Pipeless Gas Fire Suppression System Installation, Wiring, and Commissioning Manual

Table of Contents

Preface

This manual is compiled by Guangzhou Lain Intelligent System Development Co., Ltd. in accordance with the following current national standards: *Code for Design of Gas Fire Extinguishing Systems* (GB 50370-2005), *Code for Construction and Acceptance of Gas Fire Extinguishing Systems* (GB 50263-2007), *Cabinet Gas Fire Extinguishing Equipment* (GB 16670-2006), and *Gas Fire Extinguishing Systems and Components* (GB 25972-2010). It is applicable to the full-cycle guidance of installation, wiring, commissioning, acceptance inspection, and operation and maintenance of the company’s full range of pipeless (pre-engineered) gas fire suppression devices.

The pipeless gas fire suppression system, also known as the pre-engineered gas fire suppression system, is a total-flooding fire extinguishing device that pre-integrates the extinguishing agent storage container, discharge activation components, nozzles, and control system as a complete unit. It requires no dedicated storage room or delivery pipe network and is deployed directly within the protected area. It offers significant advantages including flexible installation, rapid response, simple operation and maintenance, and low project cost. It is widely used in important facilities such as data centers, telecommunication base stations, power distribution rooms, archives, and precision instrument rooms.

This manual covers sixteen core modules including product introduction, composition, classification, checklist, principles, technical parameters, functional features, application scenarios, installation, wiring, commissioning, precautions, maintenance, common faults, Q&A, and acceptance inspection. The content is detailed, the data is accurate, and the process standards are clearly defined. It serves as a reference for engineering construction personnel, fire protection operation and maintenance personnel, property management personnel, and the client’s technical representatives.

Chapter 1 Product Introduction

1.1 Product Definition

The pipeless gas fire suppression system (pre-engineered gas fire suppression system) is an independent fire suppression system in which the extinguishing agent storage device, discharge components, and activation control device are pre-designed, assembled as a complete unit under specified application conditions, and equipped with linkage control functions. Compared with the piped gas fire suppression system, its core characteristic is that the extinguishing agent does not need to be conveyed over long distances through piping; instead, it is discharged directly from the device body into the protected area. The system offers high integration, minimal on-site construction work, and short deployment cycles.

According to the provisions of the national standard GB 50370-2005, the pre-engineered fire suppression system is applicable to a protected space where a single protected area does not exceed 500 m² in floor area and 1600 m³ in volume. When multiple pre-engineered devices are installed in the same protected area, they must be capable of simultaneous activation, and the response time difference between devices shall not exceed 2 s. The system charging pressure shall not exceed 2.5 MPa.

1.2 Extinguishing Agent Overview

The mainstream extinguishing agent used in this series of pipeless gas fire suppression systems is heptafluoropropane (HFC-227ea). Some special scenarios may be equipped with perfluorohexanone (Novec 1230) extinguishing agent.

1.2.1 Heptafluoropropane Extinguishing Agent

Heptafluoropropane is a clean gas extinguishing agent that extinguishes fire primarily through chemical inhibition, supplemented by physical cooling. Its molecular formula is CF₃CHFCF₃. At normal temperature and pressure, it is a colorless and odorless gas that can be stored as a liquid in steel cylinders under pressure. Its core characteristics are as follows:

Environmental Performance: Ozone depletion potential (ODP) = 0, global warming potential (GWP) = 3220, atmospheric lifetime of 36.5 years. It is a Halon replacement recognized by the *Montreal Protocol* and complies with national environmental protection policy requirements.

Fire Extinguishing Efficiency: Low extinguishing concentration. The design concentration for Class A solid surface fires is 5.8%, for Class B liquid fires is 6.7%, and for electrical fires is 8%. Early-stage fires can be rapidly extinguished within 10 seconds of discharge, providing high extinguishing efficiency.

Safety Performance: The no-observed-adverse-effect level (NOAEL) is 9%. The design extinguishing concentration is generally lower than the NOAEL value, making brief personnel exposure safe. The extinguishing agent is non-conductive and residue-free. After discharge, it rapidly vaporizes and disperses, causing no secondary damage to electronic equipment, precision instruments, or paper archives.

Storage Stability: Excellent liquid-state storage stability, non-corrosive, with no adverse effects on common metallic materials. Under normal storage conditions, the service life can exceed 10 years.

1.2.2 Perfluorohexanone Extinguishing Agent

Perfluorohexanone is a new-generation clean extinguishing agent. At normal temperature, it is a colorless transparent liquid. It is stored as a liquid and extinguishes fires as a gas. It has a significantly lower GWP value (GWP = 1), providing superior environmental performance. It is suitable for high-end data center scenarios with personnel present and extremely high environmental protection requirements. Its extinguishing mechanism is similar to that of heptafluoropropane, and it likewise features residue-free and non-conductive properties.

1.3 Product Development History and Industry Position

After the era of Halon 1211 and Halon 1301, gas fire suppression technology was gradually phased out due to ozone depletion concerns. Since the 1990s, clean gas fire suppression technologies such as heptafluoropropane and IG541 have developed rapidly. Among these, the pipeless pre-engineered system has become widely popular in small and medium protected area scenarios owing to its installation convenience, establishing itself as one of the mainstream solutions in the data center fire protection field.

Guangzhou Lain Intelligent System Development Co., Ltd. has been deeply engaged in the data center fire protection field for many years. All pipeless gas fire suppression products manufactured by the company have passed the national compulsory product certification (3C certification). The core components use high-quality raw materials and precision machining processes, and the system stability and extinguishing reliability have reached an advanced level within the industry. These products are widely used in data center construction projects across multiple industries including government, finance, telecommunications, education, and healthcare.

1.4 Applicable Product Standards

The design, production, inspection, installation, and acceptance of this product strictly comply with the following national and industry standards:

  • GB 50370-2005 *Code for Design of Gas Fire Extinguishing Systems*
  • GB 50263-2007 *Code for Construction and Acceptance of Gas Fire Extinguishing Systems*
  • GB 16670-2006 *Cabinet Gas Fire Extinguishing Equipment*
  • GB 25972-2010 *Gas Fire Extinguishing Systems and Components*
  • GB 50116-2013 *Code for Design of Automatic Fire Alarm System*
  • TSG 23-2021 *Safety Technical Regulation of Gas Cylinder*
  • GA 1061-2013 *Requirements for Consistency Check of Fire Protection Products*

Chapter 2 Product Composition

The pipeless gas fire suppression system consists of two major parts: the fire extinguishing device body and the alarm/linkage control system. Taking the cabinet type as an example, the fire extinguishing device body includes the cabinet, extinguishing agent storage cylinder set, valve assemblies, discharge assemblies, and signal feedback assemblies. The alarm/linkage control system includes the fire suppression controller, fire detectors, manual control devices, audible and visual alarm devices, and discharge indicator lights.

