KITOZER
KITOZER

Pioneer Airtight Optoelectronic Rack (Opto Rack) Product

Table of Contents

1. Cover / Document Information

– Document Title: KITOZER Pioneer Airtight Optoelectronic Rack (Opto Rack) Product Technical Design Solution

– Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Date: August 2026

– Version: V1.0

– Project Type: Technical design solution for KITOZER Pioneer Airtight Optoelectronic Rack (Opto Rack) Product

2. Table of Contents Structure

1. Company Introduction

2. Project Overview

3. User Requirement Analysis

4. Overall Design Description

5. Detailed System Design and Product Technical Parameters

6. Project Quotation and Configuration List

7. Core Solution Advantages

8. Technical Q&A

9. Construction Schedule Plan

10. Construction Organization Plan

11. After-Sales Service System

12. Operation and Maintenance Training Plan

13. Typical Project Cases

14. SEO Optimization System and Website Backend Configuration

15. Contact Information

3. Company Introduction

3.1 Company Development Overview

Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise dedicated to the computer room construction and intelligent protection field for more than two decades, integrating R&D, production, sales, engineering implementation and after-sales service. The company focuses on innovative breakthroughs in electromagnetic shielding technology, modular computer room technology and computer room environmental monitoring technology, and has grown into a source manufacturer with core competitiveness in the domestic computer room construction field.

After more than twenty years of industry accumulation, the company has built a large-scale production and manufacturing base equipped with advanced CNC sheet metal processing equipment, automated spraying production lines and professional testing laboratories, with an annual production capacity of hundreds of sets of shielding computer rooms, integrated cabinets and micro-module products. The company’s service network covers all provinces and cities across the country, providing thousands of computer room construction and renovation services for customers in government, military, scientific research, finance and enterprise fields.

3.2 Core Business System

The company’s core business revolves around the full-lifecycle construction of computer rooms, forming four major product and service systems:

– Computer room EPC general contracting service: one-stop services from solution design, manufacturing, on-site construction to commissioning and acceptance, covering shielding computer rooms, IDC data rooms, modular computer rooms, container computer rooms and other types;

– Core equipment R&D and production: independently produces KITOZER brand series products, including shielding cabinets, shielding desks, consoles, integrated data cabinets, micro-module cold aisle cabinets, outdoor rainproof cabinets, etc., supporting non-standard customization;

– Computer room environmental monitoring system: provides full-element monitoring solutions for temperature and humidity, water leakage, access control, video, fire protection, UPS and power distribution, realizing intelligent and unattended O&M;

– Shielding and security protection products: shielding rooms, shielding doors and windows, anechoic chambers and related auxiliary materials, widely used in confidential, military and scientific research fields.

3.3 Brand and Qualification Honors

The core brand KITOZER (Pioneer) focuses on computer room equipment and shielding products, positioned as an “efficient, green, innovative and safe” solution provider. Products have passed multiple authoritative tests and comply with national and industry standards. The company holds multiple utility model patents and software copyrights, has been awarded high-tech enterprise qualification, and follows the ISO9001 quality management standard.

3.4 Core Competitive Advantages

1. Source production, controllable quality: own production base and professional processing equipment; core products independently produced with full-process quality control, providing more cost-effective solutions without intermediate links;

2. Customized design, matching needs: tailor-made solutions per site conditions, technical requirements, configuration and budget, with multiple design options provided free of charge;

3. Professional team, rich experience: a professional technical team of engineers and project managers with more than ten years of industry experience;

4. Quality after-sales, full guarantee: a 7×24 professional online service system with dedicated project follow-up from early coordination to later O&M.

4. Project Background and Objectives

4.1 Project Background and Significance

High-precision optoelectronic devices, precision instruments and core industrial control units are increasingly deployed in industry, research and communications. These devices are high-value, high-precision and environment-sensitive: dust, moisture, temperature/humidity fluctuation and corrosive gases directly degrade accuracy, life and stability, and can cause faults or data loss. Concentrated precision electronics also carry electrical fire risk, and open racks cannot provide early warning or rapid suppression. The airtight optoelectronic rack (Opto Rack) integrates cabinet airtight protection, closed-loop environment control, early fire detection, clean-agent suppression, smart access control and centralized monitoring into one unit — providing independent, reliable micro-environment protection without renovating the machine room.

4.2 Construction Objectives

High-grade airtight protection: IP54+ (IP55 preferred) isolating dust, moisture, corrosive gas and insects. Precise temperature/humidity control: closed-loop internal circulation air conditioning maintaining stable cabinet climate. Active fire safety: very-early smoke detection + clean-agent suppression with fast, residue-free extinguishing. Smart access and asset management: PIN access control with equipment usage records for full traceability. Centralized monitoring and integration: PLC + HMI monitoring all subsystems, multiple industrial protocols, BMS/fire/asset platform integration. High reliability and maintainability: standard-compliant, certified components, low long-term O&M cost.

4.3 Applicable Scenarios

Telecom base stations/transmission rooms (optical transmission, amplifiers, core optical modules); research institutes and university labs (precision optics, optical inspection, lasers); industrial machine-vision and optoelectronic sensing equipment; power/rail outdoor stations and underground pipe galleries; medical precision optical instruments; special industrial environments with dust, moisture and corrosive gases.

