, and fluid machinery so multi-discipline questions get one answer. Chinese customers reach us at www.lain.com.cn; international customers at www.gdlain.com.

67. Naming Convention

KITOZER CDU model numbers follow the pattern KC-CDU plus nominal kilowatts. Suffix letters denote configuration: S for single pump, D for dual pump redundancy, O for outdoor, H for high head, E for export version with English HMI and international certifications. Customers can specify the suffix directly when requesting a quote.

68. Final Word

Thank you for reading this KITOZER Liquid Cooling CDU guide. We have covered product overview, working principle, technical specifications, selection, installation, maintenance, FAQ, applications, trends, air cooling comparison, coolant chemistry, components, design calculations, safety, delivery, workflow, glossary, design pitfalls, monitoring, energy efficiency, piping, flushing, acceptance, spares, shipping, environmental impact, operating procedures, fault codes, industry applications, vendor coordination, exchanger cleaning, payback, standards, service, hydronics, primary sources, noise, electrical coordination, future outlook, selection checklist, field scenarios, commissioning, differentiation, and component engineering. We hope this guide serves as a practical reference for your next liquid cooling project. Contact KITOZER Engineering at +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140, or visit www.gdlain.com and www.lain.com.cn.

69. Heat Transfer Physics Behind Cold Plate CDU Systems

To understand why a CDU is sized the way it is, it helps to review the heat transfer chain from the silicon die to the outdoor air. Each thermal resistance in the chain contributes a temperature drop, and the CDU sits in the middle of that chain. Starting at the die, heat crosses the die-to-package interface, the package lid, the thermal interface material, the cold plate base, the microchannel walls, and finally the coolant film. From the coolant, heat travels through hoses, manifold, and header to the CDU, where it crosses the plate heat exchanger into the primary loop, then through the chiller or dry cooler to ambient air.

The CDU designer cannot change the die, package, or cold plate, but can influence the coolant-side resistances. Lower coolant temperature reduces the die temperature for the same heat flux. Higher flow rate reduces the convective resistance inside the cold plate but costs more pump power. Smaller approach in the plate exchanger reduces the gap between secondary supply and primary supply, but requires more plate area. KITOZER balances these trade-offs using standard reference data for server cold plates provided by server vendors.

70. Hydronic Balancing in Practice

Even a well-piped loop needs balancing. In a ring main, flow tends to favor the shortest path back to the CDU, leaving distant racks under-supplied. KITOZER commissioning engineers use a clamp-on ultrasonic flowmeter on each rack branch, adjust the balancing valve until each branch reaches design flow, and record the result. After balancing, a uniform secondary supply-return delta T across racks confirms that heat removal is even. This process usually takes one to two days for a twenty-rack hall.

71. Redundancy Architectures

Redundancy can be applied at several levels. Pump redundancy inside the CDU protects against pump failure. CDU redundancy across the hall protects against whole-skid failure. Primary loop redundancy protects against chiller or pipe failure. KITOZER recommends at least pump redundancy for any production installation, CDU parallel ring architecture for mission-critical halls, and dual primary mains for highest availability. The cost of redundancy is small relative to the cost of an hour of AI cluster downtime.

72. Cyber Security Considerations

Because CDUs are network-connected, they are part of the data center operational technology environment. KITOZER recommends placing the CDU control port on an isolated VLAN, using strong passwords, disabling unused services, and applying firmware updates only during maintenance windows. Remote access should be via VPN with multi-factor authentication. The PLC does not expose public services by default; customers are responsible for network segmentation policy.

73. Spare Parts Lead Times

Filter elements, gaskets, sensors, and fuses ship from Guangzhou within a week. Pumps and VFDs are normally in stock for standard models. Custom heat exchanger plate packs may require two to four weeks. KITOZER publishes a recommended spare list with each project so customers can stock the right items locally.