2.1 Cabinet Assembly

The cabinet is the external load-bearing structure of the pipeless cabinet-type fire extinguishing device. It is manufactured from high-quality cold-rolled steel plate through CNC bending, welding, pickling and phosphating, and electrostatic spraying. The protection rating is not lower than IP30. The standard color is computer gray or milky white, and custom colors and dimensions are available upon user requirements.

The cabinet structure comprises the main body, front door, top plate, bottom plate, internal mounting brackets, cable feed-through holes, and nozzle mounting positions. The design balances structural strength, heat dissipation and ventilation, and aesthetics:

Front Door: Equipped with a dedicated lock for cylinder inspection and pressure gauge reading. The door carries the product identification plate, extinguishing agent name, model and specification, and warning labels.

Internal Brackets: Use a clamp-type fixing structure to securely fasten the storage cylinders within the cabinet, preventing toppling and shaking, with seismic resistance.

Cable Feed-Through Holes: Dedicated feed-through holes are reserved at the rear of the cabinet, fitted with rubber grommets for routing the control wiring of the solenoid actuator, pressure switch, and other components, preventing cable abrasion.

Ventilation Openings: Ventilation and heat dissipation openings are provided at the lower section of the cabinet to maintain stable temperature around the cylinder set, preventing abnormally high pressure caused by elevated temperatures.

2.2 Extinguishing Agent Storage Cylinder Set

The extinguishing agent storage cylinder set is the core pressure-bearing component that stores the extinguishing agent. It consists of a seamless steel cylinder, extinguishing agent, container valve (cylinder head valve), pressure gauge, and safety pressure relief device.

2.2.1 Storage Cylinder

Manufactured from high-quality seamless steel tube through spinning and necking, compliant with the *Seamless Steel Gas Cylinders* standard (GB 5099). The design pressure is typically 2.5 MPa or 4.2 MPa, and the hydrostatic test pressure is 1.5 times the design pressure. It features high strength, excellent sealing performance, and corrosion resistance. The cylinder body is treated with anti-corrosion coating and fitted with a permanent filling label indicating empty cylinder weight, extinguishing agent weight, total weight, filling date, and validity period.

Common capacity specifications: 40 L, 70 L, 90 L, 100 L, 120 L, 150 L, and 180 L, which can be flexibly selected based on the protected area volume.

2.2.2 Container Valve (Cylinder Head Valve)

The container valve is installed at the cylinder neck opening and is the core valve assembly controlling the release of the extinguishing agent. It integrates filling, discharge, safety pressure relief, pressure indication, and emergency activation functions. It is precision-forged from copper alloy and provides excellent sealing performance.

The main ports and functions of the container valve:

Port/Function Description
Extinguishing agent outlet Connects to the high-pressure hose and nozzle; forms the extinguishing agent discharge path
Pressure gauge port Mounts the pressure gauge for real-time monitoring of cylinder pressure
Filling port Used for extinguishing agent filling and pressure recharging
Safety relief port Contains a burst-type safety relief membrane; automatically ruptures to relieve pressure when internal pressure rises to the rated value due to abnormally high temperature, preventing cylinder overpressure explosion; the membrane must be replaced after relief
Activation port Mounts the solenoid actuator or pneumatic actuator; opens the valve upon receiving the activation signal
Emergency activation port Fitted with a mechanical emergency handle; allows manual valve opening in the event of power failure or electrical control failure

2.2.3 Pressure Gauge

A shock-resistant pressure gauge is used with a range of 0 to 6 MPa and an accuracy class of not lower than 2.5. The dial is marked with a green normal operating zone, a yellow warning zone, and a red overpressure zone for intuitive judgment of cylinder pressure status. A pressure gauge shut-off valve is installed upstream of the gauge, permitting the gauge to be removed for maintenance without releasing the extinguishing agent from the cylinder.

2.2.4 Safety Pressure Relief Device

Divided into cylinder safety relief devices and pipeline safety relief devices, both using a burst membrane structure with precise actuation pressure to ensure rapid pressure relief during system overpressure, protecting equipment and personnel safety.

2.3 Activation and Drive Assemblies

2.3.1 Solenoid Actuator

The solenoid actuator is the core execution component of electrical activation. It is installed at the activation port of the container valve and is driven by DC24V power output from the fire suppression controller. When energized, the internal electromagnetic coil generates electromagnetic attractive force that strikes the firing pin, piercing the sealing membrane of the container valve and opening the extinguishing agent release path.

Solenoid actuator technical features:

  • Rated operating voltage: DC24V; starting current: ≤1.5A
  • Manual reset function, reusable after testing
  • High insulation class, strong electromagnetic interference resistance
  • Equipped with a safety pin to prevent inadvertent activation during transportation and installation

2.3.2 Pneumatic Actuator

Used in dual-cylinder or multi-cylinder linkage scenarios. After the primary cylinder opens, high-pressure gas is delivered through the activation tubing to the pneumatic actuator of the slave cylinders, driving the slave cylinders to open simultaneously, ensuring simultaneous discharge from multiple cylinders.

2.3.3 Mechanical Emergency Activation Mechanism

Comprising a handle, connecting rod, and firing pin. When the electrical control system fails, personnel can manually operate the emergency handle to mechanically strike and open the container valve, achieving extinguishing agent release. This serves as the final activation safeguard of the system. The mechanical emergency operating point is clearly marked with the corresponding protected area name and operating instructions.

2.4 Discharge Assemblies

2.4.1 High-Pressure Hose

Constructed with a rubber inner liner sheathed in stainless steel braided mesh, with copper alloy fittings at both ends. It features high pressure resistance, bend resistance, and corrosion resistance. It connects the container valve outlet to the nozzle, cushioning the reaction force during cylinder discharge while compensating for installation dimensional deviations.

2.4.2 Nozzle

The nozzle is the key component determining the uniformity of extinguishing agent discharge distribution. It is precision-machined from copper alloy or aluminum alloy and features a dedicated flow channel and orifice structure that causes the extinguishing agent to disperse rapidly and uniformly in an atomized state, reaching the design extinguishing concentration within the specified time.

For cabinet-type devices, the nozzle is typically installed at the top or side of the cabinet, with the discharge direction adjustable according to the protected area layout. For suspended-type devices, the nozzle faces downward and covers the protected area below. The nozzle orifice dimensions are calculated based on fluid dynamics to ensure the discharge time complies with the national standard requirement (heptafluoropropane discharge time ≤ 10 s).

2.5 Signal Feedback Assemblies

The pressure switch (pressure signal device) is installed on the high-pressure hose or discharge pipeline. When the extinguishing agent is discharged, the pressure rise in the pipeline triggers the pressure switch, which outputs a passive (dry contact) switch signal to the fire suppression controller. Upon receiving the signal, the controller illuminates the discharge indicator light outside the protected area and simultaneously feeds the discharge action signal back to the fire control room.

