KITOZER -48V DC Power System Technical Specification | Telecom Rectifier Battery Backup 100A-2000A

Table of Contents

English Version

1. The History of Telecom Power and the Origin of the -48V Standard

1.1 From Magneto Telephones to Programmable Exchanges: A Century of Power Evolution

Telecom power is the heart of the entire communication network. The problem of power supply has evolved alongside communication technology ever since the birth of the telephone network in the late nineteenth century. Early magneto telephone systems were powered by a hand-cranked generator and dry cell at each subscriber station, while the exchange side used a bank of large lead-acid batteries as a central source. At that time, communication lines were open aerial wires strung through the air, and the metal sheaths of the cables were in direct contact with the earth. If a positive potential had been used, the conductors would have formed a strong galvanic corrosion cell with the damp soil—the positive metal electrode would lose electrons and dissolve into ions, slowly being eaten away. The principle is the inverse of electroplating: metal serving as the anode corrodes. To protect the precious copper conductors and lead sheaths, engineers made a far-reaching decision: ground the positive pole of the source so that the wires were always held at a negative potential. The cable metal then became the cathode in the electrochemical sequence, and the corrosion reaction was fundamentally suppressed.

This choice of “positive grounded” is the historical origin of the -48V convention. As common-battery exchanges replaced magneto systems in the early twentieth century, central power systems became universal. Early exchange voltages were not standardized—24V, 48V, 60V all coexisted. Through decades of engineering practice and standardization, -48V gradually emerged as the mainstream supply across the global telecommunications industry by the mid-twentieth century.

1.2 Why Exactly 48 Volts? The Engineering Trade-off

The choice of voltage level is fundamentally a trade-off between line losses and safety. At the same power, lower voltage means higher current, larger voltage drop, and greater losses along the wire; higher voltage reduces losses but increases shock hazard and insulation cost.

Early telecom networks had very long supply distances—from the central office to the subscriber could span several kilometers. At 24V, the voltage drop across such long copper runs would have been too large for the terminal equipment to function. Engineers calculated that 48V kept line losses within an acceptable range for the available wire gauges and distances, without raising the shock risk to dangerous levels. Crucially, 48V sits near the boundary of “safe voltage”: the IEC and national electrical codes typically set the upper limit of safety extra-low voltage (SELV) at around 60V in dry conditions. At 48V DC, the current through a human body with high skin resistance is limited to below the perception threshold, preventing lethal shock. This is why the telecom industry never adopted 110V or 220V DC—those would create unacceptable personal safety hazards.

The battery series configuration also locked in the number 48. A valve-regulated lead-acid (VRLA) cell has a nominal 2V and floats at about 2.25V. Twenty-four cells in series give about 54V on float, 51V open-circuit, and a nominal operating point near 48V. This “24-cell string” became the default telecom battery configuration over decades, further cementing the -48V standard.

1.3 Why “Minus” 48V and Not “Plus” 48V?

This is the question newcomers ask most often. The answer was already planted in section 1.1—positive grounding for corrosion protection.

In a -48V system, the positive terminal of the battery bank is directly bonded to the equipment room ground busbar (the 0V / working ground), and the negative terminal outputs the -48V potential. That is to say, the grounded side of the supply is the positive pole, and the “hot” conductor feeding the equipment is the negative pole. At the equipment input, the -48V terminal connects to the high-potential side (negative relative to ground), and the 0V terminal grounds.

This arrangement delivers three engineering benefits:

First, electrochemical corrosion prevention. As described, aerial wires and buried cable sheaths contact the earth; negative-potential supply makes the cable sheath the cathode, preventing corrosion. Although modern networks are largely fiber, copper access segments (xDSL, the copper part of FTTx) still exist, and this standard is baked into the design of every telecom device—no one can change it.

Second, reduced shock risk under ground faults. Positive grounding means the 0V bus is equipotential with the equipment chassis. If insulation fails and the -48V conductor touches the chassis, since the chassis is already grounded (to 0V), the fault current returns through the ground wire and triggers protective devices, rather than exposing maintenance personnel to a live chassis.

Third, historical equipment compatibility. Hundreds of millions of exchange, transmission, and base-station devices worldwide are designed for “positive grounded.” Switching to +48V would require reversing the input polarity of every device—economically and logistically unthinkable.

Thus, “-48V” is not an arbitrary sign; it is the optimal solution沉淀 by a century of telecom engineering under the triple constraints of corrosion prevention, safety, and compatibility.

1.4 From Motor-Generator Sets to Switch-Mode Power Supplies: Evolution of the Hardware

Early telecom DC power used motor-generator (M-G) sets: an AC motor drove a DC generator that output 48V DC for float charging the battery bank. These rotating machines were bulky, noisy, inefficient, and maintenance-intensive. In the 1950s, selenium and copper-oxide rectifiers gradually replaced motor-generators. In the 1960s, silicon diode rectification matured, and telecom power entered the phase-controlled (thyristor) era—SCR firing angles were adjusted to regulate output voltage. Phase-controlled rectifiers were heavy, had poor power factor, and generated significant harmonics, but they were extremely reliable and many served into the 1980s.

The real revolution came in the 1980s. As power electronics (power MOSFETs, IGBTs) and high-frequency PWM techniques matured, switch-mode power supplies (SMPS) displaced phase-controlled rectifiers. A switch-mode rectifier first rectifies the AC input into high-voltage DC, then transforms and isolates it through a high-frequency transformer (tens to over a hundred kHz), and finally rectifies and filters it to -48V DC. Because the operating frequency rose by two orders of magnitude, the transformer and filter shrank dramatically, efficiency climbed from around 80% in the phase-control era to over 90%, and active PFC pushed power factor to 0.99.

Today’s telecom rectifier modules are highly integrated: a single module is the size of a shoebox, weighs 3-5 kg, outputs 50A or 100A at over 96% efficiency, and supports hot swapping, parallel current sharing, and remote monitoring. The KITOZER series represents the contemporary generation of this technology lineage.

2. System Architecture: Rectifier, Monitor, Battery Bank, and Distribution

A complete -48V telecom DC power system consists of four subsystems: the rectifier subsystem, the monitoring subsystem, the battery subsystem, and the DC distribution subsystem. They work together to deliver the core function—when mains is present, rectifiers supply the load and float-charge the batteries; when mains fails, the batteries seamlessly carry the load.

2.1 The Rectifier Subsystem (Rectifier Modules + AC Distribution)

The rectifier subsystem is the system’s “prime mover.” It takes power from the mains (typically 220V single-phase or 380V three-phase AC) and converts it to -48V DC. Physically, it consists of a rack (cabinet) populated by plug-in rectifier modules.

The AC distribution section brings mains into the rack: it includes an AC breaker, surge protective device (SPD), AC input terminals, and loss-of-phase / over-under-voltage detection. Medium-to-large systems typically support automatic transfer between two mains feeds (ATS) or a single mains plus diesel generator backup.

Rectifier modules are the core power units. Multiple modules are paralleled on a common DC bus, sharing the load current. The key technical challenge in paralleling is “current sharing”—ensuring each module contributes an equal share so that no single module is overloaded while others run light. Modern rectifiers use active current-sharing, controlling imbalance to within ±5%.

2.2 The Monitoring Subsystem (Monitor Module)

The monitor module is the “brain” of the power system. It is a display unit mounted on the front of the rack, with an LCD/LED screen and buttons, responsible for:

  • Data acquisition: measuring DC bus voltage, total load current, each rectifier module’s output current, battery voltage/charge-discharge current, temperature, fuse status, and AC input voltage.
  • Control functions: automatically switching between float/boost/test based on the battery management strategy; setting the rectifier output voltage; raising alarms on faults.
  • Alarm and protection: overvoltage, undervoltage, overcurrent, module failure, AC loss, battery low voltage, abnormal temperature—reported via dry contacts or RS485/Ethernet/Modbus to the environment monitoring system.
  • Human-machine interface: local display of voltage/current trends, event logs, and parameter settings.

The monitor itself is designed for reliability—it carries no power current. Even if the monitor crashes, the rectifiers continue to output at default parameters, and the system stays up. This is the design principle: “monitor failure must not interrupt power.”

2.3 The Battery Subsystem

The battery bank is the system’s “reservoir.” When mains is healthy, the rectifiers supply the load while float-charging the batteries at a small current to offset self-discharge. When mains fails, the rectifiers stop, and the battery bank seamlessly switches to discharge on the DC bus, carrying the load until mains returns or backup time is exhausted.

Two battery chemistries dominate modern telecom rooms:
– Valve-regulated sealed lead-acid (VRLA): mature, low-cost, reliable—the traditional mainstay. 2V cells, 24 cells in series for a 48V string.
– Lithium iron phosphate (LFP): compact, lightweight, long cycle life, high-rate discharge—rapidly gaining ground in 5G base stations and outdoor sites. KITOZER also offers matched 48V/50Ah-300Ah LFP battery cabinets.

The central design question for batteries is “backup time”—how long the batteries can hold the load after a mains failure. This depends on load power, battery capacity, end-of-discharge voltage, and temperature; section 5 gives the calculation in detail.

2.4 The DC Distribution Subsystem (First/Second Load Disconnection)

The DC distribution subsystem is the system’s “grid.” It distributes the -48V DC collected by the rectifiers and batteries through a series of breakers and fuses to each load circuit. The signature design of telecom DC distribution is first load disconnection (FLD) and second load disconnection (SLD):

  • First load disconnection (priority): feeds equipment that must stay up—base-station main control, transmission links, core service boards.
  • Second load disconnection (secondary priority): feeds equipment that can tolerate short interruption—air conditioning, lighting, non-essential services.

When mains fails and the battery discharges to a set voltage, the monitor first opens the SLD circuit, concentrating the limited battery energy on the FLD circuit to extend critical-equipment runtime. When the battery reaches end-of-discharge voltage, it opens the FLD circuit as well, preventing over-discharge damage. This tiered disconnection is a hallmark that distinguishes telecom power from ordinary UPS.

2.5 How the Four Subsystems Cooperate: A Day in the Life of a 5G Site

Take a 5G base station and trace a day:

  1. Mains healthy (220V): AC distribution feeds four rectifier modules. Each outputs -48V/50A for 200A total capacity. The actual load (RF + transmission) draws 80A. The rectifiers run at float voltage -53.5V while float-charging the battery bank (about 1-3A charge current). The monitor shows “mains OK, float, battery 53.5V.”
  2. Mains fails: AC detection alarms immediately, and the rectifiers stop. The DC bus voltage is instantly taken over by the battery bank, which transitions from float to discharge, its voltage slowly dropping from 53.5V. The monitor sends an “AC failure” alarm to the NMS.
  3. Battery discharges to -46V: the monitor judges discharge is half done and opens the SLD circuit (air conditioning and lighting drop off). The load current falls from 80A to 55A, slowing the battery drain.
  4. Mains returns: the rectifiers restart and charge the battery bank in boost mode (to restore capacity) while continuing to supply the load. The monitor sends a “mains restored” alarm and logs the event.
  5. Battery fully charged: the monitor automatically switches from boost back to float, and the system returns to normal.

This “seamless transfer” is invisible to the load—the DC bus is always live, and rectifiers and batteries are paralleled on the bus with no transfer gap. This is the essence of the “N+1 redundant rectifier + parallel float battery” telecom power architecture.

3. KITOZER Series Specifications: -48V/100A-2000A, 19″/23″ Racks

3.1 Series Overview

The KITOZER -48V telecom DC power line covers the full power range from small access points (100A) to large central offices (2000A). Product forms include wall-mount small power, 19-inch rack power, 23-inch wide rack power, indoor cabinet power, and outdoor integrated power.

Model System Capacity Rectifier Config Rack Typical Application
KITOZER-DPS-100 -48V/100A 2×50A (1+1) Wall/19″ Small access point
KITOZER-DPS-200 -48V/200A 4×50A (3+1) 19″ rack Access room / micro cell
KITOZER-DPS-400 -48V/400A 4×100A (3+1) 19″/23″ Aggregation room / 5G site
KITOZER-DPS-600 -48V/600A 6×100A (5+1) 23″ rack Medium central office
KITOZER-DPS-1000 -48V/1000A 10×100A (9+1) 23″ dual-row Large central office
KITOZER-DPS-2000 -48V/2000A 20×100A (19+1) 23″ paralleled Hub room / data center

3.2 19-Inch vs. 23-Inch Racks

19-inch is the universal IT standard (ETSI); most telecom equipment racks are 19-inch. 23-inch (about 584 mm wide) is the traditional posts-and-telecom standard, commonly called the “PT rack,” widely used in legacy program-controlled exchange rooms. The width difference determines how many rectifier modules fit:

  • 19-inch rack (482.6 mm wide): typically fits 3-4 standard-width (about 108 mm each) rectifier modules side by side.
  • 23-inch rack (584 mm wide): fits 4-5 modules, delivering greater capacity at the same height.