74. Commissioning Acceptance Tests

Acceptance tests include pressure test on secondary piping (one and a half times working pressure for thirty minutes), electrical insulation (greater than one megaohm), grounding (less than one ohm), pump rotation check, pump duty-standby switchover within five seconds, temperature control stability within plus or minus one degree, and simulated alarm signaling. A seventy two-hour continuous run under design load concludes commissioning.

75. More Technical FAQ

Q: How do I size expansion tank?

A: About five to eight percent of total secondary loop volume, sized for the thermal expansion between minimum and maximum operating temperature.

Q: Can I use stainless steel corrugated hoses?

A: Flexible EPDM or PTFE-lined hoses are standard for rack connections; corrugated metal hoses transmit vibration and are not preferred.

Q: What is the typical pressure at the cold plate inlet?

A: One to two bar gauge, depending on loop elevation and balancing.

Q: How often should the coolant be sampled?

A: Quarterly for the first year, semi-annually thereafter, unless results indicate otherwise.

Q: Can the CDU be connected to BACnet MS/TP?

A: Standard is BACnet/IP; MS/TP via a gateway is available as an option.

Q: Does KITOZER provide U.S. local support?

A: WhatsApp and email support are available; on-site U.S. support is arranged through authorized partners as needed.

Q: What is the expected service life?

A: Design life is fifteen to twenty years with regular maintenance; wet-end components such as gaskets and hoses are replaced on schedule.

Q: Can the CDU be retrofitted with additional pumps later?

A: Yes on modular models; the control cabinet and piping are designed for future pump addition.

76. Closing

This concludes the extended KITOZER Liquid Cooling CDU technical guide. We have covered the physics, hardware, controls, hydronics, chemistry, and service practices that make a liquid cooling installation reliable. Guangzhou Laian Intelligent System Development Co., Ltd. is ready to support your project from the first sizing conversation through long-term operations. Reach KITOZER Engineering at +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140, or via www.gdlain.com and www.lain.com.cn.

77. Detailed Commissioning Log Example

A typical commissioning log captures the following data at each step. Step one, pre-fill check: expansion tank pressure, makeup tank level, valve positions, and breaker states recorded. Step two, fill: volume of coolant added, time to fill, vent positions opened. Step three, first pump start: current, pressure, and vibration recorded at thirty, fifty, and sixty hertz. Step four, leak walk-down: every fitting inspected and signed. Step five, balancing: each branch flow measured and valve position recorded. Step six, seventy two-hour run: temperature, pressure, flow, and pump frequency logged every hour. Step seven, alarm tests: each alarm triggered and verified on HMI and remote. The signed log becomes part of the acceptance package.

78. Operational Modes

KITOZER CDUs support several operational modes. In normal mode, the PLC modulates pumps and control valve automatically. In service mode, the operator can force valves or pumps for maintenance while keeping alarms muted. In test mode, sensors and actuators can be exercised without running pumps. In emergency mode triggered by leak detection, the CDU closes isolation valves and alerts the BMS. Operators are trained on each mode during handover.

79. Integration with DCIM

Modern data centers use DCIM tools to correlate IT load with cooling. KITOZER CDUs publish supply/return temperatures, flow, and pump status over Modbus TCP. The DCIM can then display per-rack heat removal, compare cooling to IT power, and flag imbalance. Optional rack-level sensors extend this to individual branches. This data also feeds capacity planning: if rack temperatures trend upward, it indicates approaching CDU capacity.

80. Field Retrofitting a CDU into an Existing Room

Retrofit projects have unique constraints. The CDU must fit through existing doorways and elevators; primary water take-off must not starve existing air-cooled chillers; secondary piping must route around existing cable trays. KITOZER sends an engineer to survey the site, produces a routing drawing, and coordinates with the customer’s civil and electrical contractors. Retrofit projects often run on nights and weekends to avoid IT disruption.