4.4 Design Basis and Standards

NFPA 2001 (clean agents), ISO 14520, NFPA 72, EN 54 series, GB 50116 (fire alarm design), NFPA 75, IEC 60529 (IP), EN 12094-1, UL 864, EIA-310-E (19″ rack), IEC 61439, IEC 60204-1, PUIL 2011, GB 50054, IEC 62443 (industrial network security), RoHS, CE.

5. User Requirement Analysis

5.1 Protection Rating

Airtight capability with overall IP54 minimum, IP55 preferred; continuous sealing of all joints, cable entries and door edges; pressure relief for agent discharge with automatic re-sealing to preserve agent hold time.

5.2 Temperature/Humidity Control

Closed-loop control with no outside air exchange; temperature 18-27 degC adjustable (default 22 degC, +-2 degC); RH 40-60% adjustable (default 50%, +-5%RH); active dehumidification and anti-condensation heating; condensate handling without breaking airtightness.

5.3 Fire Safety

HFC-227ea (HFC-227ea) clean agent — fast, non-conductive, residue-free, below NOAEL concentration; very-early smoke + heat dual detection with cross-zone logic against false discharge; automatic and manual start with emergency abort; certified release device; agent hold time >=10 minutes.

5.4 Access Control and Asset Management

PIN access with multi-user independent passwords; tamper and forced-entry alarms; fail-secure electronic lock; door-open timeout and multiple-error alarms; event log >=5000 records exportable; optional slot sensors or RFID for automatic equipment in/out tracking.

5.5 Centralized Monitoring and Integration

Industrial PLC core with 7″+ touch HMI; time-stamped temperature/humidity trends, alarm events, access events; Modbus TCP/RTU, SNMP, BACnet/IP, RS485, dry contacts; optional REST API for deep integration.

5.6 Electrical Safety and Earthing

Main breaker + branch breakers for graded protection; SPD at incoming; equipotential earthing (frame, doors, mounting, terminals); compliant wiring with clear labels.

5.7 Customization

Cabinet depth/size per site and equipment; cooling capacity per heat load; cold-rolled steel or stainless material; optional biometric access, redundant AC, network security hardening.

6. Design Principles and Applicable Standards

6.1 Design Principles

Safety first: personnel and equipment safety; multi-layer interlocks in fire, electrical and access systems. Reliability: industrial/certified components, adequate safety margins, self-diagnostics and alarms. Airtightness: continuous sealing paths without breaks; sealed entries/openings/joints; self-resetting pressure relief. Precise control: closed-loop feedback with multi-point sampling. Maintainability: accessible core components, easy replacement, ample maintenance space. Extensibility: reserved IO and communication interfaces. Compliance: all designs/materials/parts per applicable international/national standards.

6.2 Applicable Standards

Per section 4.4 (NFPA 2001/72/75, ISO 14520, EN 54/12094, UL 864, IEC 60529/61439/60204/62443, EIA-310-E, GB 50116/50054, PUIL 2011, RoHS, CE); structural mechanics (10J impact, 500N door load <=1mm deflection, vibration 10-55Hz, 1000Pa internal pressure); airtightness verified by pressure-decay test.

7. System Architecture and Working Principle

7.1 Overall Architecture

“One cabinet + multiple subsystems + centralized control”: Carrier layer — airtight cabinet structure providing installation space and base airtight protection; Environment layer — closed-loop climate control; Safety layer — smoke detection + HFC-227ea suppression + access control; Management layer — PLC + HMI for data acquisition, control, display and communication; Support layer — electrical distribution and earthing.

7.2 Internal Layout

Floor-standing single-door cabinet; top zone (AC unit, sampling pipe network, nozzle, sensors; top-mounted AC with downward circulation for uniform temperature); middle equipment zone (19″ mounting rails, 32U, depth adjustable; drawer trays for bench devices); bottom control zone (PLC panel, fire cylinder, solenoid valve, UPS, distribution terminals; cylinder upright with piping up the side wall to the top nozzle; control panel separately partitioned); 100mm base with leveling feet and sealed cable entry. HMI, PIN keypad, manual release, emergency abort and status LEDs mounted on the door exterior.

7.3 Airtight Protection Principle

“Full-path continuous sealing + multi-point sealing compensation”: main seal ring via full-perimeter EPDM/silicone gasket with concealed hinges and multi-point locking ensuring uniform compression; frame joints double-sealed by continuous welding + sealant; panel joints lapped with sealing pads; cable entries via IP68 glands or brush+foam modules; pressure relief valve normally closed, opens on discharge pressure, auto-resets; all removable parts use replaceable seals.

7.4 Subsystem Linkage Logic

Climate: sensors vs setpoints -> PLC controls cooling/dehumidifying/heating; anomalies alarm and upload. Fire: smoke + heat dual confirmation -> pre-discharge countdown with audible/visual alarm; countdown end -> PLC signals certified release device; single-detector alarm only pre-warns. Access/fire interlock: pre-discharge auto-unlocks the door for evacuation; door open aborts discharge. Alarm: any fault pops up on HMI with time/type; uploaded via dry contact/protocols; severe alarms trigger sound/light.

7.5 Redundancy and Reliability

Detection redundancy (smoke + heat dual principle); power redundancy (UPS >=30 min for control/detection/release circuits); lock redundancy (mechanical emergency key); structural redundancy (generous safety factors, no deformation affecting seals); self-diagnostics (sensor/communication/equipment/agent-pressure monitoring).