Pressure switch technical parameters:

Parameter Value
Actuation pressure range 0.2~1.0 MPa, adjustable
Contact rating DC24V/3A
Contact form Normally open / normally closed, selectable
Protection rating IP65

2.6 Alarm and Linkage Control System Composition

2.6.1 Gas Fire Suppression Controller

The gas fire suppression controller is the control core of the system. It is wall-mounted and contains a built-in microprocessor with functions including fire signal reception, logic judgment, delayed output, linkage control, fault monitoring, status display, and event recording.

Main functional modules:

Module Description
Detection loop Connects smoke detectors and heat detectors; supports two-wire bus communication
Control output One or more extinguishing activation outputs; DC24V power output
Linkage output Controls shutdown of HVAC, fresh air, fire dampers, and other equipment
Status display LCD screen showing system status, alarm information, and fault information
Operating keys Manual start, emergency stop, reset, menu settings, and other operations
Backup power supply Built-in backup battery; automatically switches over upon main power failure; endurance ≥ 4 hours

2.6.2 Fire Detectors

A combined smoke and heat detection logic is used. Smoke detectors and heat detectors are simultaneously deployed within the protected area:

  • Point-type photoelectric smoke detector: Detects early-stage smoke; high sensitivity; fast response.
  • Point-type heat detector: Detects ambient temperature rise; available in fixed-temperature, rate-of-rise, and rate-of-rise/fixed-temperature combined types.
  • Dual detection logic: The system enters the extinguishing delay startup sequence only when both the smoke detector and heat detector alarm simultaneously, effectively reducing the probability of inadvertent discharge.

2.6.3 On-Site Alarm and Indication Devices

Device Description
Fire audible and visual alarm Installed inside and outside the protected area; emits audible and visual warning signals upon alarm to alert personnel to evacuate
Discharge indicator light Installed above the entrance door outside the protected area; illuminates when the extinguishing agent is discharged, displaying the warning “GAS DISCHARGED — DO NOT ENTER”
Manual/automatic changeover switch Installed outside the protected area; switches the system between automatic and manual operating modes; switched to manual when personnel enter the protected area to prevent inadvertent discharge
Emergency start/stop button Installed at an easily accessible location outside the protected area; includes both emergency start and emergency stop buttons; pressing emergency stop during the delay phase terminates the discharge sequence

2.6.4 Linkage Peripheral Devices

Device Function
Fire damper Linkage closure of ventilation and air-conditioning ducts to prevent extinguishing agent loss
Electric door closer Linkage closure of protected area doors and windows to ensure sealing
Non-fire power disconnection device Linkage disconnection of non-fire power supply in the protected area
Emergency lighting and evacuation signage Linkage activation of emergency lighting

Chapter 3 Product Classification

The pipeless gas fire suppression system can be classified along multiple dimensions: structural form, extinguishing agent type, activation method, cylinder group quantity, and installation method.

3.1 Classification by Structural Form

3.1.1 Cabinet-Type Pipeless Gas Fire Extinguishing Device

The cabinet-type device is currently the most widely used pipeless product. The extinguishing agent cylinder set, valves, nozzle, and piping are all integrated within a vertical cabinet that is floor-mounted in the protected area.

Product features:

  • Neat structure, attractive appearance, good coordination with data center environments
  • Full range of single-cylinder, dual-cylinder, and multi-cylinder configurations; wide protected volume coverage
  • Extinguishing controller can be built in or external; flexible wiring
  • Easy maintenance and inspection; cylinder pressure and valve status can be checked simply by opening the door
  • Suitable for protected areas with volumes ranging from 100 to 1600 m³

Model designation: GQQXX/2.5-LA. In this designation, G represents cabinet type, Q represents gas, Q represents heptafluoropropane, XX represents the extinguishing agent weight (kg), 2.5 represents the nominal working pressure of 2.5 MPa, and LA is the enterprise code.

3.1.2 Suspended-Type Pipeless Gas Fire Extinguishing Device

The suspended-type device has its extinguishing agent storage cylinder suspended from the ceiling or upper wall section of the protected area. The structure is more compact and occupies no floor space.

Sub-types:

  • Electromagnetic suspended type: Paired with a fire alarm controller; electrically activated; multiple units can be linked; suitable for locations with a fire alarm system.
  • Temperature-sensing suspended type: Comes with a built-in temperature-sensing glass bulb activation element that automatically bursts and activates at the set temperature (e.g., 68°C, 79°C, or 93°C). No external power supply or alarm system is required. Suitable for small unattended spaces where wiring is difficult.

Product features:

  • Simple installation; occupies no floor area; ideal for confined spaces
  • Temperature-sensing type requires no wiring; ready for use immediately after installation
  • Single-unit protected volume is relatively small, typically 8 to 100 m³
  • Low project cost; strong applicability for retrofit projects

Model designation: XQQCXX/1.6-LA. In this designation, X represents suspended type, Q represents gas, Q represents heptafluoropropane, C represents electromagnetic type, XX represents the extinguishing agent weight, and 1.6 represents the nominal pressure.

3.1.3 Wall-Mounted Pipeless Gas Fire Extinguishing Device

The wall-mounted device lies between the cabinet type and the suspended type. It uses a slim-profile cabinet mounted on the wall, occupying minimal space. It is suitable for corridors, narrow equipment rooms, and similar spaces.

3.2 Classification by Extinguishing Agent Type

3.2.1 Heptafluoropropane Pipeless Extinguishing System

The mainstream product on the market. It features mature technology, high cost-effectiveness, and reliable extinguishing performance. It is suitable for the majority of data centers, power distribution rooms, archives, and similar scenarios, and is currently the preferred choice for pipeless systems.

3.2.2 Perfluorohexanone Pipeless Extinguishing System

A high-end environmentally friendly product. The extinguishing agent offers excellent environmental performance and lower toxicity. It is suitable for permanently staffed control centers, premium data centers, museum precious artifact storage, and similar locations. Equipment cost is relatively higher.

3.2.3 Hexafluoropropane Pipeless Extinguishing System

Primarily used for local application scenarios such as the interior of power distribution cabinets and localized protection of precision equipment. It leaves no residue after discharge and provides good insulation performance.

3.3 Classification by Activation Method

3.3.1 Automatic Activation Type

Paired with a fire detection and alarm system, it provides a fully automatic sequence of detection, alarm, delay, and discharge. Suitable for unattended locations or locations with few personnel during normal working hours.

3.3.2 Manual Activation Type

Retains only manual activation and mechanical emergency activation functions. Personnel press the start button after confirming a fire. Suitable for locations with permanent staffing and high personnel density, minimizing the risk of inadvertent discharge.

3.3.3 Temperature-Triggered Self-Activation Type

This is the temperature-sensing suspended device. It relies on the temperature-sensing element to trigger, requires no electrical control, and operates completely independently. Suitable for remote locations without power supply or alarm systems.