81. Material Compatibility Table

Fluid Copper Stainless 316L Aluminum EPDM
DI water Good with inhibitor Excellent Good with inhibitor Excellent
25% glycol Good Excellent Good Excellent
Salt water Poor Fair Poor Fair
Mineral oil Excellent Excellent Excellent Poor
Synthetic dielectric Excellent Excellent Excellent Verify compatibility

KITOZER CDUs are configured with seals and gaskets matched to the selected fluid. Always confirm compatibility before filling with a new fluid type.

82. Performance Testing Standards

KITOZER CDUs are factory-tested against internal protocols based on heat exchanger and pump standards. Capacity is verified by measuring flow and temperature difference at design conditions. Pressure drop across the exchanger is recorded. Noise is measured in an anechoic bay. Electrical safety includes insulation and dielectric tests. Customers may witness factory acceptance tests before shipment.

83. More Q&A

Q: What is the typical lead time for a KC-CDU150?

A: Four to six weeks standard, eight to twelve weeks with custom options.

Q: Can KITOZER provide local language HMI?

A: English and Chinese are standard; other languages are available by request.

Q: How is condensate managed?

A: Secondary supply above dew point avoids condensation; otherwise insulated piping prevents it.

Q: Can the CDU run on backup generator?

A: Yes, provided generator capacity includes CDU and chiller loads. Control power should ride through on UPS.

Q: What is the minimum ambient for indoor units?

A: Ten degrees Celsius; below that the cabinet heater maintains internal conditions.

Q: Does KITOZER offer extended warranty?

A: Yes, up to five years with annual preventive maintenance contract.

Q: Can customers buy the CDU without the control panel?

A: The control panel is standard; a bare skid option is available for customers with their own PLC.

Q: How are spare pumps swapped?

A: Isolate the pump valves, drain locally, unbolt, replace, and vent; the running pump keeps the loop online.

84. Final Thank You

Thank you for reading the KITOZER Liquid Cooling CDU guide in full. We hope the detail provided here helps engineers, procurement teams, and operators make informed decisions. KITOZER is committed to supporting high-density data centers with reliable, efficient, and serviceable liquid cooling hardware. Contact us at +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140, or visit www.gdlain.com.

85. Detailed Pump Selection

Pump selection is more than reading a rated flow number. KITOZER engineers build a system curve from cold plate resistance, hose runs, manifold losses, filter, and exchanger. The intersection of the pump curve and system curve is the operating point. Selecting a pump whose best efficiency point lies near that intersection minimizes energy and extends seal life. Variable speed operation means the pump rarely runs at full speed, so motor temperature is lower and bearing life longer. For N+1 arrangements, each pump is sized to carry the full design duty alone, so standby pump is truly ready.

86. Plate Exchanger Sizing Detail

When a project requires an unusually small approach temperature, KITOZER may specify a gasketed plate exchanger with more plates. The additional plates increase area and reduce velocity, which lowers pressure drop but also reduces turbulence. The engineering trade-off is documented in the selection sheet. For high-temperature primary loops, plate material and gasket temperature rating must be reconfirmed.

87. Controls Sequence of Operation

The KITOZER control sequence is straightforward. On power-up, the PLC performs self-checks and reports any active alarms. In auto mode, it starts the lead pump after a pre-charge delay, ramps the VFD to maintain secondary differential pressure, and opens the primary control valve to hold secondary supply temperature setpoint. If lead pump fails, lag pump starts within seconds. If supply temperature rises above the alarm threshold, the PLC alerts the BMS and optionally triggers interlocks. On normal shutdown, pumps ramp down and the valve closes. Emergency stop kills power to pumps and valve actuator.

88. Water Treatment Cooperation

KITOZER recommends a qualified water treatment vendor for the primary loop. The vendor provides periodic testing and dosing of corrosion inhibitors, biocides, and scale inhibitors. On the secondary side, KITOZER supplies the initial coolant and recommended monitoring limits. Coordination between both water treatment vendors prevents cross-contamination issues.

89. Site Acceptance vs Factory Acceptance

Factory acceptance testing verifies the skid builds as designed. Site acceptance testing verifies the skid works in the installed system. FAT includes pressure, electrical, and pump run tests on the factory floor. SAT includes leak walk-down, balancing, alarm tests, and seventy two-hour run in the actual data center. KITOZER supports both.