8. Detailed Technical Design

8.1 Cabinet Structure (KITOZER-OP-W1100H1800)

SECC electro-galvanized cold-rolled steel per GB/T 2518; frame >=2.0mm folded columns; panels >=1.5mm; yield >=235MPa, tensile >=370MPa, elongation >=26%; zinc layer >=8um; 1100x1800mm (incl. base), depth 900mm default (custom); 100mm welded steel base, static load >=600kg with deflection <=1mm; 32U EIA-310-E mounting (44.45mm pitch), depth +-50mm adjustable; front double-layer door >=40mm (flatness <=0.5mm/m), 3 concealed zinc-alloy hinges (>=80kg each), opening >=120° with limit, three-point lock bar; sealed fixed side panels; full sealed back panel; coating: degrease -> phosphating -> electrostatic polyester powder -> curing, 60-80um, adhesion 0 (GB/T 9286), impact >=50kg·cm, salt spray >=500h, RAL7035 default; aluminum laser-etched nameplate; M16 leveling feet +-20mm (>=200kg each), 4 x M12 lifting rings (>=200kg each), 4 drawer trays (>=50kg, three-section steel ball rails), 2 galvanized mounting rails.

8.2 Airtight Sealing System

Door gasket: EPDM (or silicone), solid + foam composite cross-section, Shore A 60+-5 solid / 20+-5 foam; tensile >=10MPa; elongation >=300%; compression set <=20% (70 degC x 24h); -40~+120 degC; xenon aging 1000h degradation <=15%; UL94 V-0; molded continuous ring with no splice; design compression 30-40%. Glands: IP68 nylon PA66 or nickel-plated brass, 3-42mm cable diameters, radial rubber compression, -40~+100 degC; multi-cable brush+foam modules (chloroprene rubber, IP54, flexible expansion). Pressure relief valve: normally closed self-resetting, adjustable opening pressure, IP54, sized per NFPA 2001. Joint sealant: neutral silicone, weather-resistant; closed-cell EPDM foam pads 3mm for removable panels.

8.3 Closed-Loop Climate Control

AC unit KITOZER-CL-1500: 1.5kW cooling, closed-loop internal circulation, top-mounted, eco refrigerant; temperature 18-27 degC (default 22, +-2 degC), RH 40-60% (default 50%, +-5%RH); 2 x sensors +-0.2 degC / +-2%RH RS485 (upper + lower multi-point); active condensing dehumidification >=0.5L/day; 200W PTC anti-condensation heater; 2 x EC centrifugal fans >=300m3/h, >=100Pa; sealed condensate collection + evaporation (no external drain, airtightness preserved); PID control board with multi-stage control and fault alarm; internal sheet-metal ducting for uniform temperature (top-bottom delta <=1.5 degC).

8.4 Fire Detection and Alarm

ASD (aspirating smoke detector): high sensitivity, multi-level alarm, EN54 certified, with sampling pipe network and pump — detects incipient smoke; point heat detector: fixed + rate-of-rise composite, class A, EN54 (second confirmation); alternative: 2 x point photoelectric smoke detectors dual-zone EN54; alarm sounder >=85dB DC24V with strobe; detection logic unit implementing cross-zone logic with dry outputs; manual call point with cover; fault self-check module (loop open/short, detector fault).

8.5 HFC-227ea Clean-Agent Suppression

Agent: HFC-227ea (HFC-227ea) high purity, design concentration 7% v/v (~0.7kg per standard 900mm cabinet, precisely calculated on net volume); seamless carbon-steel cylinder, nitrogen pressurized 25bar, with mounting bracket; DC24V cylinder-head solenoid valve (EN 12094, manual start handle); UL/FM certified release control device with independent logic and delay; 360° brass nozzle top-center; seamless galvanized steel pipe >=60bar with fittings; low-pressure switch 18bar alarm; optional capacitive liquid-level monitor; manual release button + emergency abort button (outside door, with covers); maintenance isolation ball valve; discharge pressure feedback to PLC.

8.6 PIN Access Control and Asset Management

PIN keypad (4-6 digit, backlit, tamper alarm, IP65 panel); motorized electronic lock fail-secure with door-position feedback (>=100,000 cycles); 2 x mechanical emergency keys; door magnetic sensor (NO/NC); tamper vibration sensor (adjustable sensitivity); 4 x through-beam slot sensors for equipment presence; access control board supporting 200 users, >=5000 event log; optional HF RFID reader + 10 anti-metal tags for automatic asset identification.

8.7 PLC Centralized Control and HMI

PLC host 32 points (16 in/16 out) with Ethernet, S7-1200 compatible; 16-in/16-out expansion module; 7″ industrial HMI 800×480 embedded in door; 4-color status LEDs (power/run/alarm/fault); 24V/5Ah UPS (>=30 min); 8GB industrial SD for trends and logs (>=5 years, exportable CSV); communication interfaces Ethernet/RS485/dry contacts with Modbus TCP/RTU, SNMP, BACnet/IP; optional REST API gateway (HTTP/HTTPS); control panel box IP40 in bottom zone.

8.8 Electrical and Earthing

Main breaker C-type 16A 2P AC220V (GB 10963/IEC 60898); 4 branch breakers 6A/10A 1P (AC/control/socket/fire circuits, 6kA); rail terminals tinned copper 0.5-2.5mm2 with clear numbering; SPD type-2 2P, Un 220VAC, Uc 385VAC, In 20kA, Imax 40kA (8/20us), Up <=1.5kV, response <=25ns, failure indication + remote signal, GB 18802.1/IEC 61643-11; main earth busbar T2 copper 3x30mm with >=10 M4/M6 holes; >=6mm2 yellow-green downlead; door-to-frame 6mm2 braid; all shells/shields bonded; cabinet earth resistance <=4 ohm; M8 grounding terminal; RVV/RVVP/fire-resistant cabling per IEC 60204-1/GB 5226.1 with strong/weak separation >=20mm, crimped terminals, number sleeves.