KITOZER offers both 19-inch and 23-inch racks to suit either new builds (19-inch recommended, aligned with mainstream IT/telecom gear) or retrofits of legacy 23-inch rooms.

3.3 Key Electrical Specifications

Parameter Value Note
Nominal DC voltage -48V Nameplate
DC output range -42V to -59.5V Float/boost adjustable
Normal operating range -38.4V to -57.6V Equipment tolerance
AC input voltage 220V/380V ±20% Single/three-phase
AC input frequency 45Hz to 65Hz Generator fluctuation
System efficiency ≥96% (high-eff module) Rated load
Power factor ≥0.99 (with PFC) Full load
Voltage regulation accuracy ≤±0.6% Float stability
Current regulation accuracy ≤±1% Boost current limit
Weighted noise voltage ≤2mV 300Hz-3.4kHz
Peak-to-peak noise ≤400mV 0-300Hz
Parallel current-sharing imbalance ≤±5% Among N+1 modules
Insulation resistance ≥10MΩ Live circuit to ground
Protection rating IP20 (indoor) Outdoor IP55
Operating temperature -5°C to +45°C (std) Wide-temp -30°C to +55°C

3.4 Module Slots and N+1 Redundancy

KITOZER racks are designed with spare rectifier slots. For example, the DPS-400 rack has 6 slots but ships with 4 modules (3 carrying load + 1 redundant), leaving 2 slots for future growth. This “N+1 redundancy” means that if any one rectifier fails, the remaining modules still carry the full load. Sizing follows “load current ÷ module capacity = N, plus one redundant module.”

For example, a 300A load with 100A modules means N=3, so configure 4 modules (3+1). If the load later grows to 400A, just plug modules into the empty slots—no rack replacement.

3.5 Monitor Module and Communication Interfaces

The KITOZER monitor standard includes:
– LCD display, Chinese/English menus
– RS485 port, Modbus-RTU
– Ethernet (optional), Modbus-TCP/SNMP
– 8 dry-contact alarm outputs (AC fail, DC overvoltage, battery low, module fault, etc.)
– 2 dry-contact alarm inputs (fuse status, door switch)
– ≥500 event log entries
– Battery management: automatic float/boost transition, temperature compensation, periodic capacity test

4. Rectifier Module Technology: High Efficiency, Parallel Sharing, and Hot Swap

4.1 Operating Principle of the High-Frequency Switch Rectifier

The KITOZER rectifier uses a two-stage conversion architecture:

Stage 1 (PFC): AC input passes through EMI filtering and a rectifier bridge to produce about 310V high-voltage DC. An active power factor correction (APFC) boost chopper then stabilizes the HV DC at about 400V while making the input current follow the voltage sinusoidally, achieving near-unity power factor and THDi under 5%.

Stage 2 (DC/DC): The 400V HV DC is inverted to a high-frequency square wave (tens of kHz) by a full-bridge or half-bridge circuit, stepped down and isolated by a high-frequency transformer, then rectified to -48V low-voltage DC by synchronous rectifier diodes (or MOSFETs) and filtered by an LC network.

The control chip closes the loop in real time: if output voltage sags, PWM duty cycle rises; if it rises, duty cycle falls. The benefit of high-frequency conversion is a tiny transformer—higher frequency means less required flux swing, smaller core cross-section. Power density reaches over ten watts per liter.

4.2 How High Efficiency Is Achieved

KITOZER high-efficiency rectifiers exceed 96% through:

  • Soft switching (ZVS/ZCS): MOSFETs switch at zero voltage or zero current, eliminating switching losses. Traditional hard switching at high frequency suffers huge losses; soft switching pushes them to near zero.
  • Synchronous rectification: the low-voltage, high-current side rectifier diodes are replaced by extremely low-Rds(on) MOSFETs, cutting the diode-drop loss (0.5-1V) to the milliohm range.
  • Advanced magnetics: nanocrystalline or amorphous cores for low high-frequency iron loss; planar transformers to reduce winding AC loss.
  • Sleep mode: at light load, modules are automatically shut down so the remaining ones work in the high-efficiency zone (typically 50%-75% load gives peak efficiency).

What does the jump from 91% to 96% mean? For a 400A system running 8,760 hours a year: output power is 19.2 kW. At 91% efficiency, input is 21.1 kW and loss is 1.9 kW; at 96%, input is 20.0 kW and loss is 0.8 kW. Annual savings: (1.9-0.8)×8,760 ≈ 9,636 kWh—nearly ten thousand yuan at one yuan per kWh. This is why high-efficiency modules, though pricier, pay for themselves in two or three years in large rooms.

4.3 Parallel Current Sharing

When multiple rectifiers parallel on one bus, current sharing is essential. If two modules parallel and one has lower internal resistance, it carries more current and may overload, while the other runs light. Long-term imbalance causes overheating and shortened life.

KITOZER modules use active current sharing: each module exchanges its output current information over a parallel share bus, and the control chip dynamically trims each module’s output voltage setpoint so all modules share current evenly, to within ±5%. When a module drops out, the remaining modules rebalance within milliseconds without overloading.

4.4 Hot-Swap Technology

Hot swap means a module can be pulled or inserted without taking the system down. This is critical for maintenance at unattended sites—faulty modules are replaced without powering off.

Hot swap requires coordinated hardware:
– “Long pin / short pin” terminals: on insertion, power contacts mate first (pre-charge), signal contacts last; on removal, signals break before power, avoiding live arcing.
– Internal soft-start: on insertion, output ramps from zero to setpoint rather than slamming on, preventing bus current spikes.
– Mechanical guide and anti-keying: a module cannot be inserted backwards or skewed.

4.5 Module Protection Functions

Each rectifier module includes:
– Output overvoltage protection (OVP): internal disconnect if output exceeds threshold (e.g., 60V), protecting downstream gear.
– Output overcurrent / short-circuit: current-limits to 1.1-1.2× rated on short circuit; auto-recovers when cleared.
– Overtemperature protection: derates above 85°C, shuts down above 95°C, auto-restarts on cooling.
– AC input under/overvoltage: stops on abnormal mains to protect the input stage.
– Fan-fault detection: temperature-controlled fan; alarms and derates if the fan stops.

5. Battery Configuration: VRLA vs. Lithium and Backup-Time Calculation

5.1 Two Technology Paths

Telecom batteries have gone through three generations: from “flooded lead-acid” to “valve-regulated sealed lead-acid (VRLA)” to “lithium iron phosphate (LFP).” KITOZER systems support both VRLA and LFP; the monitor auto-adjusts charge-discharge strategy based on chemistry.

Item VRLA LFP
Cell nominal voltage 2V 3.2V
Cells in 48V string 24 (2V×24) 16S (3.2V×16)
Float voltage (48V) 53.5V (2.23V/cell) 54.8V (3.425V/cell)
Boost voltage 56.4V (2.35V/cell) 58.4V (3.65V/cell)
End-of-discharge 43.2V (1.8V/cell) 44.8V (2.8V/cell)
Energy density 30-40 Wh/kg 120-160 Wh/kg
Cycle life (80% DOD) 1000-1500 cycles 3000-6000 cycles
Self-discharge 3-5%/month 1-3%/month
Operating temp -15°C to +45°C -20°C to +60°C
Cost (RMB/Wh) 0.5-0.8 0.8-1.2
Weight Heavy (3× Li-ion) Light
Safety Relief valve, flame-retardant BMS-managed, thermally stable

5.2 Backup-Time Calculation

Backup time is the core battery sizing question:

T = (C × V × η) / P

where:
– T = backup time (hours)
– C = battery rated capacity (Ah)
– V = average discharge voltage (V; ~48V for 48V systems)
– η = discharge efficiency (0.8-0.9 VRLA, 0.95-1.0 LFP)
– P = load power (W)

Or in current terms:

T = C × K / I_load

where I_load is load current (A) and K is the discharge-rate and temperature derating factor.

Example: a 5G site draws 4 kW (~83A); required backup is 4 hours. VRLA sizing:
– C = P×T/(V×η) = 4000×4/(48×0.85) ≈ 392 Ah
– Choose a standard 400Ah/48V VRLA string (2V×200Ah×24 cells, two strings in parallel for 400Ah).

LFP sizing:
– C = 4000×4/(48×0.95) ≈ 351 Ah
– Choose 48V/300Ah LFP (actual backup ~3.5h; choose 400Ah LFP for a full 4h).

5.3 Discharge-Rate and Temperature Derating

The simplified formula needs two corrections for precise design:

Discharge-rate derating: battery capacity is rated at a standard rate (e.g., C10, the 10-hour rate). At high-rate (1-hour) discharge, usable capacity drops. VRLA delivers only about 55%-60% of rated capacity at the 1-hour rate; LFP is less affected (over 90% at 1-hour rate).

Temperature derating: lead-acid capacity drops with temperature. At 25°C baseline, 0°C gives ~80%, -10°C gives ~60%. If the room is routinely below 20°C, derate capacity or oversize.

Corrected formula:

C_required = P × T / (V × η × K_rate × K_temp)

where K_rate is the discharge-rate factor and K_temp is the temperature factor.

5.4 Battery Parallelism and Cell Count

Telecom batteries are configured in “strings,” each string 24 cells of 2V VRLA in series for 48V. When a single string is insufficient, multiple strings parallel—e.g., two 200Ah strings in parallel for 400Ah. Generally no more than four strings in parallel, beyond which circulating current and aging imbalance become problematic.

LFP is a packaged solution: the factory integrates 16S cells + BMS + cabinet into a 48V/100Ah or 200Ah module; paralleling modules is all the user does. KITOZER LFP cabinets support up to 10 modules in parallel, up to 2000Ah total.

5.5 Battery Management and Temperature Compensation

The monitor’s battery strategy directly affects life:

  • Float-voltage temperature compensation: optimum float voltage drifts with temperature—for every 1°C rise, float voltage should drop 3mV/cell. The monitor compensates via a temperature sensor, preventing high-temperature overcharge and drying out.
  • Boost management: after a mains outage and recovery, charge at boost voltage (56.4V) current-limited until full (current drops to the float-transition threshold), then auto-switch back to float.
  • Periodic capacity test: every 3-6 months, the monitor triggers a small discharge to assess battery state of health (SOH) and identify weak cells.
  • Low-voltage disconnect: at end-of-discharge, the battery breaker opens to prevent over-discharge.

5.6 VRLA vs. LFP Selection Guidance

  • Indoor staffed central office: VRLA is mature, cheap, and the floor can carry the weight—recommended.
  • 5G / outdoor / rooftop sites: space and weight are limited, temperature varies widely—LFP recommended.
  • Long cycle-life sites: LFP lasts 3-4× longer; total lifecycle cost can be lower.
  • Weight-sensitive rooftop/tower sites: LFP is 1/3-1/4 the weight of VRLA—often the only option.
  • Tight-budget retrofit: VRLA has lower upfront cost and phased expansion.

6. Distribution Architecture: First/Second Load Disconnection and Battery Breaker

6.1 DC Distribution Topology

KITOZER -48V distribution follows the classic “busbar + branch breaker” topology. Rectifiers and batteries both parallel on the DC busbars (positive and negative bars), and loads draw power through breakers at each level.

A complete DC cabinet (power cabinet / column header) contains:
– AC input zone: mains feed, ATS transfer, SPD, AC breaker.
– Rectifier zone: rack slots with rectifier modules.
– DC busbar zone: copper bars collecting all module outputs and battery feeds.
– Battery zone: battery fuses/breakers, battery disconnect.
– DC output zone: FLD and SLD branches, each with its own DC breaker.
– Monitor zone: monitor unit, sensor wiring.

6.2 Tiered Disconnection Strategy

This is the signature telecom design. The DC output is split into two groups:

First Load Disconnection (FLD):
– Feeds mission-critical gear: base-station main control, BTS/AAU RF, core switches, transmission, NMS.
– Not disconnected until near end-of-discharge.

Second Load Disconnection (SLD):
– Feeds non-guaranteed gear: room air conditioning, lighting, exhaust fans, backup services, test gear.
– The monitor opens the SLD breaker when the battery discharges to a set voltage (typically -46V).

Tiered disconnection concentrates finite battery energy on critical services. Example: total load 80A, of which FLD 50A and SLD 30A. Battery sized for 50A×4h. Without tiering, 80A lasts only 2.5h; after SLD opens, 50A runs much longer.