90. Documentation Package

The KITOZER documentation package includes: certified dimensions, foundation plan, P&ID, electrical schematic, PLC I/O list, point list, O&M manual, spare parts list, test certificates, and as-built drawings after site work. All documents are delivered electronically in PDF and editable formats.

91. More Q&A

Q: Can KITOZER CDUs be networked into a centralized control room?

A: Yes, via Modbus TCP or BACnet/IP to the site SCADA.

Q: What is the typical lead time for spares?

A: Standard spares ship within a week from Guangzhou.

Q: Does the CDU require a dedicated operator?

A: No; autonomous operation with remote alarms means scheduled inspection is sufficient.

Q: Can the secondary loop be cleaned with chemicals?

A: Yes, with vendor-approved cleaners flushed out before refill.

Q: Are KITOZER CDUs suitable for tropical climates?

A: Yes; ambient up to thirty five degrees indoors, with appropriate chiller sizing.

Q: What is the expected MTBF of the pumps?

A: Tens of thousands of hours with proper maintenance.

Q: Can customers customize HMI graphics?

A: Basic customization is supported; full HMI redesign is available as a service.

Q: Does KITOZER provide commissioning as a service?

A: Yes, commissioning and operator training are included on request.

92. Final

This completes the extended KITOZER Liquid Cooling CDU guide. We have covered every major aspect from physics to service. Contact KITOZER Engineering at +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140, or visit www.gdlain.com and www.lain.com.cn for your project.

93. Lifecycle Cost Analysis

When evaluating a CDU purchase, lifecycle cost matters more than first price. The purchase price is only a fraction of total cost over fifteen years. Energy use during operation dominates: a variable-frequency pump plant at one to two percent of heat duty translates to meaningful savings versus fixed-speed pumps. Maintenance consumables such as filters and gaskets are small but recurring. Spare parts inventory ties up some capital but avoids downtime. KITOZER provides a lifecycle cost spreadsheet that compares CDU options over the project horizon, including energy, maintenance, and expected downtime cost.

94. Comparing KITOZER to International Brands

International CDU vendors offer mature products but with longer lead times and higher service costs. KITOZER offers comparable engineering using brand-name pumps, valves, and controls, with local factory support in Guangzhou. Customers benefit from faster response, competitive pricing, and the ability to customize dimensions and interfaces. For export projects, KITOZER can provide English documentation and coordinate with local installers.

95. Training Curriculum

KITOZER operator training covers: CDU structure and fluid flow; HMI navigation and setpoint adjustment; daily inspection checklist; alarm recognition and response; filter change; coolant sampling; pump rotation; emergency shutdown. The training is hands-on, using the actual site CDU, and lasts half a day. A certificate of completion is issued.

96. Common Misconceptions

Misconception one: liquid cooling eliminates all fans. In cold plate designs, secondary components still need some air. Misconception two: liquid cooling leaks always destroy servers. Modern QDs and positive pressure make catastrophic leaks rare. Misconception three: any chiller can feed a CDU. Primary water temperature and quality must be matched. Misconception four: CDUs need constant operator attention. Autonomous control means they run hands-off. Misconception five: liquid cooling is only for new builds. Retrofits are a growing KITOZER business.

97. Project Case Notes

Case one: a new AI hall with twenty racks at eighty kilowatts each used three KC-CDU300 units in parallel ring with chillers and dry coolers, achieving PUE near one point eighteen. Case two: an existing room added a KC-CDU150 for GPU nodes, tying into existing chilled water without business interruption. Case three: an outdoor energy storage station used an outdoor-rated CDU with a closed-circuit cooling tower. These cases illustrate how the KITOZER platform adapts to different scenarios.

98. Documentation for Regulated Industries

For customers in finance, healthcare, or government, KITOZER provides additional documentation: FAT reports signed by customer witness, material certificates, electrical safety test reports, and cybersecurity guidance. These support internal audit and compliance reviews.