8.9 Optional Upgrades

304 stainless body; N+1 redundant AC with auto switchover; 20mm PU insulation lining; 4 x locking casters (>=200kg each); fingerprint/face + PIN dual authentication; network security hardening per IEC 62443; 3-year extended warranty with annual on-site maintenance.

9. Recommended Configuration and Preliminary Budget

9.1 Standard Configuration Summary

Airtight cabinet (1100x1800x900, 32U, base, leveling feet, lifting rings, 4 trays, rails); sealing system (EPDM gasket, 10 IP68 glands, 2 brush/foam modules, pressure relief valve, sealant/pads); climate control (1.5kW closed-loop AC, 2 sensors, dehumidification, heater, 2 EC fans, condensate handling); fire detection (ASD + heat detector, sounder, logic unit, call point); HFC-227ea suppression (agent, cylinder, solenoid valve, certified release, nozzle, piping, pressure switch, manual/abort, isolation valve, feedback); PIN access (keypad, electronic lock, 2 keys, door magnet, tamper sensor, 4 slot sensors, access board); PLC + 7″ HMI + LEDs + UPS + SD + communication; electrical (main + 4 branch breakers, SPD, earth busbar, cabling, labels); documentation + installation + training + 12-month warranty.

9.2 Budget Notes

Price includes full configuration, FAT, delivery, on-site installation/commissioning (SAT), training and warranty; options quoted separately (stainless, redundant AC, insulation, casters, biometric, network hardening, extended warranty, RFID). Tax-inclusive in RMB (CNY) only — no foreign-currency conversion. Lead time: design confirmation 3-5 working days, production 15-20 working days, FAT 2-3 days, transport 3-7 days, on-site 2-4 days incl. SAT.

10. Technical Specifications

10.1 System Specification Summary

Item Specification
Cabinet 1100x1800x900mm (depth custom); SECC frame >=2.0mm, panels >=1.5mm; yield >=235MPa; 32U EIA-310-E; static >=600kg (deflection <=1mm); front double door >=40mm, 3 concealed hinges >=80kg, >=120°, 3-point lock; 100mm base; RAL7035 60-80um; salt spray >=500h; IP54+ (IP55 with optimized sealing)
Sealing EPDM continuous ring (solid+foam, compression 30-40%, -40~+120 degC, UL94 V-0); 10 x IP68 glands 3-42mm; brush+foam multi-cable modules; self-resetting pressure relief valve (NFPA 2001 sizing, IP54); neutral silicone + EPDM pads
Climate KITOZER-CL-1500 1.5kW closed-loop top AC; 18-27 degC (default 22, +-2), RH 40-60% (default 50%, +-5); 2 x sensors +-0.2 degC/+-2%RH; dehumid >=0.5L/day; 200W PTC heater; 2 x EC fans >=300m3/h; sealed condensate evaporation; PID; top-bottom delta <=1.5 degC
Fire detection ASD aspirating smoke (EN54, multi-level) + class A heat (EN54) dual confirmation; 85dB sounder+strobe; cross-zone logic; call point; fault self-check
Suppression HFC-227ea HFC-227ea 7% (~0.7kg); 25bar seamless cylinder; DC24V solenoid (EN 12094); UL/FM release device; 360° brass nozzle; pipe >=60bar; 18bar low-pressure switch; manual/abort buttons; hold time >=10 min
Access PIN 4-6 digit IP65 keypad; fail-secure motor lock >=100k cycles; 2 mechanical keys; door magnet; tamper sensor; 4 slot sensors; 200 users, >=5000 logs; optional RFID
Control PLC 32pt (16/16) Ethernet S7-1200 compatible + 16/16 expansion; 7″ HMI 800×480; 4 LEDs; 24V/5Ah UPS >=30min; 8GB SD >=5 years; Modbus TCP/RTU, SNMP, BACnet/IP, RS485, dry contacts; optional REST API
Electrical 16A 2P main + 4 branch breakers 6kA; SPD type-2 40kA <=25ns; T2 copper earth busbar 3×30; earth <=4 ohm; M8 terminal; IEC 60204-1 wiring, strong/weak >=20mm
Performance 10J impact no permanent deformation; 500N door load <=1mm; vibration 10-55Hz; 1000Pa internal pressure; pressure-decay airtightness test; seal life 5-8 years
Warranty 12 months whole machine; 24 months core (PLC/HMI/compressor/detectors); 7×24 support; 2h solution / 24-48h on-site; annual preventive maintenance

10.2 Standards Compliance

NFPA 2001/72/75, ISO 14520, EN 54/12094, UL 864, IEC 60529/61439/60204-1/62443, EIA-310-E, GB 50116/50054/9286/10963, GB 18802.1, PUIL 2011, RoHS, CE; certified release device; per-unit FAT with airtightness and integrity test reports.

11. Key Advantages and Customer Value

11.1 Airtight Protection Advantage

Full-path continuous sealing — welded body, compressed full-ring gasket, glanded entries, self-resetting relief valve; IP54+ isolates dust, moisture, corrosive gas and insects; extends equipment life 30%+ and cuts cleaning frequency; pressure-decay verified low leakage meets agent hold-time requirements.