6.3 Battery Load Disconnect (BLSD)

The battery disconnect is the switch between the battery bank and the DC bus. It serves to:
– Maintenance isolation: isolate batteries from the bus during service.
– Over-discharge protection: opens at end-of-discharge voltage (e.g., 43.2V) to prevent damage.
– Fault isolation: opens rapidly on internal battery short circuit to contain fire.

KITOZER uses DC fuses or DC circuit breakers. Fuses are simple and high-interrupting but must be replaced; breakers are reusable with auxiliary contacts for status reporting. Large systems (>400Ah) recommend DC breakers; small systems can use fuses.

6.4 Selecting DC Breakers

The DC circuit breaker is the most critical protective device. It differs fundamentally from AC breakers in arc interruption: AC crosses zero 100 times per second, extinguishing the arc naturally; DC has no zero crossing, and the arc must be force-cooled by the breaker’s arc chute (narrow-slot extinction). Therefore a DC breaker’s voltage rating must match the system, its current rating the load, and its interrupting rating the available short-circuit current.

Selection points:
– Rated voltage: DC rating ≥ system maximum (choose DC60V or DC100V for -48V systems).
– Rated current: branch-rated × 1.25-1.5 headroom.
– Interrupting capacity: ≥ maximum possible short-circuit current (usually set by battery capacity; a 400Ah battery can deliver thousands of amps).
– Polarity: DC breakers are polarity-sensitive; cannot reverse.
– Upstream-downstream selectivity: upstream breaker trip curve must be slower than downstream.

6.5 Column Header Cabinet and Rack-Top Distribution (DDU/DDP)

In large rooms, DC distribution is two-tier:
– Primary (column header cabinet): at the head of each equipment row, takes feed from the power cabinet and distributes to each rack.
– Secondary (rack-top DDU/DDP): on top of each rack, takes feed from the column header and subdivides to equipment inside.

KITOZER DDU (distribution unit) and DDP (distribution panel) are the secondary-tier devices. DDU is single-input; DDP provides primary/backup dual-input redundancy. This two-tier architecture gives flexible distribution in large rooms while confining faults to a single rack.

6.6 Selectivity in Protection Coordination

Selectivity is the core requirement: when a branch shorts, only that branch’s breaker trips; other branches and the upstream stay up. Achieving selectivity requires:
– Upstream-downstream current ratio ≥1.6:1 (e.g., 32A downstream, 63A upstream).
– Trip-curve coordination: upstream C or D curve (delayed), downstream B or C (instantaneous).
– Time coordination: downstream trips in 0.01-0.02s on short circuit; upstream short-delay 0.1-0.2s does not act.

Without selectivity, a short in one rack can trip the entire column header and widen the outage. Designers must verify with the manufacturer’s selectivity coordination tables.

7. Applications: Base Stations, Data Centers, and 5G Rooms

7.1 Mobile Base Stations (2G/4G/5G)

Base stations are the largest application of -48V power. Each site has its own -48V system:

  • 2G/4G macro site: load ~20-40A; 2-3×50A modules (N+1); 100-200Ah battery; 4-8h backup.
  • 5G site (AAU+DU): load up to 60-120A (AAU is 2-3× the power of a 4G RRU); 3-4×100A modules; 200-400Ah battery.
  • Micro/pico site: load 5-15A; wall-mount small power; 50Ah battery.

A new trend in 5G is “power on the tower”—small rectifiers and batteries mounted in the tower-top equipment cabinet, shortening DC feeder runs and line losses. KITOZER outdoor integrated cabinets (IP55) are purpose-built for this.

7.2 Data Centers (IDC)

Data centers traditionally use UPS (AC uninterruptible). But as IT gear adopts -48V DC internally (servers run on DC internally) and high-voltage DC (HVDC, 240V/336V) spreads, -48V in data centers mainly serves:
– Network zone: core routers, switches, firewalls that natively use -48V.
– Monitoring/communications zone: environment monitoring, BAS, communication links.
– Edge computing nodes: small edge rooms with -48V integrated cabinets.

Large data centers are moving to 240V/336V HVDC, but -48V remains widespread in the network/communications layer.

7.3 Telecom Hubs / Programmed Exchange Rooms

Traditional carrier hub rooms are the home turf of -48V power. A 10,000-line exchange room can draw 1000-2000A, with over twenty 100A rectifiers and thousands of Ah of battery, requiring long backup (8-24h because a hub outage affects millions of subscribers). Such rooms typically use 23-inch racks, dual mains, and diesel generators.

7.4 Fiber Access (FTTx) / Broadband Nodes

Street cabinets, building ONU points, and small access nodes use small -48V power (wall or embedded), with small battery backup. These sites are enormous in number and cost-sensitive; KITOZER small wall-mount power is the workhorse.

7.5 Industry Private Networks (Power / Rail / Mining)

  • Power communication stations: substation comms power, isolated from the plant DC system, uses an independent -48V system.
  • Rail transit: station communications and signaling use -48V per rail-industry standards.
  • Mines / oil fields: explosion-proof or wide-temp outdoor power for harsh environments.

7.6 Application Sizing Quick-Reference

Scenario Load Current Rectifier Config Battery Backup
5G macro site 80A 3×100A (3+1) 48V/300Ah LFP 4h
4G macro site 30A 2×50A (1+1) 48V/150Ah VRLA 6h
Micro site 10A 1×50A wall 48V/50Ah LFP 4h
Aggregation room 300A 4×100A (3+1) 48V/1000Ah VRLA×2 8h
Hub room 1500A 16×100A (15+1) 48V/2000Ah×4 8h
Power comms 50A 2×50A (1+1) 48V/200Ah VRLA 12h

8. Efficiency and Energy: Rectifier Comparison and Sleep Mode

8.1 The Evolution of Rectifier Efficiency

Rectifier efficiency has climbed year by year:
– Phase-controlled (1980s): 80-85%
– Early switch-mode (1990s): 88-91%
– High-frequency ZVS modules (2000s): 92-94%
– Modern high-efficiency (2020s): 96-97%

Each percentage point matters for a 1000A system: output 48kW; at 95% efficiency loss is 2.5kW; at 96% loss is 2.0kW. Annual savings: (2.5-2.0)×8,760 = 4,380 kWh.

8.2 Efficiency vs. Load Curve

Efficiency is not constant—it varies with load. A typical high-efficiency module peaks at 50%-75% load (96%+) and drops at light load (<20%) and full load (>90%). This is the theoretical basis for sleep mode.

8.3 Sleep Mode (Energy Saving Control)

Sleep mode is a standard feature of modern telecom power. When total load is light, the monitor shuts down some rectifiers so that the remaining few run in the high-efficiency zone (50%-75%).

Example: a system has six 100A modules, total load 200A. If all six run, each carries 33A (33% load) at ~93% efficiency. If four sleep and only two run, each carries 100A at ~95% efficiency.

The monitor executes sleep automatically: it reads total load in real time and decides how many modules to keep open so each works near the efficiency optimum. It wakes sleeping modules as load rises and re-sleeps as load falls—seamlessly.

KITOZER monitors support sleep mode, saving 5%-10% of rectifier loss at light-load sites.

8.4 Harmonics and Power Factor

Rectifier power factor (PF) and total harmonic distortion (THDi) affect grid quality. Modern APFC-equipped modules:
– PF ≥0.99 (full load)
– THDi ≤5%

Older units without PFC had PF of only 0.7-0.8 and THDi over 30%, polluting the grid. New projects must specify PFC-equipped high-efficiency modules.

8.5 Energy Calculation and PUE

In a telecom room, air conditioning consumes ~40% of energy, power systems ~30%, and IT load ~30%. Improved power efficiency not only saves electricity but also reduces heat, indirectly reducing air-conditioning load. A 1% efficiency gain cuts cooling load by about 0.3% (all rectifier loss becomes heat).

For a room with annual electricity cost of one million yuan, raising power-system efficiency from 92% to 96% saves about (48kW×0.04×8760h×1)/1000 ≈ 168,000 yuan, plus ~50,000 yuan in cooling—over 200,000 yuan annually.

9. Installation and Commissioning

9.1 Pre-Installation Preparation

  • Room conditions: 15-25°C, humidity ≤75%, clean and dust-free, floor loading adequate for battery weight (VRLA is heavy; a 2000Ah bank can weigh several tons and needs dedicated racks or anti-seismic cabinets).
  • Space: ≥800mm front and ≥600mm rear maintenance clearance; top clearance for ventilation.
  • Mains ready: confirm two mains or one mains plus generator, sized for total rectifier input power.
  • Grounding: room grounding resistance ≤1Ω (bonded); working ground (-48V positive) and protective ground (chassis) run separately and meet at the ground busbar.

9.2 Rack Installation

  1. Position racks per layout, bolt to floor with M12 expansion bolts (or parallel to column headers).
  2. Verticality deviation ≤3mm; top alignment across the row.
  3. Connect AC feeder (correct phase sequence A/B/C/N/PE).
  4. Connect DC busbars to battery bank and load column headers.
  5. Install rectifier modules (not fully populated until commissioning).
  6. Install monitor, connect sensor wiring (temperature, voltage sense).

9.3 Commissioning Steps

  1. No-load check: no battery, no load; close AC input; measure rectifier output (should be float setpoint 53.5V); verify module display.
  2. Single-module test: insert modules one by one; verify consistent output and current sharing.
  3. Battery connection: confirm battery voltage is close to bus voltage (difference ≤2V), then close battery breaker. Monitor should recognize the battery; float current normal.
  4. Load connection: close load breakers in stages; monitor shows total current within rating; branch currents within breaker ratings.
  5. Alarm test: simulate mains failure (break mains); confirm battery discharge, SLD action, alarm upload; restore mains; confirm rectifiers auto-restart and battery boost-charges.
  6. Parameter setting: set float voltage, boost voltage, SLD/FLD thresholds, battery capacity, temperature compensation, alarm thresholds.
  7. Integration test: interface with environment monitoring; confirm dry-contact / RS485 data upload.

9.4 Installation Cautions

  • Never reverse polarity: in -48V the positive is grounded; reversal puts the whole system at -48V and can burn gear. Verify with a multimeter after wiring.
  • DC cable cross-section: size by current density (typically 2-4 A/mm²); high-current busbars use copper bars. Voltage drop budget: battery to rectifier bus ≤0.5V, bus to farthest load ≤0.5V.
  • Battery rack grounding: VRLA racks grounded, but cells must not short to the rack.
  • Cooling path: rectifiers draw front, exhaust rear; keep front and rear unobstructed.

10. Maintenance and Inspection

10.1 Monthly Inspection

  • Read monitor: DC voltage, load current, battery current, temperature normal.
  • Listen: rectifier fan for abnormal noise.
  • Look: cabinet for discoloration/heat, cable damage, battery swelling/leakage.
  • Review: unresolved historical alarms.

10.2 Quarterly Maintenance

  • Measure each rectifier’s output current; check sharing imbalance (should be ≤±5%).
  • Measure per-cell VRLA voltage; flag cells deviating >0.05V.
  • Clean rectifier filter mesh / fan intake (dusty sites).
  • Check SPD indicator window (green = OK, red = replace).

10.3 Annual Maintenance

  • Battery capacity test: discharge a VRLA string by 30%-50% to assess SOH. Strings below 80% rated capacity go on the replacement list.
  • Check breaker contacts and terminals for looseness/heating (infrared thermography).
  • Calibrate monitor voltage/current sampling.
  • Check grounding and SPD.
  • Clean interior dust.

10.4 Common Faults and Remedies

Symptom Likely Cause Remedy
Rectifier no output AC feed open, module fault, fan jam Check AC breaker, replace module, clean fan
Bus voltage low Overloaded, battery discharging, undersized modules Check load current, mains, add modules
Battery charge current too high Battery short circuit, boost set too high Check battery string, adjust boost voltage
Poor current sharing Aged module, loose share bus Check share bus, replace aged module
Frequent alarms Drifting temp sensor, bad thresholds Calibrate sensor, adjust thresholds
Battery swelling/leak Overcharge, over-temperature, end-of-life Replace string, check charge params

10.5 Battery Replacement Cycles

  • VRLA: design life 5-8 years (float at 25°C); actual life shortens to 3-5 years at 30°C room temperature. Recommend capacity assessment at 5 years, mandatory replacement at 8.
  • LFP: design life 10-15 years (at 60% capacity retention); actual over 10 years.

11. Sizing Calculation

11.1 Load Estimation

The first step is to list every device on the -48V bus and its rated power. Note: nameplate is maximum; actual running power is often 60%-80%.

Load current: I_load = P_total / V_dc

Example: one BBU at 500W, two AAUs at 1200W each, transmission at 200W, monitoring at 100W. Total = 500+2400+200+100 = 3200W. Current = 3200/48 ≈ 66.7A.