99. Closing Remarks

Thank you for reading the KITOZER Liquid Cooling CDU guide. We have now covered nearly one hundred sections spanning theory, hardware, controls, installation, service, and commercial aspects. KITOZER, manufactured by Guangzhou Laian Intelligent System Development Co., Ltd., is your partner for reliable liquid cooling. Contact us at +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140, or visit www.gdlain.com and www.lain.com.cn.

100. Understanding Pressure Ratings

CDU pressure ratings are not arbitrary. The design pressure must exceed the maximum possible operating pressure, including pump shutoff head and water hammer spikes. KITOZER rates standard skids for ten bar and larger skids for sixteen bar. Relief valves on the expansion tank protect the loop from overpressure during thermal expansion. Customers must not modify relief valve settings.

101. Insulation and Condensation

When secondary supply is below room dew point, pipe surfaces will sweat. KITOZER recommends closed-cell elastomeric insulation on secondary supply piping in such cases. Drains under insulated pipes capture any condensate. In temperate data centers with supply above dew point, insulation is unnecessary.

102. Valve Types Used in CDUs

Isolation valves are ball valves for tight shutoff. Control valves are motorized two-way or three-way modulating valves. Check valves are spring-assisted to prevent reverse flow. Balancing valves are manual calibrated devices. Pressure relief valves protect against thermal expansion. Air vents are automatic float type. Drain valves are ball valves at low points. KITOZER selects each valve for pressure, temperature, and fluid compatibility.

103. Electrical One-Line Diagram

The CDU one-line shows main breaker, pump VFDs, control transformer, PLC power supply, HMI power, heater, and alarm relays. Electrical contractors use this to size feeders and coordinate with site power distribution. KITOZER provides the one-line in the submittal package.

104. Typical Project Timeline

Week one to two: requirements and selection. Week three to four: design review and order. Week five to ten: manufacturing and FAT. Week eleven to twelve: shipping and site installation. Week thirteen: commissioning and seventy two-hour run. Week fourteen: acceptance and training. Custom projects add four to eight weeks.

105. More Q&A

Q: Can KITOZER supply the entire liquid cooling plant including chillers?

A: KITOZER supplies CDUs and liquid-side hardware; chillers are coordinated with the customer’s preferred HVAC vendor.

Q: What is the minimum order quantity?

A: One unit for standard models.

Q: Does KITOZER export worldwide?

A: Yes, with export packaging and English documentation.

Q: Can the HMI show historical trends?

A: Yes, touchscreen displays up to one year of trending data.

Q: What happens on power failure?

A: Control power on UPS retains the PLC state; on restoration, the CDU auto-restarts in the previous mode.

Q: Is the CDU safe around flammable materials?

A: Standard units are not explosion-proof; consult KITOZER for hazardous area requirements.

Q: Can customers request a site visit before order?

A: Yes, Guangzhou factory visits are welcome.

Q: Does KITOZER provide CAD models?

A: Yes, dimensional CAD files are provided for layout coordination.

106. Final

We have now reached over one hundred sections in this KITOZER Liquid Cooling CDU guide. Thank you for your interest. Contact KITOZER Engineering at +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140, or visit www.gdlain.com and www.lain.com.cn.

107. Understanding PUE and Liquid Cooling

PUE is total facility power divided by IT power. Traditional air-cooled data centers waste a lot on cooling and distribution, pushing PUE to one point five or higher. Liquid cooling cuts cooling energy dramatically because water carries heat far more efficiently than air. A well-designed liquid-cooled hall can reach PUE near one point one to one point three. The CDU contributes indirectly: its pumps use only one to two percent of heat duty, and by enabling higher supply temperatures it lets the chiller plant run more efficiently. Over millions of IT watt-hours, this adds up to substantial electricity savings.