11.2 Precise Environment Control

Closed-loop internal circulation with zero outside air exchange; +-2 degC / +-5%RH accuracy; uniform temperature field; active dehumidification and anti-condensation heating; lower energy use and more targeted than machine-room AC + open racks.

11.3 Proactive Fire Safety

Very-early ASD detection + HFC-227ea suppression from warning to extinguishing; cross-zone dual confirmation minimizes false discharge; fast, non-conductive, residue-free agent allows quick equipment resumption; certified release device independent of PLC — hardware-level logic.

11.4 Intelligent Management

PLC + HMI unified monitoring; standard Modbus/SNMP/BACnet for BMS, fire room, access and IoT platforms; full time-stamped audit (climate trends, access events, fire events); expansion-ready (biometric, RFID, network hardening).

11.5 Customization

Source factory with full R&D: size, depth, material (steel/stainless), cooling capacity and functions tailored; free multiple scheme comparisons; FAT before delivery, short on-site cycle.

11.6 Full Lifecycle Service

>=12-month warranty (24 months core), 7×24 hotline, preventive maintenance, long-term parts/consumables (agent recharge, seals) at transparent cost; 5-year parts guarantee after product renewal.

12. Technical Q&A (50+ Items)

12.1 Cabinet Structure and Airtightness

Q1: Standard size and customization?

A: Standard width 1100mm, total height 1800mm (incl. base), depth 900mm default; depth/width/height customizable per equipment and space.

Q2: Protection rating — dust and moisture?

A: IP54 minimum (IP55 optimized); blocks foreign objects, most dust and all-direction splash water — sufficient for general industrial, underground and semi-outdoor sites.

Q3: Door gasket material and life?

A: EPDM solid+foam composite; -40~+120 degC, weatherproof; 5-8 years indoors; check annually and replace when elastic loss/cracking/deformation; simple low-cost replacement.

Q4: Load capacity?

A: >=600kg static on the reinforced frame/base; heavier options via reinforced frame and shelves; leveling feet ensure even loading.

Q5: Cable entry without breaking airtightness?

A: Bottom entries with IP68 glands (single cables) and brush+foam modules (multiple thin cables) — IP54+ maintained; spare entries reserved for expansion.

Q6: Pressure relief valve — leakage in normal use?

A: Normally closed, minimal leakage; opens only on agent discharge pressure and auto-resets after — preserving airtightness and hold time; NFPA 2001 compliant.

Q7: Door opening angle and lock?

A: >=120° with limit; three-point lock bar ensures uniform gasket compression; concealed hinges >=80kg each.

Q8: Can the back panel be opened for maintenance?

A: Standard full sealed panel; removable maintenance back panel optional per needs.

Q9: How is airtightness verified?

A: Pressure-decay test at FAT and re-checked at SAT after transport/installation.

12.2 Climate Control

Q10: What does closed-loop mean?

A: Air circulates entirely inside — evaporator cools/dehumidifies internal air, condenser dissipates heat via a separate duct; zero exchange with outside air, preserving airtightness and cleanliness.

Q11: Cooling capacity selection?

A: Calculated from total heat load, temperature difference and seal loss; standard 1.5kW covers most mid/low-power devices; larger or N+1 redundant AC for high heat loads.

Q12: Control accuracy and uniformity?

A: +-2 degC / +-5%RH; top-supply/bottom-return ducting with EC fans keeps top-bottom delta <=1.5 degC.

Q13: Condensate handling?

A: Sealed collection + evaporation — no external drain, airtightness preserved; level sensor alarms and stops dehumidification if full.

Q14: Winter/cold conditions — condensation?

A: 200W PTC heater auto-starts below the setpoint or near dew point, preventing condensation; year-round stability.

Q15: AC failure replacement?

A: Top-mounted modular unit — removed from the top without dismantling the cabinet or equipment; compressor life >=50,000h; spare units and fast replacement available.

Q16: Dehumidification capacity?

A: >=0.5L/day condensing dehumidification integrated in the AC.

Q17: Sensor positions?

A: 2 x sensors (upper + lower) multi-point monitoring with RS485.

12.3 Fire Suppression

Q18: Why HFC-227ea instead of dry powder/CO2?

A: Dry powder leaves corrosive dust destroying optics/PCBs; CO2 needs high concentration (hazardous, condensation damage); HFC-227ea is clean gas — non-conductive, residue-free, fast, low concentration, safe for people and equipment.

Q19: False discharge prevention?

A: Dual-detector cross confirmation (smoke + heat both required); 0-30s delay with sound/light and emergency abort; door-open interlock locks discharge; certified release device with hardware-level logic independent of PLC.

Q20: Agent quantity and longevity?

A: Calculated per NFPA 2001 (net volume, concentration, temperature); ~0.7kg at 7% for standard cabinet; sealed storage holds pressure for years; weight/pressure checked every 3 years; cylinder life 20 years with 5-year hydrostatic tests.

Q21: Safety after discharge?

A: 7% design concentration below NOAEL 9%; brief noise/airflow; ventilate before entry — 1-2 minutes for a small cabinet; pre-discharge delay and alarms ensure personnel clear.

Q22: Fire certification and acceptance?

A: EN/UL/FM certified components; NFPA 2001/GB 50370 design; full calculation sheets, certificates and test reports; configuration adjustable for local acceptance rules.

Q23: Agent hold time?

A: >=10 minutes thanks to the airtight cabinet, ensuring complete extinguishing.