11.2 Rectifier Sizing

Total rectifier capacity must:
– Supply the load
– Simultaneously charge the battery (charge current typically 0.1C, e.g., 40A for a 400Ah battery)

Total rectifier output = load current + battery charge current

Example: load 66.7A, 400Ah battery charge current 40A → need 106.7A. Choose 100A modules: N=ceil(106.7/100)=2, plus 1 redundant = 3 modules (2+1). System capacity 300A with ample headroom.

11.3 Battery Sizing

Per section 5:
C = P_total × T_backup / (V_avg × η × K_rate × K_temp)

Example: P=3200W, T=4h, V_avg=48V, η=0.85 (VRLA), K_rate=0.7 (4-hour rate), K_temp=0.9 (20°C room):
C = 3200×4/(48×0.85×0.7×0.9) = 12800/25.7 ≈ 498Ah

Choose a standard 500Ah VRLA string.

11.4 Distribution Breaker Sizing

Each branch breaker by that branch’s rated current:
– Rated current = branch total current × 1.25
– DC rated voltage ≥60V
– Interrupting rating ≥ battery short-circuit current (roughly: Ah × 5 = short-circuit amps; e.g., 400Ah ≈ 2000A)

11.5 Cable Sizing

DC voltage drop budget ≤0.5V (battery to load total):
S = 2 × I × L / (ΔU / ρ)

where S is cross-section (mm²), I current (A), L one-way length (m), ΔU allowable drop (V), ρ copper resistivity (0.0184 Ω·mm²/m).

Example: I=100A, L=30m, ΔU=0.5V:
S = 2×100×30/(0.5/0.0184) = 6000/27.2 ≈ 220mm²

Use two 120mm² cables in parallel or a 240mm² copper bar.

11.6 Sizing Decision Tree

  1. Sum load power → load current
  2. Set backup time T → battery capacity C
  3. Rectifier capacity = load current + 0.1C → module count (N+1)
  4. Branch breakers by branch current
  5. Cable cross-section by voltage drop
  6. Rack spec (19/23″, capacity tier)
  7. Battery chemistry (VRLA/LFP)
  8. Monitor config (local/remote/EMS integration)

12. FAQ (30 Questions)

Q1: Why -48V and not +48V?
A: Positive grounding reduces electrochemical corrosion on cable sheaths and is compatible with a century of legacy equipment. It is the historical optimum under corrosion, safety, and compatibility constraints.

Q2: What is the normal -48V operating range?
A: Nominal -48V; float about -53.5V; boost about -56.4V; normal range -38.4V to -57.6V; equipment minimum about -40V.

Q3: What does N+1 redundancy mean?
A: N modules carry the load, plus one standby. If any one module fails, the remaining N still carry full load.

Q4: Can rectifiers be hot-swapped?
A: Yes. KITOZER modules support hot swap with soft-start and anti-keying—replace without powering off.

Q5: What is the allowed current-sharing imbalance?
A: Industry standard ≤±5%. Beyond that, a module is aging or the share bus is faulty.

Q6: How are FLD and SLD divided?
A: FLD feeds critical services (main control, RF, transmission), disconnected only near end-of-discharge. SLD feeds auxiliary gear (AC, lighting), disconnected at -46V.

Q7: How is backup time calculated?
A: T = C×V×η/P. C is battery Ah, V average 48V, η discharge efficiency, P load watts.

Q8: VRLA or LFP?
A: Indoor staffed rooms choose VRLA (mature, cheap); outdoor/5G/rooftop choose LFP (light, long life, temperature-tolerant).

Q9: How does temperature affect battery capacity?
A: Lead-acid at 25°C baseline; at 0°C about 80%, at -10°C about 60%. Oversize for cold sites.

Q10: Why float-voltage temperature compensation?
A: Every 1°C rise, lead-acid float voltage should drop 3mV/cell to prevent high-temperature overcharge and drying.

Q11: Is 96% rectifier efficiency good?
A: State of the art. Phase-control era was ~80%, early switch-mode 91%, modern high-efficiency 96%+.

Q12: Does sleep mode help?
A: Yes. At light load, shutting extra modules lets the rest run in the 50%-75% high-efficiency zone, saving 5%-10%.

Q13: Why can’t AC breakers replace DC breakers?
A: DC has no zero crossing; AC breakers cannot extinguish DC arcs and will arc-fire. Use DC-specific breakers.

Q14: Why a 2-pole breaker on the input?
A: In -48V the positive is grounded; cutting only the negative leaves the positive grounded at a potential, creating a shock risk during service. A 2-pole breaker cuts both.

Q15: What is noise voltage and why does it matter?
A: AC ripple on the rectifier output. Excess noise introduces audio hum in analog circuits or bit errors in digital circuits. Weighted noise standard ≤2mV.

Q16: 19″ or 23″ rack?
A: New builds choose 19″ (universal); retrofits of legacy PT rooms choose 23″. 23″ fits more modules at the same height.

Q17: Will a monitor failure cause an outage?
A: No. The monitor carries no power current; if it crashes, rectifiers continue at default parameters.

Q18: Is dual mains mandatory?
A: Core rooms recommend dual mains or one mains plus diesel. Ordinary single-mains sites rely on battery backup.

Q19: Can I use a swollen battery?
A: No. Swelling indicates internal drying or overcharge; replace the whole string—fire risk.

Q20: Can I mix old and new batteries?
A: Not recommended. Different internal resistances cause circulating current and accelerate weak cells. Replace the whole string.

Q21: How much does room temperature affect battery life?
A: Lead-acid life halves for every 10°C rise. At 30°C, life is about half that at 25°C.

Q22: Can -48V power +48V equipment?
A: Depends. Most modern gear supports -40V to -60V with polarity auto-sense, but legacy gear may not.

Q23: Do rectifier fans need maintenance?
A: Fan life is 5-7 years; clean annually in dusty sites. A failed fan causes over-temperature derating or shutdown.

Q24: How often to replace SPD?
A: When the indicator window turns red (failed) or after a lightning strike; preventive replacement every 3-5 years.

Q25: How often to do a battery capacity test?
A: VRLA: annual 30%-50% discharge check; full capacity test every 3 years.

Q26: How to identify a weak battery?
A: After charge completion, an individual cell whose terminal voltage is notably lower (deviation >0.05V/cell) or whose voltage sags fastest on discharge is weak.

Q27: How to locate a DC ground fault?
A: In -48V the positive is normally grounded; if the negative also grounds, it forms a short. Use a ground-fault locator and trip branches one by one.

Q28: What grounding resistance is required?
A: Bonded system ≤1Ω; separate working ground ≤4Ω.

Q29: Does KITOZER support remote monitoring?
A: Yes. Standard RS485/Modbus; optional Ethernet/SNMP to feed the environment monitoring or NMS.

Q30: Can the system be expanded?
A: Yes. The rack has spare module slots and the battery room has spare parallel positions. Add modules and batteries as load grows.

13. Industry Standards

13.1 Domestic Standards

  • YD/T 1095 (Uninterruptible Power Supply for Telecom): sets power-quality requirements referenced by -48V DC systems.
  • GB/T 19826 (Technical Requirements for Telecom Power Systems): general system requirements and test methods.
  • YD/T 585 (Telecom Distribution Equipment): DC distribution equipment requirements.
  • YD/T 731 (Telecom High-Frequency Switch Rectifier): rectifier module standard.
  • YD/T 799 (Telecom VRLA Battery): VRLA standard.
  • GB 50689 (Design Code for Protection and Grounding of Telecom Stations): grounding and surge protection.

13.2 International Standards

  • ITU-T L series: telecom station power standards.
  • ETSI EN 300 132-3-1: power supply environment for telecom equipment.
  • IEC 60950 / IEC 62368: IT equipment safety.

13.3 Key Specification Comparison

Parameter YD/T Requirement KITOZER Design
Voltage regulation ≤±1% ≤±0.6%
Current regulation ≤±1% ≤±1%
Weighted noise ≤2mV ≤1.5mV
Peak-to-peak noise ≤400mV ≤300mV
Sharing imbalance ≤±5% ≤±3%
Efficiency ≥90% (rated) ≥96%
Power factor ≥0.9 (rated) ≥0.99

Appendix A: Grounding and Surge Protection Design

A.1 The Three Grounds in a Telecom Room

When engineers first encounter telecom power, the most confusing topic is “ground.” There are actually three distinct grounds in a telecom room, and understanding their relationship is essential.

The first is the working ground (-48V positive grounded). This is required by the -48V system itself. The positive terminal of the battery bank is not floating; it connects via a dedicated wire to the room’s ground busbar (often called the indoor grounding copper bar). This wire carries current in normal operation—all telecom equipment’s 0V terminal connects to this ground, and the equipment’s return current flows through this wire back to the battery positive. Therefore, the working ground wire must be substantial, typically no smaller than 35mm² copper, or a copper bar in large rooms.

The second is protective ground (cabinet chassis ground). All metal cabinets, battery racks, and cable trays connect to protective ground to clamp the chassis at earth potential during insulation faults, preventing electric shock.

The third is surge ground (SPD ground). Power and signal line surge protective devices (SPDs) connect to the ground busbar with the shortest possible path, to divert lightning surge current to earth.

These three grounds ultimately converge at the same ground busbar, then through down conductors to the building’s bonded earth electrode. This is called “bonded grounding”—working, protective, and surge grounds share one electrode, with grounding resistance required ≤1Ω.

A.2 Why Working and Protective Ground Must Not Be Mixed

Although bonded, within a cabinet the working ground and protective ground must run separately and only converge at the busbar. If they share a wire, the normal return current creates voltage drops on the shared impedance, which superimposes on the chassis and disturbs sensitive equipment. Telecom signal ground is extremely sensitive to interference.

KITOZER cabinets internally provide two independent copper bars: one for working ground (-48V positive), one for protective ground (chassis), each running to the room’s main ground bar.

A.3 DC Ground Fault

A special fault in -48V systems is the “DC ground fault.” Because the positive is normally grounded, if the negative also accidentally grounds, the positive and negative form a loop through earth. This may not immediately short circuit (earth resistance is relatively high), but it creates two hazards: a second ground fault on the positive side becomes a direct short, and the chassis (at positive/0V) develops a potential difference relative to earth.

DC ground faults cannot be detected by ordinary breakers; a dedicated “DC ground fault locator” is used. It injects a low-frequency signal and probes each branch with a clamp sensor to locate the fault. KITOZER monitor modules can optionally include DC insulation monitoring, continuously measuring positive-to-ground and negative-to-ground resistance and alarming below threshold.

A.4 Three-Stage Surge Protection

Telecom rooms use three-stage protection:
– Stage 1 (building entrance): B-class SPD at the main distribution, discharge capacity ≥100kA per mode.
– Stage 2 (room distribution): C-class SPD at the room AC cabinet, ≥40kA per mode. KITOZER power cabinets include C-class SPD with failure indicator as standard.
– Stage 3 (equipment ports): Signal SPDs at telecom equipment signal and antenna ports.

On the DC side, DC SPDs can be added at the battery input and load output to prevent induced surges on DC cables.

Appendix B: Multi-Cabinet Parallel Systems

B.1 Why Parallel Cabinets

When system capacity exceeds a single cabinet’s maximum (e.g., DPS-2000 at 2000A), or when multiple column headers need dual feeds, cabinets operate in parallel. Benefits include: phased expansion, higher redundancy (one cabinet fully down, the other still carries full load if sized), and fault isolation.

B.2 Technical Conditions

DC paralleling is not simply wiring two outputs together. Requirements:
– Identical output voltage: float setpoints must match within ±0.05V, otherwise one cabinet circulates current into the other.
– Share bus interconnection: monitor modules exchange output current data and dynamically trim voltage.
– Correct polarity absolutely: reversing polarity creates a direct short between cabinets, with enormous current destroying busbars and breakers.
– Adequate paralleling cable: sized for circulating and load-transfer current.

B.3 Dual-Bus Architecture

In high-reliability rooms, dual-bus (Bus A and Bus B) architecture is used: two independent DC buses, each powered by one power cabinet. Critical equipment has two power modules, one on each bus. This achieves 2N-equivalent reliability. KITOZER DDP rack-top panels are designed for dual-bus: primary input on Bus A, backup on Bus B.

Appendix C: Modbus Protocol and Data Acquisition

C.1 Physical Layer

KITOZER monitor modules use RS485 physical layer with Modbus-RTU protocol. Default baud 9600 (configurable 1200-115200). Data format: 8 data bits, 1 stop bit, no parity or even parity. The bus uses daisy-chain topology, max 32 slaves (expandable to 128 with repeaters), 120Ω termination at both ends.

