ToggleRows, Aisles, and Cold/Hot Air
When you have more than 2 racks, layout matters. Proper arrangement separates cold air intake from hot air exhaust, so each rack gets cool air.
Layout Rules
- Racks face each other in rows: front of one row faces front of next row.
- The aisle between rack fronts is the cold aisle (cool air enters here).
- The back of one row faces back of the next row: the hot aisle (hot air exits here).
- Cold aisles get cold supply air (from AC vent or perforated floor tiles).
- Hot aisles have return air vents (or ceiling returns).
- Block the ends of aisles with curtains or walls to stop air mixing.
Aisle Width
| Aisle Type | Minimum Width |
|---|---|
| Maintenance aisle (front) | 1200mm (to open rack door + work) |
| Service aisle (back) | 1000mm |
| Walkway between rows | 1200mm |