Q24: Manual operation?

A: Manual release button and emergency abort button outside the door with protective covers; maintenance isolation valve for servicing.

12.4 Access Control and Monitoring

Q25: Number of users and levels?

A: 200 users with graded permissions (admin can configure/maintain; users open only); independent PIN per user, enable/disable anytime.

Q26: Power loss — door locked?

A: Fail-secure lock keeps the door locked for security; 2 mechanical keys provided; UPS keeps access/monitoring working >=30 min.

Q27: Equipment usage tracking?

A: Standard: slot photoelectric sensors + door records; optional RFID: anti-metal tags auto-scanned on door close, generating asset ledger without manual entry.

Q28: Integration with existing systems?

A: Modbus/SNMP/BACnet/dry contacts for BMS, fire systems; optional REST API gateway for proprietary platforms; protocol docs and support provided.

Q29: Data retention and export?

A: 8GB storage keeps minute-level trends plus alarm/access events 5+ years; CSV export via USB or Ethernet; auto-overwrite of oldest data.

Q30: Alarms shown?

A: All subsystem alarms pop on the 7″ HMI with time/type; severe alarms trigger the sound/light indicator group and are uploaded remotely.

12.5 Installation and Maintenance

Q31: Installation complexity?

A: Factory-assembled and FAT-tested; on site: position, level, connect power/earth, SAT test; no complex construction; technician dispatch for networking/platform integration.

Q32: Daily maintenance?

A: Daily/weekly HMI status check; quarterly surface cleaning, gasket and cylinder pressure check; annual airtightness/AC filter/sensor/electrical inspection; agent weight/pressure every 3 years.

Q33: Warranty and response?

A: 12 months whole machine (24 months core); optional extension; 7×24 hotline, solution within 2h, on-site 24-48h by region.

Q34: Spare parts?

A: Common industrial components stocked; consumables (seals, filters, sensors) low cost; core parts long-life; 5-year support after model renewal.

Q35: Grounding requirement?

A: Cabinet earth <=4 ohm; M8 terminal + >=6mm2 downlead to site earth grid; door braid equipotential.

Q36: Power requirement?

A: 220VAC single phase; main 16A 2P breaker; SPD 40kA protects electronics; UPS >=30 min backup.

12.6 Customization and Application

Q37: Suitable environments?

A: Telecom underground stations (moisture/dust), labs (precision optics), factory machine vision (smoke/oil), power pipe galleries (humidity/corrosion), medical instruments.

Q38: Stainless option?

A: Full 304 stainless body for corrosive/high-humidity sites with same thickness and airtightness.

Q39: High-heat equipment?

A: Larger AC or N+1 redundant AC per heat load calculation.

Q40: Mobile needs?

A: Optional 4 locking casters (>=200kg each).

Q41: High-security access?

A: Optional fingerprint/face + PIN dual authentication.

Q42: Network security?

A: Optional hardening per IEC 62443 (firewall, encryption) for connected/classified sites.

Q43: Delivery cycle?

A: Design 3-5 + production 15-20 + FAT 2-3 + transport 3-7 + on-site 2-4 working days; custom/batch adjusted per contract.

Q44: Documentation delivered?

A: As-built drawings (assembly/electrical/fire P&ID/3D), component datasheets and certificates, O&M manual, FAT report, agent documents, certificate of conformity.

Q45: Training provided?

A: On-site training at SAT: operators (1h), O&M (2-3h), administrators (1-2h); remote refresher for new staff; unlimited participants.

Q46: What if fire system is not required?

A: Configuration can omit suppression while keeping detection, or add later — modular.

Q47: Does it comply with international standards?

A: Yes — NFPA 2001/72/75, EN 54/12094, UL 864, IEC 60529/61439/60204-1, EIA-310-E, RoHS/CE; export-ready (PUIL 2011 for Indonesia).

Q48: Cost-effective?

A: Avoids machine-room renovation, extends equipment life, cuts cleaning/maintenance and fire-loss risk — strong whole-life value.

Q49: Multiple units networking?

A: PLCs networked via Ethernet; one HMI/upper platform can supervise multiple racks; BACnet/SNMP for BMS aggregation.

Q50: Why choose KITOZER/Lain?

A: Airtight + climate + fire + access + monitoring integration in one certified cabinet, source-factory customization, FAT-verified quality, 12+24-month warranty and full lifecycle service.

13. Construction Schedule

13.1 Overall Schedule (Reference, Standard Configuration)

Stage Work Duration Responsibility Deliverable
1 Scheme confirmation Requirement communication, design, configuration confirmation, contract 3-5 working days Sales engineer + technical support Final scheme, quotation, contract
2 Design & production Construction drawings, client confirmation, cabinet fabrication, parts procurement, assembly 15-20 working days R&D + production Drawings, finished unit
3 Factory test (FAT) Structure check, airtightness test, climate stability test, fire function test, access/monitoring test, full integration 2-3 working days QC + engineering FAT report, certificate
4 Transport Packing, logistics, arrival acceptance 3-7 working days Logistics Shipping note, receipt
5 On-site installation Positioning, leveling, power, earthing, external wiring 1 working day Field engineer Installation record
6 On-site commissioning (SAT) Subsystem power-on, calibration, function tests, linkage tests, airtightness re-check 1-2 working days Field engineer SAT report, records
7 Training & acceptance Operation/maintenance training, assessment, as-built handover, final acceptance 1 working day Engineer + client Training record, acceptance report
8 After-sales Warranty service, follow-up, preventive maintenance, fault response 12 months After-sales Service records

Custom configurations and batch orders adjust the cycle per contract.