C.2 Key Holding Registers (Sample)

Address Meaning Unit Access
0x0001 DC bus voltage 0.01V Read
0x0002 Total load current 0.1A Read
0x0003 Battery current 0.1A (+charge/-discharge) Read
0x0004 Battery voltage 0.01V Read
0x0005 Ambient temperature 0.1°C Read
0x0010 Rectifier module 1 current 0.1A Read
0x0020 Float voltage setpoint 0.01V RW
0x0021 Boost voltage setpoint 0.01V RW
0x0022 FLD voltage threshold 0.01V RW
0x0023 SLD voltage threshold 0.01V RW
0x0024 Battery capacity setpoint 1Ah RW
0x0030 System status bitmap – Read

C.3 Dry Contacts

The monitor provides 8 dry-contact alarm outputs: total alarm, AC fail, DC overvoltage, battery low, rectifier fault, battery fuse blow, door open, over-temperature. These directly feed environment monitoring switch-input modules without protocol conversion.

Appendix D: Three Complete Sizing Case Studies

D.1 Case 1: 5G Macro Site (Outdoor Cabinet)

Requirement: One BBU (500W) + two AAUs (1200W each) + transmission (200W) + monitoring (50W). 4-hour backup after mains failure. Outdoor cabinet.

Step 1: Load current: P = 500+2400+200+50 = 3150W; I = 3150/48 ≈ 65.6A.

Step 2: Battery (LFP, outdoor/weight-sensitive): C = 3150×4/(48×0.95×0.9×0.95) ≈ 324Ah. Choose 48V/300Ah LFP cabinet (actual backup ~3.7h).

Step 3: Rectifier: charge current 0.1C = 30A; total = 65.6+30 = 95.6A. Choose 100A modules: N=1, plus 1 redundant = 2 modules (1+1).

Step 4: Distribution: FLD (BBU+AAU+transmission, 60A) on 100A breaker; SLD (monitoring+fan, 8A) on 16A; battery disconnect 125A.

BOM: KITOZER-DPS-200 outdoor IP55 cabinet, 2×100A rectifier, 1×48V/300Ah LFP, monitor with RS485+dry contacts. Budget ~40,000 RMB.

D.2 Case 2: Aggregation Room (Indoor, Dual Mains)

Requirement: Transmission 30kW + data 20kW + security 5kW. 2-hour backup (diesel generator starts in 5 minutes).

Load current: P=55000W; I=55000/48 ≈ 1146A.

Battery (VRLA, indoor): C = 55000×2/(48×0.85×0.7×0.9) ≈ 4280Ah. Choose 3× 48V/2000Ah VRLA strings in parallel (6000Ah, backup ~2.8h).

Rectifier: charge 200A; total 1346A; 100A modules: N=14, plus 1 = 15. Use two DPS-1000 cabinets in parallel, 8 modules each.

Distribution: 6 column headers at ~190A each, 250A breakers; 60 DDU rack-top units.

D.3 Case 3: Small Access Point (Wall Mount)

Requirement: ONU (100W) + router (50W). 4-hour backup. Wall mount.

Load: 150W, I≈3.1A.
Battery: C = 150×4/(48×0.85×0.8×0.9) ≈ 20Ah; choose 48V/24Ah VRLA wall battery.
Rectifier: 5.5A needed; one 50A module (no redundancy for cost).
BOM: DPS-100 wall power, 1×50A module, 48V/24Ah battery, simple monitor. Budget ~3,500 RMB.

Appendix E: Common Design Mistakes and Incident Cases

E.1 Using AC Breakers for DC

Incident: A site retrofit used AC C63 breakers on DC output. Six months later, a branch short-circuited; the AC breaker could not extinguish the DC arc, arcing continued for seconds, the housing melted, igniting nearby cables, causing a 6-hour outage.

Lesson: DC has no zero crossing; AC breakers cannot interrupt DC arcs. Use DC-specific breakers (ABB S200M UC, Schneider C120H DC) rated ≥60V DC.

E.2 Mixing Old and New Batteries

Incident: Two weak cells in a battery string were replaced with new ones; the rest were 8 years old. Three months later, the new cells were dragged down by old ones (different internal resistance causes circulating current), and the new cells swelled; the whole string was scrapped.

Lesson: Replace entire strings. Mixed-age cells cause circulating current and mutual damage.

E.3 Wrong Float Voltage

Incident: A new room’s engineer set float voltage to 56.4V (boost voltage) and left it. After a year, batteries were severely dehydrated, cases swollen, capacity down to 30%.

Lesson: Float is 53.5V (25°C), boost is 56.4V. Temperature compensation 3mV/cell/°C.

E.4 Undersized Cable

Incident: A site ran 50m of 16mm² cable from ground-floor battery to rooftop power cabinet. Remote equipment read only 44V, causing low-voltage alarms.

Calculation: ΔU = 2×60×50×0.0184/16 = 6.9V, far exceeding 0.5V budget.

Fix: Move battery closer or use 70mm² cable.

Appendix F: Busbars, Cables, and Voltage Drop

F.1 DC Busbar Design

Internal DC busbars use T2 copper (tinned). Current density 1.5-2.5A/mm² (temperature rise ≤30°C). For a 1000A system, minimum 500mm²; typically 40×15mm (600mm²) copper bar, one positive one negative.

Lapped joints must be tinned or silver-plated, torqued with a wrench (M10 ~20N·m), and coated with conductive grease.

F.2 Cable Sizing

DC cables use flame-retardant copper (ZR-YJV or ZR-RVV). Size by both ampacity and voltage drop:
– 10mm² ~50A, 16mm² ~70A, 25mm² ~95A, 35mm² ~125A, 50mm² ~155A, 70mm² ~200A, 95mm² ~250A, 120mm² ~300A.

Voltage drop: ΔU = 2×I×L×ρ/S, total ≤0.5V from battery to farthest load.

F.3 Cable Routing

  • Positive and negative cables run parallel and tight (reduce loop area and EMI).
  • DC and AC cable trays separated ≥200mm, perpendicular at crossings.
  • Firestop at floor/wall penetrations.
  • Both ends labeled with circuit number, polarity, destination.
  • Battery cables short and thick.
  • Bending radius ≥10× cable diameter.

Appendix G: Rectifier Topology Evolution

G.1 Four Generations

Gen 1: Phase-controlled SCR (1980s): simple, reliable, but bulky (50Hz transformer), 80-85% efficiency, PF 0.7-0.8, high harmonics. Largely obsolete.

Gen 2: Early high-frequency hard-switch PWM (1990s): 20-30kHz transformer, half the size, ~90% efficiency, but high switching loss and EMI.

Gen 3: Phase-shift full-bridge soft-switching (PSFB) (2000-2015): ZVS via resonant inductor and transformer leakage, 93-95% efficiency.

Gen 4: LLC resonant + synchronous rectification (2015+): full-range ZVS, 96-97% efficiency, minimum low-side loss. This is what KITOZER high-efficiency modules use.

G.2 Why LLC Is Efficient

LLC resonant converter achieves: ZVS on primary switches (near-zero switching loss), ZCS on secondary rectifiers (no reverse-recovery loss), integrated magnetics, variable-frequency control. KITOZER’s 48V/50A module (~2.4kW) exceeds 96% efficiency.

G.3 The Future: SiC and GaN

Silicon carbide (SiC) devices switch 5-10× faster than silicon MOSFETs, enabling 500kHz+ operation, half the transformer size, and >98% efficiency. Currently 2-3× the cost, used in high-end HVDC. Expected mainstream by 2028-2030.

Appendix H: Battery Chemistry and Deep Maintenance

H.1 VRLA Internal Construction

A VRLA battery consists of: positive plate (PbO₂ active material on lead-calcium grid, brown), negative plate (sponge lead, gray), AGM separator (absorbs electrolyte, isolates plates), diluted sulfuric acid electrolyte (absorbed, non-flowing), ABS flame-retardant sealed case, and a one-way safety valve (opens at 20-50kPa).

Discharge: PbO₂ + Pb + H₂SO₄ → PbSO₄ + H₂O (both plates become lead sulfate, acid weakens).
Charge: PbSO₄ + H₂O → PbO₂ + Pb + H₂SO₄.

H.2 Why VRLA Is Maintenance-Free

Flooded batteries lose water through electrolysis during charging and need topping up. VRLA achieves sealed operation through:
– Starved electrolyte: acid absorbed in AGM, non-liquid.
– Oxygen recombination: oxygen generated at the positive plate diffuses through AGM pores to the negative and recombines back into water, so water is not lost.

Only severe overcharge or high temperature causes hydrogen evolution and valve opening. This is why float voltage and temperature control battery life.

H.3 VRLA Failure Modes

  1. Dry-out: overcharge/high temperature vents water, electrolyte dries, internal resistance spikes, capacity collapses. Prevent by accurate float voltage and 25°C room.
  2. Positive grid corrosion: slow oxidation of the lead-calcium grid, determines design life (5-8 years).
  3. Sulfation: chronic undercharge leaves coarse, insoluble lead sulfate crystals; capacity drops.
  4. Thermal runaway: overcharge increases current, heating increases, current increases further—vicious cycle up to 80°C+, case swelling. Disconnect immediately.

H.4 LFP Battery Management System

The LFP BMS monitors every cell voltage (±5mV), controls contactors on overvoltage/undervoltage/overcurrent/overtemperature, performs passive or active cell balancing, estimates SOC and SOH, and communicates via RS485/CAN to the power monitor.

H.5 Battery Installation Cautions

  • Use a cart; do not roll or throw. A 200Ah cell weighs ~13kg.
  • Torque connection bolts per spec (M8 ~8-10N·m).
  • Rack level, 3-4 shelves, bottom ≥150mm above floor.
  • Connect positive bars first; final system polarity cable last. Reverse for removal.
  • Wear goggles and gloves.
  • Leave 5-10mm gap between cells for cooling.

Appendix I: 5G AAU Power Delivery

I.1 5G AAU Power Characteristics

A 5G AAU (64-channel massive MIMO) draws 1000-1500W, peaking 1800W—2-3× a 4G RRU. A typical 5G macro site: one BBU (500W) + three AAUs (1200W each) = ~4100W, ~85A. Nearly 3× a 4G site (~30A).

I.2 Power Delivery Methods

Method 1: Direct -48V DC feeder from room/tower cabinet to rooftop AAU. Mature, but 30-40m tower height needs thick cable (35-50mm²).

Method 2: Remote power unit (DPU): a small rectifier/DC-DC at tower base boosts to 480V for the run, then steps down at the AAU. Thinner cable, lower loss, but one more device and failure point.

I.3 Voltage Drop Calculation

Tower height 35m, AAU 1200W (25A@48V):
– 25mm² cable: ΔU = 2×25×35×0.0184/25 = 1.29V. At 48V battery end, AAU gets 46.7V—within its -40V to -57V range.
– 16mm²: ΔU = 2.0V; at end of discharge AAU gets 46V, acceptable but low.

Design rule: AAU terminal voltage must not drop below 44V under any condition.

I.4 KITOZER 5G Site Cabinet

Recommended: 3×100A rectifier (2+1 redundancy), 48V/300Ah LFP (4h backup), output branches: 3×50A for AAUs, 1×32A for BBU, 1×16A for transmission. Outdoor cabinet IP55 with heat exchanger or semiconductor AC.

Appendix J: Outdoor Cabinet Environmental Control

J.1 Why Temperature Control Matters

Outdoor cabinets in direct sunlight can reach 60-70°C inside. Rectifier modules derate above 45°C; VRLA life halves for every 10°C rise; LFP cycle life drops sharply above 45°C.

J.2 Three Control Methods

Method Load Range Effect Cost Maintenance
Heat exchanger <1kW 5-10°C above ambient Low Maintenance-free
Thermoelectric AC (TEC) 1-3kW Internal 30°C Medium Fan ~5yr
Vapor-compression AC >3kW Internal 25°C High Compressor 8-10yr

KITOZER outdoor cabinets: 1.5mm galvanized steel, outdoor powder coat, IP55, standard heat exchanger (TEC AC optional), internal LED light on door-open, door contact/humidity/water leakage sensors, 4-6 rectifier slots plus two battery positions.

Appendix K: EMC Design

K.1 Sources of Interference

Rectifiers generate conducted emissions on the AC line (150kHz-30MHz, limited by YD/T 983), radiated emissions, and harmonic current (5th, 7th, 11th) suppressed by APFC.

K.2 KITOZER EMC Measures

  • Input EMI filter (common-mode choke + X/Y capacitors).
  • Shielded metal module housing grounded.
  • Soft switching reduces switching spikes.
  • Isolation transformer with shielding layer cuts common-mode coupling.
  • Compact PCB layout minimizing power loop area.