3.4 Classification by Cylinder Group Quantity

3.4.1 Single-Cylinder Unit

The cabinet houses one extinguishing agent storage cylinder. Simple structure and lower cost. Suitable for small and medium volume protected areas. Common specifications include 40 L, 70 L, and 90 L single-cylinder units.

3.4.2 Dual-Cylinder Unit

The cabinet houses two extinguishing agent storage cylinders. The primary cylinder is fitted with a solenoid actuator, and the slave cylinder is fitted with a pneumatic actuator for synchronized activation. The extinguishing agent quantity is doubled. Suitable for medium-to-large protected areas, such as 90 L×2 and 120 L×2 dual-cylinder units.

3.4.3 Multi-Cylinder Linkage

Multiple cabinet-type devices are deployed in the same protected area and controlled simultaneously by the fire suppression controller. Suitable for large protected areas ranging from 500 to 1600 m³, supporting linkage of up to 8 units.

3.5 Classification by Storage Pressure

3.5.1 Low-Pressure Storage Type (1.6 MPa / 2.5 MPa)

Stored under normal saturated vapor pressure. Low charging pressure, thinner cylinder walls, lighter weight, easy transportation and installation. This is the mainstream specification for current cabinet-type devices.

3.5.2 High-Pressure Storage Type (4.2 MPa)

Nitrogen-pressurized storage. Faster discharge rate and longer extinguishing agent delivery distance. Suitable for larger protected areas requiring rapid filling.

Chapter 4 Product Checklist

4.1 Standard Configuration Checklist for Cabinet Single-Cylinder Heptafluoropropane Fire Extinguishing Device

Using the GQQ120/2.5-LA cabinet-type heptafluoropropane fire extinguishing device as an example, the standard configuration is as follows:

No. Component Specification/Model Unit Qty Remarks
1 Cabinet shell 1800×600×500 mm, cold-rolled steel plate, powder coated set 1 Computer gray
2 Extinguishing agent storage cylinder 120 L, 2.5 MPa, seamless steel cylinder pc 1 Includes container valve
3 Heptafluoropropane extinguishing agent HFC-227ea, purity ≥ 99.9% kg 120 Filled in cylinder
4 Container valve Copper alloy, with safety relief pc 1 Integrated pressure gauge port
5 Pressure gauge 0~6 MPa, shock-resistant pc 1 With pressure gauge shut-off valve
6 Solenoid actuator DC24V, 1.5A pc 1 With safety pin
7 High-pressure hose DN25, stainless steel braided pcs 1 Length 800 mm
8 Nozzle Atomizing type, copper alloy pc 1 Orifice φ3.2 mm × 6
9 Pressure switch 0.5 MPa actuation, passive contact pc 1 Discharge feedback output
10 Cylinder mounting clamp Galvanized steel plate set 1 Includes bolts
11 Mechanical emergency start handle Steel, powder coated set 1 With operating label
12 Safety relief membrane 3.5 MPa burst pressure pc 1 Plus 1 spare
13 Product nameplate Aluminum, etched pc 1 Mounted on cabinet door
14 Warning labels PVC adhesive set 1 Includes operating instructions
15 Product certificate of conformity — sheet 1 Shipped with product
16 3C certification certificate copy — copy 1 Shipped with product
17 User manual — book 1 Shipped with product

4.2 Standard Configuration Checklist for Alarm and Linkage Control System

The standard configuration for a single protected area alarm and linkage system is as follows:

No. Component Specification/Model Unit Qty Remarks
1 Gas fire suppression controller Single-zone, wall-mounted, DC24V output set 1 Includes backup battery
2 Point-type photoelectric smoke detector Addressable, two-wire bus pc 2 Adjust per area
3 Point-type heat detector Addressable, rate-of-rise/fixed-temperature pc 2 Adjust per area
4 Detector base Dedicated matching base pc 4 Includes terminal blocks
5 Fire audible and visual alarm Addressable, DC24V pc 2 1 inside and 1 outside the area
6 Discharge indicator light 24V, “GAS DISCHARGED — DO NOT ENTER” pc 1 Installed outside the door
7 Emergency start/stop button With protective cover, start and stop dual buttons pc 1 Installed outside the door
8 Manual/automatic changeover switch With status indicator pc 1 Installed outside the door
9 End-of-line resistor 4.7 kΩ / 10 kΩ pc as required At loop termination
10 Terminal junction box 200×300×100 mm pcs 1 In-area wiring
11 Control cable ZR-RVS-2×1.5 m as measured Signal bus
12 Power cable ZR-BV-2×2.5 m as measured 24V power line
13 Metal conduit Φ20 hot-dip galvanized steel tube m as measured Cable protection
14 Conduit clamps, junction boxes, auxiliary materials — batch 1 Installation accessories

4.3 Configuration Checklist for Suspended Electromagnetic-Type Fire Extinguishing Device

Using the XQQC30/1.6-LA model as an example:

No. Component Specification/Model Unit Qty Remarks
1 Extinguishing agent storage cylinder 30 L, 1.6 MPa pc 1 Integrated container valve
2 Heptafluoropropane extinguishing agent HFC-227ea kg 30 Filled
3 Solenoid starter DC24V pc 1 Top-mounted
4 Atomizing nozzle Downward discharge type pc 1 Bottom-mounted
5 Suspension bracket Angle steel, welded, galvanized set 1 Secured with expansion bolts
6 Pressure switch Passive contact output pc 1 Optional
7 Expansion bolts M10×100 set 4 For bracket fixing

4.4 Technical Documentation Checklist

Each product is shipped with the following technical documents:

  • Product certificate of conformity
  • Copy of national compulsory product certification (3C) certificate
  • Product user manual
  • Packing list
  • Extinguishing agent filling record
  • Copy of cylinder inspection report
  • Inspection report of major components
  • Installation and wiring diagram
  • Product warranty card

Chapter 5 Product Working Principles

5.1 Fire Extinguishing Mechanism

Heptafluoropropane extinguishes fire primarily through chemical inhibition, supplemented by physical cooling and oxygen displacement (suffocation):

Chemical Inhibition: Heptafluoropropane molecules decompose under the action of high-temperature flames, producing fluorine-containing active free radicals that combine with active free radicals such as H· and OH· in the combustion reaction, interrupting the combustion chain reaction and causing the flame to be extinguished. This is the primary extinguishing mechanism of heptafluoropropane.

Physical Cooling: Liquid heptafluoropropane rapidly vaporizes after discharge, absorbing a large amount of heat and lowering the temperature of the protected area and the flame, thereby suppressing the combustion reaction.

Suffocation Effect: After vaporization, the extinguishing agent expands dramatically in volume, diluting the oxygen concentration in the protected area and assisting in slowing the combustion reaction.

The three effects work synergistically to extinguish Class A solid surface fires, Class B liquid fires, Class C gas fires, and Class E electrical fires within an extremely short time, with high extinguishing efficiency and no re-ignition.