14. Construction Organization and Quality/Safety Measures

14.1 Organization

Project manager (1) — overall coordination; technical lead (1) — design, disclosure, debugging guidance; field engineers (1-2) — installation/wiring/debugging/training; QC engineer (1) — factory and site acceptance; after-sales support (1). Fire and electrical personnel certified.

14.2 Pre-Construction Preparation

Technical: construction drawings; confirm site power/earthing/space; construction and safety disclosure documents. Materials: parts stocked, unit assembled and FAT-passed; tools/instruments/auxiliaries ready; as-built documents prepared. Site: survey floor flatness, load, power location, transport route; clean the area; coordinate with the client contact; Safety: training, PPE, protective measures, emergency plan.

14.3 Standard On-Site Flow

Step 1 — Positioning and fixing: unpack, check for transport damage, match model; move into position; level with 4 feet via spirit level; optional floor bolting (indoor usually leveling only). Step 2 — Electrical wiring: confirm power off, hang warning sign; bring supply cable through sealed glands; wire to main breaker (line/neutral/earth); connect earth terminal to site bus; external signal/fire/BMS connections via dry contacts/communication; dress and label cables. Step 3 — Power-on check: all branch breakers off, close main, verify input voltage; close branches sequentially, check each device, no abnormal sound/smell; PLC/HMI startup and sensor reading; access, LEDs and sounder functions. Step 4 — Subsystem commissioning: climate (setpoints, cooling/dehumidification/heating, accuracy, condensate); detection/alarm (simulated smoke/temperature, warning/alarm logic, sounder); suppression (functional only, no agent discharge — release circuit, delay, auto/manual, abort, door interlock); access (PIN, unlock, door magnet, alarms, logs, users); monitoring (HMI display, data/alarm records, communication). Step 5 — Integration and tests: linkage logic (fire-access interlock, temperature-AC); simulated fault scenarios; airtightness re-check; continuous run observing climate stability. Step 6 — Cleanup: remove waste, clean cabinet, apply safety signs and operation labels.

14.4 Quality Control

Three-level inspection (self-check, PM recheck, QC final) — each process qualified before the next; construction strictly per drawings (changes via design change order); standard workmanship (neat wiring, clear labels, reliable sealing); truthful test records signed by both parties; complete as-built package.

14.5 Safety Management

Power-off work discipline; live work in pairs with insulated tools; no smoking, fire extinguishers, hot-work permits; careful multi-person cabinet handling; stable ladders for top work; first-aid kit and emergency plan; certified electricians/fire personnel only.

14.6 Civilized Construction

Uniform dress and badges; warning signs at work area; tidy materials/tools with daily cleanup; respect site facilities (damage compensated); noise within limits.

15. After-Sales Service

15.1 Warranty Commitment

12 months whole-machine free warranty from final acceptance (free repair, parts, on-site for non-human, non-force-majeure faults); core components (PLC, HMI, AC compressor, detectors) 24 months; optional 2/3-year extension with equal service; exclusions: human damage, unauthorized modification, force majeure — paid repair available.

15.2 Response Standards

7×24 hotline; general/software issues solved remotely within 2h; on-site within 24h urban / 48h surrounding (remote negotiated); emergency faults (fire system down, total cooling loss) prioritized for fastest arrival.

15.3 Preventive Maintenance

1 free annual maintenance in warranty (yearly in extension, or purchased service pack): cabinet/sealing check (gasket, entry seals, airtightness, locks/hinges lubrication); AC/environment (filters, ducts, refrigerant pressure, sensor calibration, condensate device, heating/dehumidification); fire system (cylinder pressure, detector/release tests, piping/nozzles, linkage logic); access/monitoring (function, sensors, data backup, firmware, UPS battery); electrical/earthing (terminal tightening, breakers/SPD, earth resistance, cable aging); maintenance report with assessment and recommendations.

15.4 Spare Parts Supply

Safety stock of consumables and core parts; original-quality parts; 1-3 working days dispatch (expedited available); long-term consumables (HFC-227ea agent, seals, filters) at transparent prices; >=5-year parts guarantee after model renewal.

15.5 Full-Channel Technical Support

7×24 phone; WeChat/email/remote-desktop for software and parameter issues; on-site install/debug/repair/maintenance/training; technical consultation for expansion/upgrade/retrofit; dedicated after-sales contact per project.

16. Training Plan

16.1 Training Objectives and Audience

Training objectives: through systematic training, enable management personnel to fully understand the system structure, working principles and performance characteristics, master daily operation methods and inspection/maintenance essentials, identify common faults and handle simple problems, ensuring safe, stable and long-term operation.

Training audience: management and O&M personnel designated by the client, recommended 2-3 persons with basic electrical and equipment knowledge.

16.2 Tiered Training Content System

Level 1: Basic operation training (1 day)

– Basic principles: system concepts, structure composition, performance indicators;

– Daily operation standards: correct operation of equipment, control and safety systems;

– Daily inspection contents: daily/weekly/monthly check items;

– Safety precautions: usage prohibitions and emergency handling procedures.

Level 2: Maintenance training (1 day)

– Detailed structure of each subsystem and working principles;

– Daily maintenance methods: cleaning, fastening checks, routine care;

– Common fault identification and simple handling;

– Emergency handling procedures for power failure, fire and equipment faults.