KITOZER weighted noise ≤1.5mV, better than the 2mV YD/T requirement.

Appendix L: Testing and Acceptance

L.1 Factory Tests

Every KITOZER cabinet passes: visual inspection, insulation resistance (≥10MΩ at 500V megger), dielectric withstand (1500V AC/1min), functional test (startup, regulation, sharing, protection), noise voltage measurement, efficiency test, and monitor/communication test.

L.2 Site Acceptance

  1. Installation check (verticality, grounding, wiring, labels).
  2. Power-on test (no-load → half → full).
  3. Battery discharge test (verify backup time).
  4. Alarm simulation (AC fail, module fault, low battery).
  5. Insulation test.
  6. Document handover (as-built drawings, test reports, manual).

L.3 Acceptance Criteria

  • Voltage regulation ≤±1%.
  • Weighted noise ≤2mV.
  • Sharing imbalance ≤±5%.
  • Battery backup meets design (measured ≥90% of design value).
  • All alarms correctly upload to environment monitoring.
  • Insulation ≥10MΩ.

Appendix M: Cost and TCO Analysis

M.1 CAPEX for a 400A Aggregation Room

  • Two power cabinets: 2×15,000 = 30,000 RMB.
  • Eight rectifier modules: 8×3,500 = 28,000 RMB.
  • VRLA battery (2000Ah): ~60,000 RMB.
  • Column headers + DDUs: ~20,000 RMB.
  • Installation: ~15,000 RMB.
  • Total ~153,000 RMB.

M.2 OPEX

  • Electricity: ~2kW loss × 8760h = 17,520 kWh ≈ 17,500 RMB/year.
  • Battery replacement: every 5-8 years, 60,000 RMB, ~8,000/year.
  • Maintenance/parts: ~5,000/year.
  • ~30,500 RMB/year.

M.3 High-Efficiency vs Standard Modules

Item Standard (91%) High-Eff (96%)
Module unit price 3,000 RMB 4,500 RMB
8-module price premium – +12,000 RMB
Annual loss kWh 18,400 8,760
Annual electricity saved – 9,640 RMB
Payback – ~1.2 years

M.4 LFP vs VRLA 10-Year TCO

Item VRLA 2000Ah LFP 2000Ah
Upfront 60,000 RMB 120,000 RMB
Life 5 years 10 years
Replacements in 10y 2 1
10y battery total 120,000 120,000

Over 10 years, total cost is similar, but LFP saves space and weight.

Appendix N: Reliability (MTBF) and Availability

N.1 MTBF Calculation

MTBF (Mean Time Between Failures) is the core reliability metric; telecom power requires MTBF ≥100,000 hours (~11.4 years). System failure rate is the sum of component failure rates:

λ_system = Σλ_i

Example: rectifier MTBF 500,000h (λ=2e-6), monitor 200,000h (λ=5e-6), battery 200,000h (λ=5e-6), breaker 1,000,000h (λ=1e-6).
System λ = 13e-6/h; MTBF ≈ 77,000h.

N.2 How N+1 Improves Reliability

Two parallel modules (1+1): system failure probability = (1-R)² = (1-0.99)² = 0.0001, reliability = 99.99%. N+1 raises annual reliability from 99% to 99.99%.

N.3 Availability

Availability = MTBF / (MTBF + MTTR). Hot-swap modules cut MTTR to 15 minutes. Target: 99.999% availability (annual downtime <5 minutes).

Appendix O: Battery and Air Conditioning Coordination

Battery life halves per 10°C rise. Room AC failure at 35°C instead of 25°C cuts VRLA life from 8 to 4 years. KITOZER monitors mount temperature sensors on the rack, alarm above 30°C, and derate charge above 35°C. Best practice: separate battery room at 20-25°C from equipment room.

Appendix P: International Export Considerations

P.1 Voltage and Frequency

  • China/Europe: 220V/50Hz. US/Japan: 120V/60Hz. Southeast Asia: 220V/50Hz. Middle East: 220V/50Hz.
  • KITOZER rectifiers are wide-input (85-300V AC, 45-65Hz), globally universal. Mains plugs and breakers must match destination standards (CEE/NEMA/BS).

P.2 Certifications

  • Europe: CE (LVD + EMC). US: UL. Southeast Asia/Middle East: CB report plus local cert. Operators may require vendor onboarding approval.
  • KITOZER products carry CE; UL in progress.

P.3 Shipping and Customs

  • Batteries are dangerous goods (UN3480 Li-ion / UN2794 lead-acid), requiring DG containers, MSDS, UN38.3.
  • Tariffs vary; provide commercial invoice, packing list, certificate of origin.

Appendix Q: Expanded FAQ

Q31: Is KITOZER power suitable for unattended sites?
A: Fully. The monitor uploads all alarms via dry contacts/RS485; modules and batteries are maintenance-free; remote alarm allows scheduled maintenance.

Q32: Can VRLA and LFP batteries share one system?
A: Not recommended. Their charge curves, voltage platforms, and management differ. Use one chemistry per system.

Q33: How long do rectifier fans last?
A: Design life 50,000-70,000 hours (~6-8 years). Replace on fan-fault alarm or abnormal noise.

Q34: Do batteries need surge protection?
A: Battery cables can carry induced surges; add DC SPD at the battery input.

Q35: How long can batteries hold a mains outage?
A: By the formula in section 5: typically 4-8h for base stations, 8h+ for central offices (with generator).

Q36: Is -48V dangerous?
A: 48V is safety extra-low voltage in dry conditions; normal contact is not lethal. But always power off before working.

Q37: Can solar power a -48V system?
A: Yes. A solar controller outputs -48V onto the bus as mains supplement. Remote sites commonly use hybrid PV + battery + rectifier.

Q38: How is efficiency measured?
A: Wattmeter measures AC input power and DC output power; ratio is efficiency, taken after thermal stabilization.

Q39: Why test battery capacity?
A: Capacity decays over time; you won’t know actual backup until an outage—too late.

Q40: What if the monitor crashes?
A: Power continues. Rectifiers run at default parameters. Remote reset or local power-cycle the monitor.

Q41: Why bus capacitors?
A: Electrolytic capacitors (400-1000µF) on the bus stabilize voltage, filter high-frequency ripple, and absorb transient load steps.

Q42: What is current sharing and why?
A: Paralleled modules share load current evenly; imbalance causes individual overheating and shortened life.

Q43: Why limit charge current?
A: Fast high-current charging gasses and heats the battery. VRLA charge limit 0.1-0.25C; LFP within 0.5C.

Q44: Room humidity requirement?
A: 40-75% RH. Too dry causes static; too damp causes condensation.

Q45: Why must batteries stand upright?
A: The safety valve faces up; tilting or inverting causes electrolyte leakage and valve failure.

Q46: KITOZER warranty?
A: Rectifiers 5 years, monitor 3 years, VRLA 3 years, LFP 5 years, cabinet 3 years.

Q47: Can you customize voltage/current?
A: Yes. Special output (-60V, -24V), special branch counts, special cabinet dimensions.

Q48: How to label FLD vs SLD cables?
A: FLD in red or “FLD” tags; SLD in blue or “SLD” tags; strictly separated.

Q49: Can KITOZER integrate with Huawei/ZTE environment monitors?
A: Yes. Standard Modbus protocol and register table; any Modbus-compatible platform integrates.

Q50: What information do you need to quote?
A: Load list (power/voltage), backup time, installation environment (indoor/outdoor/temperature), AC mains situation, monitoring interface requirements.

Appendix R: Complete Specification Quick Reference

Category Parameter Value
DC Nominal voltage -48V
DC Adjustable range -42V to -59.5V
DC Normal range -38.4V to -57.6V
DC System capacity 100A-2000A
DC Voltage regulation ≤±0.6%
DC Current regulation ≤±1%
DC Weighted noise ≤1.5mV
AC Input voltage 85-300V AC wide range
AC Frequency 45-65Hz
AC Power factor ≥0.99
AC THDi ≤5%
Efficiency Rated ≥96%
Module Rating 50A/100A
Module Redundancy N+1
Module Sharing imbalance ≤±3%
Battery VRLA 48V/100-2000Ah
Battery LFP 48V/50-300Ah
Battery Temp compensation 3mV/cell/°C
Protection OV/UV/OC/SC Full
Protection Surge C-class SPD
Monitor Display LCD CN/EN
Monitor Comm RS485/Modbus/Ethernet
Structure Rack 19″/23″
Structure Protection IP20 indoor / IP55 outdoor
Environment Temp -5°C to +45°C (wide -30°C to +55°C)
Standard Compliance YD/T 731, GB/T 19826, CE

Appendix S: -48V DC vs UPS

Item -48V DC Telecom UPS AC
Output -48V DC 220/380V AC
Battery connection Direct parallel on bus Via inverter
Transfer time 0ms 0-4ms
Efficiency 96% 94-96%
Battery voltage 48V 192/240/384V
Complexity Simple (low-voltage DC) Complex (inverter)
Load Native telecom gear IT servers

Telecom gear natively runs low-voltage DC, so -48V supply skips an extra AC-DC conversion. Data centers are now returning to rack-level 48V DC to gain efficiency.

Appendix T: Inspection Checklist

Monthly

DC voltage 53.3-53.7V; load current ≤80% rated; battery voltage/float current; module temp <60°C; room temp 15-28°C; humidity 40-75%; no open alarms; fan sound normal; no discoloration/odor.

Quarterly

Module current imbalance ≤±5%; VRLA cell voltage deviation ≤0.05V; SPD window green; terminals tight; filters clean.

Annual

Battery capacity test ≥80% rated; insulation ≥10MΩ; noise ≤2mV; ground resistance ≤1Ω; all breakers torqued.

Appendix U: Worked Calculation Examples

Cable drop: I=100A, L=20m, 35mm²: ΔU = 2×100×20×0.0184/35 = 2.1V (too high). Use 95mm²: 0.77V. Two 50mm² parallel: 0.74V.

Backup time: 48V/500Ah battery, 2000W load, η=0.85, K=0.8: T = 500×48×0.85×0.8/2000 = 4.08h.

Module count: 300A load + 100A charge = 400A; N=4 modules of 100A, plus 1 redundant = 5.

Breaker sizing: 5kW branch: I=5000/48=104A; ×1.25=130A; choose 160A DC breaker rated ≥60V.

Appendix V: Future Technology

  • SiC/GaN: 98%+ efficiency, half size by 2030.
  • AI power: predictive load, predictive maintenance, digital twin.
  • Green energy: PV + storage hybrid sites, zero-grid off-grid operation.
  • HVDC evolution: 48V → 240V/336V in data centers; potential 400V DC standard.

Appendix W: Grounding and Surge Engineering Example

A typical aggregation room: building foundation steel as natural electrode plus five 50×5 galvanized vertical rods (2.5m, 5m spacing) welded with 40×4 flat steel; measured 0.8Ω. Two down conductors to an indoor 30×300 copper bar. Separate working-ground and protective-ground bars with 95mm² wires. SPD grounded with shortest path. Ground resistance tested by three-pole method at ≤1Ω.

Appendix X: Battery Recycling and Environment

VRLA batteries contain lead and acid—hazardous waste, recycled by licensed processors into new batteries. LFP batteries go through cascade reuse (energy storage, low-speed vehicles) then material recovery. KITOZER supports compliant recycling channels. Products meet RoHS, REACH, WEEE, and China RoHS.

Appendix Y: Project Implementation Flow

  1. Requirements (1-2 weeks): load, backup, site survey, preliminary proposal.
  2. Design (1 week): sizing calculations, drawings, customer confirmation.
  3. Manufacturing (3-4 weeks): cabinet, modules, battery, assembly, factory test.
  4. Shipping (1-2 weeks): export crate, logistics, customs.
  5. Installation (1 week): placement, wiring, power-on, discharge test, EMS integration.
  6. Acceptance (1 week): sign-off, documentation, training, warranty starts.

Appendix Z: Glossary

Term Meaning
Float Charge Trickle charge to maintain full state
Boost Charge High-current fast recharge after outage
FLD/SLD First/Second load disconnection
Hot Swap Replace modules under power
Current Sharing Balanced output among parallel modules
Ripple/Noise AC component on DC output
PFC Power factor correction
LLC Resonant converter topology
VRLA Valve-regulated lead-acid
LFP Lithium iron phosphate
BMS Battery management system
SPD Surge protective device
BLSD Battery load disconnect
DDU/DDP Rack-top distribution unit/panel
MTBF Mean time between failures
SOC/SOH State of charge/health
HVDC High-voltage DC
ATS Automatic transfer switch
PUE Power usage effectiveness

Appendix AA: Hub Room Design Case

A provincial hub room: 200m², 1200A load (~58kW), dual mains + diesel generator, 2-hour battery backup.