5.2 System Operating Mode Principles

The pipeless gas fire suppression system has three control modes: automatic control, manual control, and mechanical emergency manual control. The three modes provide progressive backup to ensure system reliability.

5.2.1 Automatic Control Mode

When the system is in the “Automatic” operating state, the fire suppression controller continuously monitors the smoke and heat detector signals within the protected area:

Single-Loop Alarm: When only the smoke detector or only the heat detector alarms, the controller issues a first-level alarm signal. The audible and visual alarm devices inside and outside the protected area activate to alert on-site personnel to inspect for fire, but the extinguishing sequence is not started.

Dual-Loop Alarm: When both the smoke detector and the heat detector alarm simultaneously, the controller confirms a fire condition and enters the second-level alarm state. A 30-second delay countdown starts, and linkage actions are simultaneously initiated to close the HVAC, fresh air supply, fire dampers, doors, and windows, and to disconnect the non-fire power supply.

Delayed Discharge: After the 30-second delay elapses, the controller outputs DC24V activation power to the solenoid actuator. The solenoid actuator operates to open the container valve, and the extinguishing agent is atomized through the nozzle and discharged into the protected area, achieving total-flooding extinguishment.

Signal Feedback: After the extinguishing agent is discharged, the pressure switch operates and feeds the discharge signal back to the controller. The controller illuminates the discharge indicator light and simultaneously transmits the signal to the fire control room.

Emergency Stop: During the 30-second delay phase, if on-site personnel confirm that discharge is not required, the emergency stop button outside the protected area can be pressed to terminate the discharge sequence. The system remains in the alarm state and returns to normal after reset.

5.2.2 Manual Control Mode

When the system is in the “Manual” operating state, detector alarms produce only audible and visual warnings without automatically starting the extinguishing sequence. On-site personnel must confirm the fire and then press the emergency start button outside the protected area to initiate the delayed discharge sequence.

Manual mode is suitable for protected areas frequently entered by personnel, preventing inadvertent extinguishing agent discharge while personnel are present. After personnel leave the protected area, the system should be switched back to automatic mode.

5.2.3 Mechanical Emergency Manual Control Mode

When the electrical control system fails, power is lost, or both automatic and manual control are unavailable, the mechanical emergency activation method may be used:

1. Confirm that all personnel have evacuated the protected area

2. Close the doors, windows, air-conditioning, and ventilation equipment of the protected area

3. Remove the safety pin from the solenoid actuator

4. Forcefully pull the mechanical emergency handle on the container valve to strike and open the container valve

5. The extinguishing agent is discharged through the nozzle to extinguish the fire

Mechanical emergency activation is a purely mechanical mechanism that does not rely on any power supply or electronic components. It is the ultimate activation safeguard of the system.

5.3 Multi-Unit Linkage Working Principle

When a single protected area has a large volume requiring multiple cabinet units linked for protection, the fire suppression controller outputs a synchronized activation signal to the solenoid actuators of all units, ensuring that all units receive the activation signal simultaneously. Due to differences in mechanical performance, an action response time difference of ≤ 2 s is permitted. Within this tolerance, the extinguishing agent still mixes uniformly and satisfies the total-flooding extinguishing concentration requirement.

In a dual-cylinder cabinet, the primary cylinder is opened by the solenoid actuator. A portion of the high-pressure extinguishing agent inside the cylinder is diverted through the activation tubing to drive the pneumatic actuator of the slave cylinder, achieving synchronized discharge of both cylinders and ensuring the extinguishing agent release rate and total dosage.

5.4 Fault Monitoring Principle

The fire suppression controller has comprehensive fault self-diagnostic functions:

Fault Type Description
Main power fault Main power outage or abnormal voltage; automatic switchover to backup battery with audible and visual fault signal
Backup power fault Backup battery low voltage or disconnection; fault signal issued
Loop fault Detector loop short circuit, open circuit, or detector offline; fault signal issued
Activation line fault Extinguishing activation line open circuit or short circuit; fault signal issued
Pressure feedback fault Abnormal pressure switch circuit; fault signal issued

All fault information is displayed on the LCD and recorded, facilitating troubleshooting by operation and maintenance personnel.

Chapter 6 Product Technical Parameters

6.1 Cabinet-Type Heptafluoropropane Fire Extinguishing Device Technical Parameters

Using the GQQ series products of Guangzhou Lain Intelligent System Development Co., Ltd. as an example, the technical parameters for each specification are as follows:

Parameter GQQ40/2.5-LA GQQ70/2.5-LA GQQ90/2.5-LA GQQ120/2.5-LA GQQ150/2.5-LA
Extinguishing agent charge 40 kg 70 kg 90 kg 120 kg 150 kg
Storage cylinder capacity 40 L 70 L 90 L 120 L 150 L
Nominal working pressure 2.5 MPa 2.5 MPa 2.5 MPa 2.5 MPa 2.5 MPa
Maximum working pressure 3.5 MPa 3.5 MPa 3.5 MPa 3.5 MPa 3.5 MPa
Safety relief actuation pressure 3.5±0.2 MPa 3.5±0.2 MPa 3.5±0.2 MPa 3.5±0.2 MPa 3.5±0.2 MPa
Extinguishing agent discharge time ≤10 s ≤10 s ≤10 s ≤10 s ≤10 s
Extinguishing concentration 5.8%~8% 5.8%~8% 5.8%~8% 5.8%~8% 5.8%~8%
Maximum protected volume ~500 m³ ~850 m³ ~1100 m³ ~1450 m³ ~1600 m³
Solenoid activation voltage DC24V DC24V DC24V DC24V DC24V
Solenoid activation current ≤1.5A ≤1.5A ≤1.5A ≤1.5A ≤1.5A
Pressure switch contact rating DC24V/3A DC24V/3A DC24V/3A DC24V/3A DC24V/3A
Operating ambient temperature 0~50℃ 0~50℃ 0~50℃ 0~50℃ 0~50℃
Cabinet dimensions (H×W×D) 1700×500×400 mm 1750×550×450 mm 1800×600×500 mm 1850×650×550 mm 1900×700×600 mm
Total unit weight ~95 kg ~160 kg ~200 kg ~260 kg ~320 kg
Protection rating IP30 IP30 IP30 IP30 IP30
Service life ≥20 years ≥20 years ≥20 years ≥20 years ≥20 years