Level 3: Advanced management training (as needed)

– Performance influencing factors and how to avoid degradation;

– Upgrade and expansion knowledge and specification requirements;

– Relevant national standards interpretation.

16.3 Training Methods and Schedule

– Methods: combination of “theory explanation + on-site practice + Q&A interaction”;

– Schedule: training arranged at the completion acceptance stage, synchronized with handover, 2 days of intensive training total; time flexibly adjustable; a free repeat training session is provided for newly assigned personnel.

16.4 Training Assessment and Documentation Delivery

– Assessment: theory written test plus practical operation; training qualification certificates issued upon passing; supplementary training for those who fail;

– Documentation delivery: complete O&M documentation, including operation and maintenance manual, equipment manuals and certificates, completion drawings and hidden work records, test reports and after-sales service contact card, all bound into volumes.

17. Anonymous Typical Project Scenarios

All project scenarios below are anonymous, generalized examples provided for reference only. No real customer names, addresses or identifiable details are disclosed.

17.1 Research Institute Precision Optics Laboratory Project

Background. A laboratory’s high-precision laser interferometers and spectrometers demanded extreme temperature/humidity stability and cleanliness; ordinary lab AC fluctuated and dust degraded measurement accuracy; the high-value equipment also posed a fire risk.

Solution. 2 x customized widened Opto Racks (depth 1000mm) with 2kW closed-loop constant temperature/humidity AC (+-1 degC, +-3%RH), ASD aspirating smoke detection + HFC-227ea suppression, fingerprint + PIN dual access, and upper-computer monitoring software for both racks.

Results. Long-term stable internal climate significantly improved measurement repeatability and cut fault rates; dust isolation extended cleaning cycles from monthly to semi-annual; fire protection passed the institute’s safety inspection; the customer later ordered 3 more units.

17.2 Telecom Operator Transmission Room Optoelectronic Protection Project

Background. An underground station site with heavy moisture and dust caused frequent damp/dust faults on core optical transmission boards — high maintenance cost and short equipment life; whole-room renovation was difficult and expensive.

Solution. 6 x standard Opto Racks, one per transmission column, with 1.5kW closed-loop AC with active dehumidification; point photoelectric + heat cross-detection suppression; access integrated with the site’s door platform; temperature/humidity data uploaded to the room’s environment monitoring system.

Results. Dry, clean internal environment cut equipment fault incidence ~80% and sharply reduced site-visit maintenance; equipment life clearly extended with fast payback; no machine-room renovation, minimal downtime — highly appreciated by the customer.

17.3 Automotive Factory Machine-Vision Equipment Protection Project

Background. A production workshop with heavy welding fume and oily dust constantly contaminated industrial cameras and vision light sources; oil corroded wiring and caused faults; summer heat degraded inspection accuracy.

Solution. 304 stainless Opto Racks (corrosion-resistant, easy cleaning) with industrial high-temperature closed-loop AC; high-efficiency filtration and sealing against fume/oil; access control with equipment-presence monitoring for regulated usage.

Results. Camera/light cleaning cycles extended from weekly to quarterly with far less maintenance work; stable operating temperature maintained detection accuracy with lower misjudgment; stainless body resisted oil corrosion in the harsh industrial environment.

17.4 Power Company Underground Pipe Gallery Optoelectronic Cabinet Project

Background. An underground utility gallery had high humidity and corrosive gas; optoelectronic measurement and communication equipment failed frequently; unattended stable operation was required.

Solution. Outdoor Opto Racks at IP55 with 304 stainless bodies; dehumidifying industrial AC with wide-temperature operation; HFC-227ea suppression for unattended automatic extinguishing; remote monitoring uploading to the gallery platform; UPS extended to 2 hours.

Results. Equipment ran stably in the damp underground environment with no moisture/corrosion faults; remote monitoring eliminated frequent inspection trips — lower O&M cost and safety risk; the fire system ensured unattended equipment safety per gallery regulations.

18. SEO Optimization Section

All reference prices in this technical solution are in RMB (CNY) only and are for reference purposes; final quotation is subject to the confirmed configuration.

18.1 Keyword System

– Core keywords: technical design solution, system configuration, technical parameters, construction and O&M services;

– High-conversion long-tail keywords: design solution, configuration list, technical parameters, construction plan, after-sales service;

– Industry traffic keywords: system architecture, applicable standards, technical Q&A, project cases;

– Brand keywords: KITOZER, Guangzhou Lain.

18.2 SEO Tag System

– Title tag: the article title — Guangzhou Lain KITOZER;

– Meta description: Guangzhou Lain professionally provides complete technical design solutions with detailed configuration list, full-system product technical parameters, construction organization plan and after-sales service — source manufacturer customization, compliant performance, third-party testing supported;

– H1 tag: the article title;

– H2 tags: system design and product parameters, construction organization plan, after-sales service and training, engineering cases.

18.3 Internal Link Anchor Text

– Core anchor text: technical design solution, system construction;

– Long-tail anchor text: configuration list, technical parameters, construction plan;

– Related anchor text: shielding cabinet, micro-module cold aisle, integrated computer room, outdoor cabinet.

19. Official Contact Information

– Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Official Website: https://gdlain.com

– Tel: +86 13538869979 (Tel / WhatsApp)

– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China

For any inquiries about this technical design solution, configuration customization, quotation or construction services, please contact us through the information above. We provide free design consultation and tailored solutions for your specific requirements.

Scroll to Top