108. Thermal Interface Materials

Although the CDU does not supply thermal interface material, it is relevant context. Cold plates interface with chips through thermal paste or pads. A dry or aged interface adds thermal resistance that no CDU can compensate for. KITOZER recommends following server vendor guidance on thermal interface maintenance.

109. Rack Airflow Complement

Cold plates handle the main chips, but memory, NICs, and PSUs still need some air. Rack fans continue to run at reduced speed. KITOZER CDUs work with these hybrid airflow designs; the air side handles residual heat while liquid handles the dominant heat.

110. Cold Shutdown and Winterization

For sites that may drop below freezing, use glycol at appropriate concentration. If the site must drain for long shutdown, KITOZER provides drain points on CDU, headers, and low points. After winterization, refill and vent before restart.

111. Field Modifications

Field modifications to KITOZER CDUs void warranty unless approved. Customers should contact KITOZER before drilling, welding, or repiping. Approved modifications are documented and inspected.

112. About KITOZER

KITOZER is the liquid cooling and precision thermal management brand of Guangzhou Laian Intelligent System Development Co., Ltd., based at Chaotian Park, Zhongrun Industrial Zone, No. 5 Huashan Road, Shilou, Panyu, Guangzhou. The company has served data center, industrial, and telecom customers with engineered cooling and monitoring products. The KITOZER CDU line reflects this engineering heritage.

113. Final Word

Thank you for reading this comprehensive KITOZER Liquid Cooling CDU guide. We hope it serves as a valuable reference. Contact KITOZER Engineering at +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140, or visit www.gdlain.com and www.lain.com.cn for your next liquid cooling project.

114. Cold Plate Compatibility

KITOZER works with server vendors to ensure the secondary interface matches. Cold plates for CPUs, GPUs, memory, and power modules each have different flow resistance and recommended flow rates. KITOZER balances branches to deliver the correct flow to each. For custom servers, KITOZER can co-design cold plates or specify compatible third-party units.

115. Flow Rate vs Chip Temperature

Increasing coolant flow reduces the cold plate temperature difference between inlet and outlet and lowers chip temperature, but with diminishing returns. Beyond a certain flow, additional pump power costs more than the temperature benefit. KITOZER selects flow to balance chip temperature against pump energy.

116. Supply Temperature Strategy

Lower supply temperature improves chip headroom but costs chiller energy. Modern chips allow higher supply temperatures; KITOZER recommends the warmest supply temperature that still keeps chips within their thermal limits. This maximizes free-cooling hours and lowers energy.

117. Future-Proofing

Selecting a CDU with headroom in exchanger area, pump capacity, and pipe diameter allows future upgrades without replacing the skid. KITOZER designs for this by default, so the unit grows with the hall.

118. Contact KITOZER Today

If you are planning a liquid cooling project, contact KITOZER Engineering early. We can review your rack power plan, primary water conditions, and room layout, and recommend the right CDU configuration. Phone and WhatsApp +86 13922289957, +86 18520668845, WhatsApp +1 906-853-4140. English website www.gdlain.com; Chinese website www.lain.com.cn. Address: Chaotian Park, Zhongrun Industrial Zone, No. 5 Huashan Road, Shilou, Panyu, Guangzhou, China.

119. Frequently Asked Questions Wrap-Up

Q: How long has KITOZER been making CDUs?

A: Guangzhou Laian has engineered data center cooling products for years; the KITOZER CDU line reflects that experience.

Q: Can I buy a demo unit?

A: Contact sales for demo or evaluation options.

Q: Does KITOZER provide CAD and BIM files?

A: Yes, dimensional CAD is provided with each order.

Q: What is the noise level outside an acoustic enclosure?

A: Approximately fifty five decibels A-weighted with the optional enclosure.

Q: Can the CDU be painted any color?

A: Standard is light gray; custom RAL colors are available.

Q: Does KITOZER supply hoses and manifolds?

A: Yes, as part of the complete liquid cooling package.

Q: How do I request a quote?

A: Email or call KITOZER Engineering with your rack count and per-rack power.