6.2 Suspended-Type Heptafluoropropane Fire Extinguishing Device Technical Parameters

Parameter XQQW10/1.6-LA XQQC20/1.6-LA XQQC30/1.6-LA XQQC40/2.5-LA
Extinguishing agent charge 10 kg 20 kg 30 kg 40 kg
Storage cylinder capacity 10 L 20 L 30 L 40 L
Nominal working pressure 1.6 MPa 1.6 MPa 1.6 MPa 2.5 MPa
Activation method Temperature-sensing glass bulb Solenoid activation Solenoid activation Solenoid activation
Temperature-sensing actuation temperature 68℃ (optional 79/93℃) — — —
Discharge time ≤8 s ≤8 s ≤8 s ≤10 s
Maximum protected volume ~80 m³ ~240 m³ ~360 m³ ~500 m³
Operating ambient temperature 0~50℃ 0~50℃ 0~50℃ 0~50℃
Device diameter φ219 mm φ273 mm φ325 mm φ325 mm
Device overall height 550 mm 750 mm 900 mm 1050 mm
Total unit weight ~25 kg ~55 kg ~80 kg ~105 kg

6.3 Gas Fire Suppression Controller Technical Parameters

Using the single-zone gas fire suppression controller as an example:

Parameter Technical Specification
Operating voltage AC220V±15%, 50Hz
Backup power supply DC24V/7Ah lead-acid battery × 2
Backup power endurance ≥4 hours (standby state)
Detection loop 1 loop, up to 32 addressable points
Communication method Two-wire bus, non-polarized
Extinguishing activation output 1 channel, DC24V/3A
Linkage output 2 channels, DC24V/1A (expandable)
Feedback input 2 channels of passive dry contacts
Display 128×64 dot-matrix LCD
Operation method Membrane keypad
Event log 1000 records, retained on power loss
Operating environment Temperature -10~55℃, humidity ≤95%RH non-condensing
Dimensions 380×280×100 mm (wall-mounted)
Mounting method Wall-mounted, fixed with M6 expansion bolts
Protection rating IP30
Relative humidity ≤95%, non-condensing

6.4 Main Component Performance Parameters

6.4.1 Container Valve

Parameter Value
Nominal diameter DN25, DN32, DN40
Nominal pressure 2.5 MPa, 4.2 MPa
Operating temperature -20~60℃
Sealing performance No leakage at 1.1× nominal pressure
Strength performance No deformation or rupture at 1.5× nominal pressure
Opening reliability No malfunction over 100 actuation cycles

6.4.2 Solenoid Actuator

Parameter Value
Rated voltage DC24V
Actuation voltage range DC18V~DC28V
Starting current ≤1.5A
Insulation resistance ≥100 MΩ
Dielectric strength AC500V/1 min, no breakdown
Mechanical life ≥100 cycles
Operating environment -20~60℃

6.4.3 Pressure Switch

Parameter Value
Actuation pressure 0.2~1.0 MPa adjustable; factory-set at 0.5 MPa
Contact form 1 normally open + 1 normally closed
Contact rating DC24V/3A, AC220V/1A
Operating pressure range 0~6 MPa
Port thread G1/2″
Protection rating IP65

6.4.4 Point-Type Smoke Detector

Parameter Value
Operating voltage Bus 24V
Standby current ≤0.5 mA
Alarm current ≤2 mA
Sensitivity class 3 levels, adjustable
Protection area 60~80 m²
Ambient temperature -10~55℃
Relative humidity ≤95%RH

6.4.5 Point-Type Heat Detector

Parameter Value
Operating voltage Bus 24V
Standby current ≤0.5 mA
Alarm current ≤2 mA
Type Rate-of-rise/fixed-temperature combined
Actuation temperature 60℃ (fixed temperature)
Protection area 20~30 m²
Ambient temperature -10~60℃

6.5 System Performance Specifications

Parameter Value
Fire extinguishing response time Delay of 0~30 s adjustable after dual-alarm confirmation; default 30 s
Extinguishing agent discharge time ≤10 s (heptafluoropropane)
Extinguishing time Visible flame extinguished within 10 s of discharge
System reliability MTBF ≥ 100,000 hours
Multi-unit linkage time difference ≤2 s
Power adaptability Normal operation at main power AC187~242V
Interference resistance Complies with EMC requirements of GB 16838

Chapter 7 Product Functions and Features

7.1 Core Functions

7.1.1 Fire Detection and Alarm Function

The system monitors fire conditions in the protected area in real time through dual smoke and heat detectors with graded alarms: first-level pre-alarm (single detector alarm) and second-level fire alarm (both detectors alarming simultaneously). The audible and visual alarm devices emit warning signals at different frequencies to help on-site personnel assess the fire alarm level.

7.1.2 Automatic Fire Extinguishing Control Function

The combined smoke and heat alarm logic effectively reduces the probability of false alarms and inadvertent discharge. An adjustable discharge delay of 0 to 30 seconds is supported, allowing time for personnel evacuation. During the delay period, linkage actions close ventilation, air-conditioning, fire dampers, doors, and windows, and disconnect non-fire power supplies to maintain the sealing of the protected area and improve extinguishing efficiency.

7.1.3 Manual Control Function

Emergency start/stop buttons and a manual/automatic changeover switch are installed outside the protected area. Personnel switch to manual mode upon entering, can manually start upon fire confirmation, and can perform an emergency stop in the event of a false alarm. Operation is flexible and safely controllable.

7.1.4 Mechanical Emergency Activation Function

The purely mechanical emergency activation device does not depend on power supply or electrical control systems. It can still reliably initiate extinguishing under extreme conditions. The triple activation safeguard ensures fail-safe operation.

7.1.5 Status Indication and Feedback Function

  • Discharge indicator light installed outside the protected area, illuminated during discharge to warn personnel against entry
  • Controller displays system status, alarm location, and fault information in real time
  • Discharge action signals can be uploaded to the fire control room main console for centralized monitoring
  • Manual/automatic status indication is clearly displayed for duty personnel to monitor the system mode

7.1.6 Fault Monitoring and Alarm Function

The controller continuously monitors the main and backup power supplies, detection loops, activation lines, and feedback lines 24 hours a day. In the event of any fault, an audible and visual fault signal is issued immediately, and the LCD displays the specific fault type and location for rapid troubleshooting and repair.

7.1.7 Event Recording Function

The system automatically records all alarm, fault, activation, and operation events, including event time, type, and location information. The storage capacity is ≥1000 records, retained on power loss, facilitating post-event traceability and incident analysis.

7.1.8 Multi-Unit Linkage Function

Supports synchronized linkage activation of up to 8 pre-engineered fire extinguishing devices, with an action response time difference of ≤2 s. Suitable for large-volume protected areas, ensuring uniform extinguishing agent distribution and compliance with extinguishing concentration requirements.

7.2 Product Features

7.2.1 Convenient Installation and Deployment, Short Project Cycle

The pipeless design requires no dedicated storage room and no complex delivery piping. The cabinet arrives as a complete unit. On-site installation only requires securing the cabinet and connecting the alarm wiring. Compared with piped systems, construction workload is reduced by more than 70%, and the project cycle is significantly shortened. This is particularly suitable for fire protection retrofits of existing buildings.