Load: backbone transmission 16kW, core routers 10kW, data switches 12kW, NMS 6kW, security 1kW, air conditioning 16kW (SLD), lighting 2kW. FLD = 45kW, SLD = 18kW.

Battery: C = 45000×2/(48×0.85×0.7×0.9) ≈ 3500Ah; choose 2× 48V/2000Ah VRLA parallel (4000Ah, ~2.3h).

Rectifier: FLD current 937.5A + charge 200A = 1137.5A; N=12 modules of 100A, plus 1 = 13. Two DPS-1000 cabinets in parallel, 7 modules each (6+1), total 14.

Dual-bus architecture, four column headers, forty DDU units. Total BOM ~373,000 RMB.

Appendix AB: Installation Mistakes Illustrated

  • Reversed polarity: burns gear; verify with multimeter, label cables.
  • Battery short: arcing, fuse blow; insulated gloves/tools, connect positive first.
  • Undersized cable: heating, remote low voltage; size by drop calculation.
  • Poor grounding: interference, lightning damage; bonded grounding ≤1Ω.
  • No expansion slots: forced cabinet replacement later; reserve 30% slots.

Appendix AC: Temperature Compensation Detail

VRLA float voltage optimum drifts with temperature: -3mV/cell/°C. For a 24-cell 48V string, compensation = 72mV/°C. At 25°C float 53.5V; at 35°C = 52.78V; at 15°C = 54.22V. Sensor mounts at the rack center (thermal汇集 point). Default -3mV/cell/°C at 25°C reference.

Appendix AD: Monitor Interface Description

Main screen shows: system name, DC bus voltage (large), total load current, battery voltage/current, status (mains/float/boost), time, alarm icon. Menus: live data, event log, parameter settings (float/boost/thresholds/capacity), system info (version/address/baud). On alarm, red flashing bar and buzzer; acknowledge to mute.

Appendix AE: Battery Parallel Circulating Current

When strings parallel, voltage or internal-resistance mismatch causes circulating current even with no load. Harm: wastes capacity, over-charges/discharges one string, accelerates imbalance. Mitigate: same batch/model/age, equal cable lengths, series diode/fuse per string, max four strings, monitor per-string current.

Appendix AF: Rectifier Parallel Commissioning

Insert modules one by one at no load; verify current sharing at each step; run full load 30 minutes; simulate one-module removal (remaining carry full load, no alarm); reinsert (auto-share). All modules must be same model/version, identical voltage setpoint (≤0.05V), and same manufacturer.

Appendix AG: DC Insulation Coordination

Live circuit to ground ≥10MΩ (normal), ≥1MΩ humid; dielectric 500V DC/1min. Insulation drops from damp rooms, cracked cables, leakage contamination, dust. KITOZER optional insulation monitor alarms below 30kΩ; test annually with 500V megger.

Appendix AH: KITOZER Selection Decision Tree

  1. Sum load power → load current.
  2. Set backup time → battery capacity.
  3. Rectifier capacity = load + 0.1C → module count (N+1).
  4. Branch breakers by branch current.
  5. Cable by voltage drop.
  6. Rack size (19″/23″, capacity tier).
  7. Chemistry (VRLA/LFP).
  8. Monitor config (local/remote/EMS).

Appendix AI: Additional FAQ

Q51: Can KITOZER products be exported? Are certifications complete?
A: Yes. CE certified, wide-input 85-300V AC / 45-65Hz. UL in progress. Confirm destination certification requirements for export projects.

Q52: Can customers procure batteries separately?
A: Yes; KITOZER systems are compatible with major VRLA and LFP brands, but matched KITOZER batteries ensure charge-strategy alignment.

Q53: Can I add rectifier modules later?
A: Yes. Spare slots accept new modules that auto-parallel and share current; the monitor recognizes them.

Q54: What is rectifier failure rate?
A: KITOZER modules MTBF ≥500,000h (~57 years); field failure ~0.5%/year. N+1 redundancy means a single module outage never affects the system.

Q55: How to order? What do you need to provide?
A: Call/WhatsApp with load list, backup time, installation environment, AC mains, and monitoring requirements. We return a proposal and quote within 24 hours.

Appendix AJ: Why -48V Is the Golden Voltage

Voltage selection is a trade-off among line loss, safety, and device complexity. Line loss scales as P²R/V² (higher voltage is better), but human shock risk rises above ~60V, and device voltage ratings (cost) rise with voltage. Forty-eightV sits at the sweet spot: enough voltage to limit long-distance loss, low enough for touch safety, and matched to 100V MOSFET devices (48V bus rectified to ~80V). This is why 24V has excessive loss and 60V is unsafe; 48V is the century-validated optimum. Notably, data centers are “returning to 48V”—rack-level 48V bus with point-of-load DC-DC beats traditional 12V by several percentage points.

Appendix AK: The Next Century of -48V

From magneto telephones to 5G, -48V has survived five generations of power technology while keeping its “positive grounded” architecture—because no other point balances corrosion, safety, efficiency, and compatibility. It will continue to power 5G/6G, edge computing, and IoT. SiC/GaN, AI management, and green-energy integration will make it more efficient, smarter, and lower-carbon. KITOZER will keep deepening this field for operators and enterprises worldwide—whether a Guangzhou core room, a tropical Southeast Asian site, or a desert Middle Eastern station.

Appendix AL: Deep Terminology

  • Float: small trickle charge (0.005-0.01C) maintaining full state at ~2.23V/cell (53.5V string).
  • Boost: fast recharge after outage at ~2.35V/cell (56.4V string), auto-returning to float when full.
  • Hot swap: live module replacement via long/short pins, soft-start, anti-keying.
  • N+1: N modules carry load plus one standby; any single failure stays up.
  • Noise/ripple: AC component on DC output; weighted noise ≤2mV to avoid audio hum or bit errors.
  • PF: real/apparent power ratio; PFC-equipped modules reach ≥0.99.
  • THDi: current harmonic distortion; ≤5% with PFC.
  • SOC/SOH: state of charge (remaining %) and state of health (capacity vs rated; replace below 80%).

Appendix AM: Customer Procurement FAQ

  • Lead time: standard stock 7-15 working days; custom 25-35 days; expedited available.
  • MOQ: none; even one cabinet or module.
  • Samples: available at quoted price, deductible against batch orders.
  • Payment: domestic T/T 30%/70%; international T/T 30% deposit, 70% against B/L copy, or L/C.
  • After-sales: domestic partner engineers; international remote support via WhatsApp/email.
  • OEM/ODM: accepted; private-label arrangement negotiated.
  • Documentation: technical manual, selection software, 3D drawings, CAD wiring on request.

Appendix AN: Brand Comparison

Versiv NetSure is premium but expensive; KITOZER matches its 96% efficiency, 50/100A modules, and N+1 redundancy at 30-40% lower price with open Modbus and high customization. Huawei power is strong but bundled with Huawei gear; KITOZER offers open protocols, flexible pricing, and customization. KITOZER differentiates on cost-performance, customization, 24-hour response, full-stack product range, and export capability.

Appendix AO: How to Reach Us

Technical: +86 13922289957 (WeChat), 9:00-18:00.
Overseas: WhatsApp +1 9068534140, English, 24h.
Sales: +86 18520668845 (WeChat).
Web: lain.com.cn / gdlain.com.
Address: Zhaotian Park, Zhongrun Industrial Zone, No.5 Huashan Road, Shilou, Panyu, Guangzhou, China.

Appendix AP: White Paper Summary

This encyclopedia is part of KITOZER’s telecom power documentation suite, including the -48V Sizing Handbook (50-page PDF), rectifier datasheets, Excel sizing tool, installation videos, and maintenance SOP. All materials are bilingual Chinese/English for domestic and overseas projects.

Appendix AQ: Quick Reference Card

Item Value
Nominal -48V
Float -53.5V (25°C)
Boost -56.4V
End-of-discharge -43.2V
Normal range -38.4V to -57.6V
SLD threshold -46V
FLD threshold -43.5V
Temp comp -3mV/cell/°C
VRLA cells 24×2V
LFP cells 16S×3.2V
Efficiency ≥96%
PF ≥0.99
Sharing ≤±5%
Noise ≤2mV
Ground resistance ≤1Ω
Room temp 15-25°C
Module MTBF ≥500,000h

Appendix AR: A Word to Engineers

Behind the seemingly dry breakers, busbars, and batteries is the lifeline of the entire communication network. A wrong float voltage can kill a battery string in three years; an undersized cable causes remote low-voltage alarms; a reversed parallel polarity can burn a cabinet. We hope this encyclopedia helps you avoid pitfalls. KITOZER engineers each carry over a decade of field experience and are glad to share. Technology evolves—phase control to LLC, VRLA to LFP, manual inspection to AI predictive maintenance—but the mission of reliable power never changes. KITOZER stands with you to guard every watt of the communication network.

Appendix AS: Deep Dive on the History of the -48V Standard

The story of the -48V standard begins not in a laboratory but in the corrosion pits of nineteenth-century underwater cables. As the telegraph and later the telephone networks expanded, engineers noticed something alarming: the iron and copper sheaths of buried cables were corroding away within a few years. Chemical analysis revealed an electrochemical process. When two dissimilar metals sit in an electrolyte (damp soil), they form a galvanic cell, and the metal serving as the anode oxidizes and dissolves.

Early power systems had the positive electrode connected to the line wires, making those wires the anode relative to the earth. To reverse this, engineers grounded the negative electrode instead, making the wires the cathode. Cathodic protection, as it is called today, is a standard corrosion-prevention technique used in pipelines, ship hulls, and reinforced concrete.

But why 48 volts specifically? In the early days of telephony, central offices experimented with various voltages. The Bell System in the United States standardized on 48 volts after extensive testing. At 48 volts, the current required to drive telephone transmitters was sufficient for several kilometers of line, yet the voltage remained low enough that a technician touching both wires would receive, at most, a mild shock. The human body’s resistance in dry conditions is typically 50,000 to 100,000 ohms, so 48 volts produces less than one milliamp—well below the 10-milliamp threshold of pain and far below the 100-milliamp threshold of ventricular fibrillation.

When transistorized equipment arrived in the 1950s and 1960s, it needed low-voltage DC. Rather than redesign the entire power infrastructure, the industry adapted. Rectifiers converted AC mains to 48V DC, floating batteries supplied backup, and the positive-ground convention was preserved. Even as vacuum tubes gave way to transistors, transistors to integrated circuits, and analog to digital, the 48V bus remained. Today’s 5G radio units draw ten times the current of yesterday’s exchanges, but they still run on -48V.

This continuity is remarkable. It means that a battery manufactured in 1985 can still be charged by a rectifier made in 2025, provided the voltage matches. It also means that the design rules developed over decades—cable sizing, breaker coordination, grounding topology—remain valid.

Appendix AT: Rectifier Module Architecture in Detail

A modern 48V/100A rectifier module is a marvel of power density. In a chassis roughly 270mm wide, 400mm tall, and 130mm deep, it packs an input filter, an input bridge rectifier, a power factor correction stage, an isolated DC-DC converter, an output filter, a control board, and a cooling fan.

The input filter consists of a common-mode choke on the AC lines, X-rated capacitors between lines, and Y-rated capacitors from lines to chassis. This filter suppresses both conducted emissions and incoming spikes. The bridge rectifier converts AC to raw DC, which ripples at 100 or 120 Hz.

The PFC stage then boosts this raw DC to a regulated 400V DC bus while shaping the input current into a sine wave in phase with the voltage. A modern transition-mode PFC controller uses a boost inductor, a boost switch (MOSFET), and a boost diode. The control loop adjusts the switching frequency to force the average input current to follow the input voltage waveform.

The 400V DC bus feeds the isolated DC-DC stage. In KITOZER’s high-efficiency modules, this is an LLC resonant converter. The primary side has a half-bridge or full-bridge of MOSFETs that switch the 400V bus across a resonant tank (series inductor, transformer leakage inductance, and a series capacitor). The resonant tank creates a sinusoidal current waveform, allowing the MOSFETs to turn on at zero voltage (ZVS), which dramatically reduces switching loss.

The high-frequency transformer steps the 400V down to about 50V AC at the secondary. The secondary uses synchronous rectification—two MOSFETs instead of diodes—to minimize conduction loss. At 100A output, even a 0.5V diode drop wastes 50W; a synchronous rectifier with 2mΩ on-resistance drops only 0.2V and wastes 20W.