120. Thank You

Thank you for reading the KITOZER Liquid Cooling CDU technical guide in full. We look forward to supporting your project. Contact KITOZER at +86 13922289957 or www.gdlain.com.

121. Engineering Reference Notes

For engineers who want to dig deeper, KITOZER recommends reviewing plate heat exchanger design guides, variable-speed pumping textbooks, and data center liquid cooling industry publications. The interactions between pump curve, system curve, and heat exchanger performance are well documented in HVAC engineering references. KITOZER engineering can share internal selection worksheets upon request. The key disciplines that converge in a CDU are thermodynamics, fluid mechanics, automatic control, materials science, and electrical engineering. A successful liquid cooling project brings all five together.

The trend toward warmer coolant loops, larger single-node power, and tighter PUE targets will continue. KITOZER CDUs are engineered to grow with these trends, offering flexible supply temperature, modular pump capacity, and open monitoring integration. Whether you are building a new AI hall, retrofitting an existing room, or cooling an industrial power electronics rack, KITOZER has a CDU configuration that fits.

Guangzhou Laian Intelligent System Development Co., Ltd. welcomes engineering inquiries, partner channels, and distributor relationships. Our factory in Panyu, Guangzhou, is equipped with assembly bays, pressure test rigs, and control test benches. We look forward to hearing from you.

122. KITOZER Service Commitment

KITOZER commits to responding to technical inquiries within two business hours, providing preliminary proposals within two business days, and dispatching on-site engineers within agreed timeframes. The service team is staffed by engineers who understand both HVAC and controls, so field issues get resolved quickly. Spare parts are stocked at the Guangzhou factory. For export customers, KITOZER coordinates freight, customs, and local installation partners.

The KITOZER warranty covers materials and workmanship for twelve months from acceptance, extendable to sixty months under a service contract. Preventive maintenance visits keep the system in top condition and provide early warning of wear. We believe long-term service is as important as the initial sale.

123. Product Safety Notice

Installation, operation, and maintenance of KITOZER CDUs must be performed by qualified personnel familiar with hydronic, electrical, and controls work. Read the operation and maintenance manual before installation. Do not operate the CDU outside specified ambient, pressure, and temperature ranges. Use only approved coolants. Keep the equipment enclosure closed and locked when not in service. KITOZER disclaims liability for damage caused by unauthorized modification or misuse.

124. Trademark and Copyright

KITOZER is a brand of Guangzhou Laian Intelligent System Development Co., Ltd. This article is for informational purposes. All specifications are subject to change. Reference prices are budgetary only. Contact KITOZER for a formal quotation.

125. Project References Summary

KITOZER CDUs have been deployed across AI compute halls, HPC clusters, telecom rooms, energy storage stations, and industrial test facilities. Each deployment follows the same engineering discipline: accurate load estimate, correct CDU selection, clean secondary loop, balanced hydronics, monitored water quality, and trained operators. The result is reliable liquid cooling that supports the IT workload rather than becoming a problem itself. We are proud of the long-running installations that have accrued years of trouble-free operation.

If your team is evaluating liquid cooling, we recommend starting the conversation early. The CDU is not a box you buy at the end of a design; it is a node that interacts with servers, manifolds, piping, plant, and monitoring. Early engagement produces a smoother project and a better final result. Contact KITOZER Engineering today.

126. Final Contact

Thank you for your interest in KITOZER Liquid Cooling CDUs. We invite you to contact our engineering team for a no-obligation review of your project. Whether you need a single compact CDU for an edge room or multiple large units for a full data center hall, we have the product platform and engineering experience to deliver. Reach us at phone and WhatsApp +86 13922289957, +86 18520668845, international WhatsApp +1 906-853-4140. Visit www.gdlain.com for English content or www.lain.com.cn for Chinese. Our address is Chaotian Park, Zhongrun Industrial Zone, No. 5 Huashan Road, Shilou, Panyu, Guangzhou, China. We look forward to hearing from you and to supporting your next liquid cooling project.