7.2.2 No Extinguishing Agent Pipeline Loss, High Extinguishing Efficiency

The extinguishing agent is discharged directly from the cabinet nozzle into the protected area, with no residual agent loss or pressure drop caused by pipeline conveyance. The extinguishing agent utilization rate is high, discharge speed is fast, and the extinguishing concentration can be achieved in the shortest possible time, rapidly extinguishing early-stage fires and controlling fire spread.

7.2.3 Clean and Environmentally Friendly, No Secondary Damage to Protected Objects

Heptafluoropropane is clean, colorless, non-conductive, and non-corrosive. After discharge, it rapidly vaporizes with no residue, causing no water damage, staining, or corrosion to servers, switches, precision instruments, paper archives, cultural relics, or calligraphy and paintings. The protected area can be quickly restored to normal use after extinguishment.

7.2.4 Safe and Reliable, Multiple Protection Mechanisms

  • Combined smoke and heat detection logic reduces inadvertent discharge probability
  • 30-second delay for evacuation ensures personnel safety
  • Emergency stop function terminates inadvertent discharge
  • Triple activation modes serve as mutual backup
  • Overpressure safety relief prevents cylinder explosion
  • Comprehensive fault monitoring identifies hidden hazards in advance

7.2.5 Simple Operation and Maintenance, Low Total Cost

The system is highly integrated with standardized components. Routine maintenance only requires periodic pressure checks, detector cleaning, and linkage function testing. No complex pipeline purging or pressure testing is required. Operation and maintenance workload is minimal, resulting in low long-term usage costs.

7.2.6 Attractive Structure, Suitable for Data Center Environments

Cabinet-type devices use cold-rolled steel plates with electrostatic spraying, providing a smooth and attractive appearance. The color can be coordinated with the data center decoration style without compromising the overall aesthetics of the protected area. Suitable for data centers, control rooms, and other locations with aesthetic requirements.

7.2.7 Flexible Configuration, Wide Applicability

From 10 kg suspended types to 150 kg cabinet types, from single-cylinder units to multi-cylinder linkage configurations, a wide range of specifications is available to cover protected areas ranging from 8 m³ to 1600 m³, meeting the fire protection needs of different scales and scenarios.

The pipeline-less gas fire suppression system is suitable for extinguishing Class A, B, C, and E fires. It is widely applied to the protection of small-to-medium, standalone important equipment and valuable goods. Typical application scenarios are as follows:

8.1 Data Center and Computer Room Applications

8.1.1 Small-to-Medium Computer Rooms

Enterprise server rooms, network rooms, surveillance/monitoring rooms, etc., typically ranging from tens to several hundred square meters, housing servers, switches, routers, storage devices, and other precision electronic equipment. These are the most typical application scenarios for the pipeline-less heptafluoropropane system. The system extinguishes fire without electrical conductivity and leaves no residue, causing no secondary damage to equipment. It features flexible installation and does not require a separate cylinder room.

8.1.2 Telecommunications Rooms and Base Stations

Telecom operator base station rooms, access network rooms, transmission rooms, small IDC rooms, etc. These spaces are independent, house high-value equipment, and are normally unattended. The pipeline-less system provides fully automatic fire protection. Suspended units are particularly suitable for confined base station rooms.

8.1.3 UPS Power Distribution Rooms and Battery Rooms

UPS power rooms, battery rooms, precision power distribution rooms, etc. These present risks of electrical fire and battery electrolyte leakage fires. Heptafluoropropane effectively extinguishes electrical and liquid fires without causing battery short circuits or damage to power distribution equipment.

8.2 Electrical Power Applications

8.2.1 Power Transformation and Distribution Rooms

High/low voltage power distribution rooms, transformer rooms, capacitor rooms, switchgear rooms, etc. These areas feature dense electrical equipment at high voltage levels. Water sprinkler suppression can easily cause short circuits and equipment damage, making gas suppression the optimal solution. Small-to-medium distribution rooms are suited for cabinet-type pipeline-less systems; large distribution rooms can use multiple units in coordinated operation.

8.2.2 Generator Rooms

Diesel generator rooms present fuel fire risks. Heptafluoropropane effectively extinguishes Class B liquid fires and electrical fires, leaving no residue after discharge and not affecting subsequent generator operation.

8.2.3 Electrical Control Rooms and Control Cabinets

Industrial automation control rooms, PLC control cabinets, variable frequency drive cabinets, DCS system cabinets, etc. These contain numerous precision electronic components with high cleanliness requirements for extinguishing agents. Pipeline-less gas suppression provides precise protection.

8.3 Archives, Cultural, and Museum Applications

8.3.1 Archives and Document Repositories

Archive rooms of government agencies and enterprises, financial records rooms, personnel file repositories, etc. Paper archives are valuable and irreplaceable — water suppression would cause irreversible water damage. Heptafluoropropane extinguishes fires without residue or contamination, preserving archival materials intact.

8.3.2 Libraries and Rare Book Repositories

Library special collections rooms, rare book storerooms, precious book repositories, etc. These require extremely high cleanliness of the extinguishing medium. Gas suppression extinguishes fires without damaging books.

8.3.3 Museums and Artifact Warehouses

Museum artifact exhibition halls, artifact repositories, art gallery collection storage, etc. Priceless cultural relics can suffer irreversible damage from any water stains or contamination. Clean gas suppression is the preferred fire protection solution.

8.4 Industrial and Scientific Research Applications

8.4.1 Precision Instrument Rooms

Metrology and testing rooms, calibration laboratories, precision instrument workshops, etc. High-precision instruments are expensive and demand high environmental cleanliness. Gas suppression does not cause instrument contamination or precision degradation.

8.4.2 Chemical Laboratories

Small-to-medium chemical laboratories and pharmaceutical storerooms present risks of flammable liquid and gas fires. Total-flooding gas suppression quickly controls fire incidents and prevents chemical spread.

8.4.3 Clean Production Workshops

Electronics manufacturing cleanrooms, pharmaceutical clean production areas, etc. These demand high production environment cleanliness. Water sprinklers and dry powder suppression both cause environmental contamination and product scrap; clean gas suppression has the minimal impact.

8.5 Other Important Locations

8.5.1 Banks and Financial Institutions

Bank data rooms, cash vaults, safe rooms, certificate repositories, etc. These have high security requirements and are well suited for pipeline-less gas fire suppression systems.

8.5.2 Medical Equipment Rooms

Hospital MRI rooms, CT rooms, precision medical equipment rooms, etc. Equipment is expensive and sensitive to water and contamination; gas suppression offers excellent compatibility.

8.5.3 Broadcasting and Television Stations

Radio/TV broadcast control rooms, transmission rooms, studio equipment rooms, etc. These protect broadcast continuity and prevent on-air incidents caused by fire.