The output filter is a combination of low-ESR electrolytic capacitors and a small inductor, smoothing the rectified 50V into a clean -48V DC. The control board monitors output voltage, output current, temperature, and fan speed, and adjusts the LLC switching frequency to regulate the output.

Appendix AU: Battery Room Design Best Practices

A battery room is not just a storage closet; it is a precision environment that directly determines battery life. The design principles are straightforward but often violated.

First, temperature control. VRLA batteries have a rated life at 25°C. For every 10°C rise above 25°C, life is roughly halved. A battery room that averages 35°C will see its batteries fail in three to four years instead of eight. The room should have dedicated air conditioning sized for both the heat load and the desired setpoint. A setpoint of 22-25°C is ideal.

Second, ventilation. VRLA batteries vent small amounts of hydrogen during overcharge. While the recombination design minimizes this, a fault condition can release hydrogen, which is explosive at 4% concentration in air. Battery rooms require either natural ventilation (vents near the ceiling where hydrogen accumulates) or mechanical ventilation with a hydrogen sensor interlock.

Third, containment. A battery failure can leak acid or, in extreme cases, rupture. The battery room should have a liquid-tight floor with a containment sump, acid-resistant coating, and eye-wash station. Racks should be anchored to the floor with seismic bracing.

Fourth, separation. The battery room should be physically separated from the equipment room to prevent a battery fire from spreading to telecom gear. Fire suppression should be a clean-agent system (not water, which damages batteries).

Fifth, monitoring. Every battery room should have: a temperature sensor at the rack center, a humidity sensor, a water leak detector under the racks, and a door contact. These feed the environment monitoring system.

Appendix AV: DC Breaker Coordination Worked Example

Selectivity—the principle that only the closest breaker to a fault trips—is harder in DC than in AC because DC arcs do not self-extinguish. Consider a distribution chain: battery disconnect (250A) to column header breaker (160A) to rack DDU breaker (63A) to equipment branch breaker (16A).

If an equipment short circuit draws 200A, which breaker should trip? The 16A equipment breaker must trip first, within 0.02 seconds. The 63A DDU breaker should not trip (it has a longer thermal-magnetic delay). The 160A column breaker should stay closed. The 250A battery disconnect should never trip for a downstream fault.

Achieving this requires careful breaker selection. The 16A breaker should be a C-curve (magnetic trip at 5-10x rated = 80-160A), so at 200A it trips instantly. The 63A breaker should be a D-curve (magnetic trip at 10-20x rated = 630-1260A), so at 200A it does not magnetically trip and relies on thermal delay (which takes seconds, giving the 16A breaker time to clear). The 160A and 250A breakers have even higher magnetic thresholds.

Manufacturers publish selectivity tables that specify which combinations guarantee selectivity. Always consult the table rather than guessing.

Appendix AW: Remote Monitoring and NMS Integration

Modern telecom power systems are rarely managed on-site. The monitor module’s data feeds a network management system (NMS) operated from a centralized operations center. A single NMS may monitor thousands of sites.

The integration path is: monitor module to RS485 bus to protocol converter to IP network to NMS server. The protocol converter (often called a communications manager or FSU, field service unit) polls each monitor at regular intervals (every 1-5 seconds for critical data) and stores the data in a database. The NMS displays site topology, alarm lists, and historical trends.

Alarms are classified by severity: critical (causes immediate service impact, e.g., AC fail, battery low), major (requires attention but service continues, e.g., one rectifier failed), and minor (informational, e.g., fan speed high). Critical alarms trigger SMS/phone calls to on-call engineers; major alarms appear in the daily report.

KITOZER monitors support standard Modbus-RTU and optional Modbus-TCP/SNMP, making integration with any third-party NMS straightforward. We provide a complete register map and test protocol.

Appendix AX: Common Questions on Battery Sizing

Q: Why not just buy the largest battery that fits?
A: Oversizing increases cost, floor loading, and charging time. An oversized battery may never fully charge, leading to chronic undercharge and sulfation. Size to the backup-time requirement.

Q: Does the battery need to be sized for peak load or average load?
A: For short backup (under 2 hours), use the actual average load during the outage window. If air conditioning is on the SLD circuit and cuts off after 5 minutes, the sustained load is lower.

Q: Can I reduce battery size if I have a diesel generator?
A: Yes. The battery only needs to bridge the generator startup time (typically 5-15 minutes) plus a margin for generator failure. A 15-30 minute battery is often sufficient for generator-backed sites.

Q: How does altitude affect battery sizing?
A: Above 2000m, air density drops and cooling is less effective. Battery temperature rises faster, and VRLA life shortens. Derate capacity by 1-2% per 1000m above 2000m.

Q: Should I use one large string or multiple smaller strings?
A: Multiple strings (2-4) provide redundancy—if one string fails, the others still carry load. But parallel strings must be identical, and more strings mean more potential circulating current.

Appendix AY: The Business Case for High Efficiency

Consider a 1000A system at a central office. Output power is 48kW. At 92% efficiency, input power is 52.2kW, and waste heat is 4.2kW. At 96% efficiency, input is 50.0kW, waste is 2.0kW.

The electricity saved: 2.2kW x 8760 hours = 19,272 kWh/year. At 0.12 USD/kWh, that is $2,313 per year.

But there is a secondary saving: air conditioning. Every watt of rectifier waste heat must be removed by the room’s air conditioning. If the air conditioner has a COP of 3.0, removing 4.2kW of heat costs 1.4kW of AC power. At 96% efficiency, the AC load drops to 0.67kW. The additional AC saving is 0.73kW x 8760 = 6,395 kWh/year, worth $767.

Total annual saving: $3,080. If the high-efficiency modules cost $2,000 more than standard modules, the payback is under 8 months. Over a 10-year life, the net saving is nearly $29,000 per system. Multiply this across hundreds of sites, and the business case is overwhelming.

Appendix AZ: KITOZER Quality Assurance Process

Every KITOZER power system undergoes a rigorous production and test process:

  1. Incoming inspection: every component (rectifier module, breaker, capacitor, connector) is checked against specifications.
  2. Assembly: wiring follows a documented harness drawing; torque values are recorded.
  3. Insulation test: 500V megger checks live-to-ground resistance at least 10M ohms.
  4. Dielectric test: 1500V AC for 1 minute on the AC input to ground.
  5. No-load power-on: verify output voltage, display, communications.
  6. Load test: 25%, 50%, 75%, 100% load steps; measure voltage regulation, efficiency, noise.
  7. Parallel test: with all modules installed, verify current sharing within +/-5%.
  8. Protection test: simulate overvoltage, undervoltage, overcurrent; verify tripping.
  9. Communication test: verify Modbus data against the register map.
  10. Aging test: 4-hour full-load burn-in at elevated temperature.
  11. Final inspection: visual, labeling, documentation package.
  12. Packing: export crate with foam and desiccant.

This process ensures that every KITOZER system delivered to a customer is tested and ready for years of reliable service.

Appendix BA: Closing Statement

The -48V telecom DC power system is one of the most enduring and proven power architectures in the history of electrical engineering. For over a century, it has delivered uninterrupted power to telephone exchanges, data centers, mobile base stations, and enterprise communication rooms. Its design—positive grounded, 24-cell lead-acid battery strings, parallel floating rectifiers, tiered load disconnection—has been refined through decades of field experience and remains the gold standard for reliable communication power.

KITOZER, manufactured by Guangzhou Laian Intelligent System Development Co., Ltd., carries forward this heritage with modern high-efficiency rectifier modules, intelligent battery management, and comprehensive monitoring. Our product line spans from 100A wall-mounted power for small access points to 2000A parallel cabinets for hub rooms, with both VRLA and lithium iron phosphate battery options, outdoor IP55 cabinets for harsh environments, and rack-top distribution units for structured DC power delivery.

We understand that in telecom power, there is no such thing as a minor detail. A 0.1V error in float voltage can shorten battery life by years. A 10mm² cable where 16mm² was needed can cause remote equipment shutdown. A reversed polarity connection can destroy thousands of dollars of gear. Our engineering team has decades of field experience and has learned these lessons the hard way. We share this knowledge freely in this encyclopedia, because we believe an informed customer is our best partner.

Whether you are designing a new 5G base station in Southeast Asia, upgrading a legacy exchange room in the Middle East, or building a data center in Europe, KITOZER has the products, the documentation, and the technical support to make your project a success. Contact us today for a tailored proposal and quotation.

Our technical team is available around the clock to answer questions about rectifier selection, battery sizing, distribution architecture, grounding design, and monitoring integration. We provide complete bilingual documentation, CAD drawings, 3D models, and commissioning support. Every KITOZER system is backed by a five-year rectifier warranty, three-year monitor warranty, and lifetime technical support. We look forward to partnering with you on your next communication power project.

Thank you for reading this comprehensive encyclopedia of KITOZER -48V telecom DC power systems. We hope it serves as a valuable reference for your engineering work, procurement decisions, and technical training. For the latest product updates, case studies, and technical white papers, visit our website at lain.com.cn (domestic) or gdlain.com (international). Reach us by phone at +86 13922289957 or +86 18520668845, or on WhatsApp at +1 9068534140.

KITOZER is committed to continuous product improvement and customer satisfaction. Our engineering team regularly updates this encyclopedia with new technical insights, field experience, and product enhancements. We welcome feedback and technical discussions from engineers, procurement managers, and partners worldwide. Together, we can build more reliable, efficient, and sustainable communication power infrastructure for the connected world. This article is periodically updated; please check our website for the latest version. All product names, specifications, and configurations are subject to change without notice. Contact our sales engineering team for the most current datasheets, pricing, and lead times. We thank you for your interest in KITOZER products and look forward to a long and successful partnership. Please do not hesitate to contact us with any questions, customization requests, or project inquiries. Our team responds to all messages within one business day, in both Chinese and English. Thank you once again for your time and attention. Best regards, KITOZER Engineering Team.


14. Packaging, Delivery, Warranty, and Company Information

14.1 Packaging

KITOZER power equipment uses export-grade wooden crating:
– Rectifier modules: individual EPE bag + carton, multiple modules per master carton.
– Cabinets: stretch-wrapped + wooden crate, foam-fixed internally.
– Battery banks: wooden crate on pallet, compliant with sea-dangerous-goods packaging (UN38.3).
– Documents: factory test report, certificate, installation manual, wiring diagrams.

14.2 Delivery

  • Standard products: ship 7-15 working days after payment.
  • Custom products: 25-35 working days.
  • Freight: domestic logistics / SF / Deppon; international sea / air / express (DHL/FedEx).
  • Installation: on-site engineers available domestically; remote guidance free.

14.3 Warranty

  • Rectifier modules: 5 years.
  • Monitor modules: 3 years.
  • VRLA batteries: 3 years (capacity guarantee).
  • LFP batteries: 5 years.
  • Cabinets / distribution: 3 years.
  • Lifetime maintenance; post-warranty at cost.

14.4 Company and Contact

Company: Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel: +86 13922289957 (WeChat) / +86 18520668845 (WeChat)
WhatsApp: +1 9068534140
Website: lain.com.cn (domestic) / gdlain.com (international)
Address: Zhaotian Park, Zhongrun Industrial Zone, No.5 Huashan Road, Shilou, Panyu, Guangzhou, China
Business: telecom power, DC distribution, UPS, precision cooling, cabinets, environment monitoring, turnkey data center infrastructure.

14.5 Images (with phone watermark, WebP, English filenames)

Six images (insert in Word/website; bottom-right watermark 18520668845 / 13922289957 / WhatsApp:19068534140; WebP compressed under 200KB):

No. Filename Content ALT Text
1 kitazer-48v-rectifier-system-front-view.webp KITOZER -48V telecom power rack front, populated modules, monitor LCD KITOZER -48V telecom DC power system rack with rectifier modules
2 kitazer-48v-rectifier-module-hot-swap.webp Single high-efficiency rectifier close-up, aluminum housing, LED KITOZER high efficiency hot-swap rectifier module 100A
3 kitazer-48v-battery-room-vrla.webp VRLA battery rack, 24×2V cells in 48V string VRLA battery bank 48V telecom backup power
4 kitazer-48v-lithium-battery-cabinet.webp 48V LFP battery cabinet, BMS, compact 48V lithium iron phosphate battery cabinet with BMS
5 kitazer-48v-dc-distribution-breakers.webp DC breaker row, FLD/SLD branches, 2-pole DC breakers DC distribution panel with first second load disconnection breakers
6 kitazer-48v-base-station-installation.webp 5G base station outdoor integrated power cabinet, IP55 5G base station outdoor integrated DC power cabinet IP55

本文由广州莱安智能化系统开发有限公司(KITOZER)编制,技术参数以实际订货合同为准。