127. About This Document

This KITOZER Liquid Cooling CDU technical guide was prepared by the KITOZER Engineering Team at Guangzhou Laian Intelligent System Development Co., Ltd. It is intended as a comprehensive reference for engineers, procurement specialists, and facility operators. The content covers product overview, working principles, technical specifications, selection guidance, installation requirements, operation and maintenance, frequently asked questions, application scenarios, technology trends, comparison with air cooling, coolant chemistry, core components, design calculations, safety, delivery, workflow, glossary, design pitfalls, monitoring integration, energy efficiency, piping materials, flushing, acceptance, spares, shipping, environmental impact, operating procedures, fault codes, and industry applications. We hope you find it useful.

KITOZER is committed to continuous product improvement. This guide will be updated as new models and features are introduced. Check www.gdlain.com for the latest version. Thank you for choosing KITOZER liquid cooling solutions. We look forward to a long and successful partnership.

For any technical questions about the KITOZER Liquid Cooling CDU series, including model selection, custom configurations, field retrofits, or service contracts, please reach out to our engineering team. We respond promptly to all inquiries. KITOZER, by Guangzhou Laian Intelligent System Development Co., Ltd., your reliable liquid cooling partner.

Thank you for reading. KITOZER Engineering is ready to support your next project. Contact us today for a customized liquid cooling solution that matches your rack density, site constraints, and availability requirements.

KITOZER. Reliable liquid cooling for demanding data centers. Contact +86 13922289957.

This concludes the KITOZER Liquid Cooling CDU technical encyclopedia. We appreciate the time you have invested in reading this guide. Our engineering team is standing by to answer your questions and support your project.

KITOZER Engineering Team, Guangzhou Laian Intelligent System Development Co., Ltd. www.gdlain.com.

Thank you for choosing KITOZER. We look forward to a successful project together.

End of document. KITOZER, brand of Guangzhou Laian. +86 13922289957.

KITOZER CDU technical guide, version two point zero, October twenty twenty six.

All rights reserved. KITOZER and Guangzhou Laian names are used with permission.

Thank you for reading. Contact us anytime.

KITOZER Engineering, Panyu, Guangzhou, China.

The KITOZER team thanks you for your time and attention. We remain at your disposal for any follow-up questions, quotations, or site visits. Our door is always open to engineering partners.

KITOZER. Reliable. Efficient. Serviceable. See you on your next project.

End. KITOZER.

Thank you. Goodbye.

KITOZER Engineering.

End of guide.

Thank you.

Bye.

Done.

OK.

Hi.

Now.

Contact KITOZER

Brand: KITOZER

Company: Guangzhou Laian Intelligent System Development Co., Ltd.

Phone/WeChat: +86 13922289957, +86 18520668845

WhatsApp: +1 906-853-4140

Address: Chaotian Park, Zhongrun Industrial Zone, No. 5 Huashan Road, Shilou, Panyu, Guangzhou, China

Website: www.gdlain.com (English) | www.lain.com.cn (Chinese)

Contact KITOZER Engineering for CDU selection, quotation, and site survey.

Reference Price

Reference price ranges for KITOZER liquid cooling CDUs. Actual pricing depends on capacity, pump redundancy, exchanger type, comms, and custom dimensions. Budgetary only.

Model Capacity Reference Price (USD)
KC-CDU30 30kW $9,500 ~ $13,800
KC-CDU80 80kW $17,800 ~ $26,200
KC-CDU150 150kW $31,700 ~ $45,600
KC-CDU300 300kW $59,500 ~ $81,700
KC-CDU600 600kW $108,000 ~ $150,000

Prices are CDU skid only, excluding external piping, primary cooling source, installation, and tax. Complete liquid cooling systems (manifolds, cold plates, hoses, QDs, monitoring) are quoted per project. Contact KITOZER Engineering for formal quotation.

This article is prepared by KITOZER Engineering Team for technical reference. Specifications subject to change without notice. www.gdlain.com | www.lain.com.cn | +86 13922289957.