8.6 Non-Applicable Scenarios

The pipeline-less gas fire suppression system is not suitable for the following fire types and locations:

  • Fires involving chemicals that oxidize rapidly without air, such as nitrocellulose, explosives, and strong oxidizers
  • Fires involving active metals such as potassium, sodium, magnesium, and titanium
  • Fires involving metal hydrides, strong reducing agents, and similar substances
  • Fires involving chemicals capable of self-decomposition
  • Public places with dense occupancy and inadequate evacuation routes
  • Areas with frequent occupancy and no rapid evacuation capability (concentration safety must be assessed)
  • Open spaces or areas with good ventilation where extinguishing concentration cannot be maintained

9.1 Pre-Installation Preparation

9.1.1 Technical Preparation

  • Familiarize with construction drawings, product manuals, and relevant codes and standards; conduct technical disclosure meetings
  • Verify protected zone dimensions, volumes, door/window structures, and ventilation conditions; confirm compliance with design requirements
  • Confirm equipment models, specifications, and quantities match design documents
  • Plan cabinet installation positions, detector points, and conduit routing; perform on-site layout marking

9.1.2 Site Condition Preparation

  • Civil construction and finishing of the protected zone substantially complete; floor flat and solid; walls capable of securing conduit
  • Protected zone doors/windows, pressure relief openings, ventilation/air conditioning, fire dampers, and other supporting facilities installed
  • On-site power supply available and adequate for construction
  • Site cleaned and free of flammable/explosive materials; ready for equipment delivery
  • Confirm protected zone enclosure structural pressure resistance ≥ 1200 Pa in compliance with code requirements

9.1.3 Equipment and Material Incoming Inspection

  • Inspect equipment packaging integrity; check for impacts, scratches, or moisture damage
  • Verify equipment models, specifications, and quantities match the packing list
  • Confirm product certificates of quality, 3C certificates, inspection reports, and other technical documents are complete
  • Inspect extinguishing agent cylinders for deformation or corrosion; pressure gauge indicator within the green normal range
  • Inspect valves, nozzles, detectors, and other components for visible damage or cracks
  • Verify cable, conduit, and accessory specifications meet design requirements with acceptable quality

9.1.4 Construction Tool Preparation

  • Installation tools: rotary hammer drill, hand drill, wrench set, socket set, screwdrivers, spirit level, tape measure, plumb bob, ladder
  • Electrical tools: wire strippers, crimping pliers, multimeter, megohmmeter, voltage tester, soldering iron, insulating tape
  • Specialized tools: cylinder transport cart, torque wrench, pressure gauge calibration instrument
  • Safety equipment: safety helmet, gloves, safety goggles, safety harness, fire extinguishers

9.2 Cabinet-Type Extinguishing Unit Installation Steps

9.2.1 Positioning and Securing the Cabinet

  • Determine cabinet installation position per design drawings; typically placed in protected zone corners or against walls, at a distance ≥ 300 mm from the wall for maintenance access
  • Cabinet position should avoid entrances/exits and evacuation routes; nozzle discharge direction should face the protected zone center with no obstructions
  • Use a spirit level to calibrate cabinet verticality; verticality deviation ≤ 2‰
  • Secure cabinet base to the floor with expansion bolts; minimum 4 anchor points per cabinet to ensure stability
  • In seismically required areas, install seismic bracing brackets on the cabinet back connected to the wall

9.2.2 Cylinder Assembly Installation

  • Open the cabinet front door and remove internal securing accessories
  • Use a cylinder transport cart to move the extinguishing agent cylinder smoothly into the cabinet; cylinder valve facing the operating side
  • Adjust cylinder position so the cylinder is vertical; verticality deviation ≤ 1‰
  • Install fixing clamps, evenly tighten bolts to securely fix the cylinder to the cabinet bracket
  • For dual-cylinder assemblies, secure the primary cylinder (right side) first, then the secondary cylinder (left side); adjust spacing to allow smooth startup piping connection

9.2.3 Valve and Piping Connection

  • Check sealing surfaces of all cylinder head valve ports for damage or foreign matter
  • Wrap PTFE tape on the pressure gauge thread and install onto the cylinder head valve pressure gauge port; tighten moderately with a wrench; orient the gauge for easy viewing
  • Connect one end of the high-pressure flexible hose to the cylinder head valve extinguishing agent outlet; apply PTFE tape or use sealing gaskets on threads; tighten with a wrench
  • Connect the other end of the high-pressure flexible hose to the nozzle inlet; ensure nozzle discharge direction faces outward
  • Install the pressure switch on the high-pressure hose or nozzle side port; ensure proper sealing
  • For dual-cylinder assemblies, connect startup gas piping: primary cylinder startup gas port → pneumatic actuator port; ensure reliable sealing of all pipe joints
  • Check all connection points for looseness or misalignment; ensure the high-pressure hose has no twisting or kinking

9.2.4 Nozzle Installation

  • Pre-mount the nozzle in the cabinet top or side mounting holes
  • Adjust nozzle angle so discharge coverage reaches the main protected areas without obstruction
  • Tighten nozzle retaining nuts to prevent loosening
  • Check nozzle orifices are free of blockage; if dust caps are fitted, retain them until commissioning is completed, then remove

9.2.5 Solenoid Actuator Installation

  • Confirm the system is de-energized; pull out the safety pin to check free movement, then reinsert
  • Align the solenoid actuator with the cylinder head valve startup port and thread it in clockwise
  • Tighten moderately with a wrench to ensure a secure connection
  • Dress the solenoid actuator lead wires through the cabinet rear cable outlet; label appropriately
  • Install the pneumatic actuator on the secondary cylinder of dual-cylinder assemblies using the same method

9.2.6 Mechanical Emergency Mechanism Inspection

  • Check the emergency handle is securely mounted, operates freely, and shows no binding
  • Confirm clear labeling at the emergency operating point indicating the protected zone name and operating method
  • Check the handle safety lock is intact to prevent accidental operation

9.3 Alarm and Control Equipment Installation

9.3.1 Gas Extinguishing Controller Installation

  • Controller is typically wall-mounted in the corridor outside the protected zone or in a duty room; mounting height with bottom edge at 1.5 m above floor
  • Drill holes in the wall per mounting hole positions; insert expansion anchors; secure the controller mounting plate with screws
  • Hang the controller on the mounting plate; level it; ensure secure fit without wobble
  • Controller should be ≥ 50 mm from the wall for heat dissipation and wiring access
  • Controller grounding terminal must be reliably connected to protective earth; grounding resistance ≤ 4 Ω

9.3.2 Fire Detector Installation

  • Mounting spacing: Smoke detector protection radius ≤ 6.7 m, spacing ≤ 15 m, distance from wall ≤ 7.5 m; heat detector protection radius ≤ 4.4 m, spacing ≤ 8 m, distance from wall ≤ 4 m
  • Mounting height: Under ceiling installation; detector base 0.05–0.3 m below the ceiling
  • Installation requirements:
  • Detectors shall be mounted horizontally; tilt angle ≤ 45°
  • Avoid air conditioning supply vents, ventilation openings, and lighting heat sources
  • Distance from light fixtures ≥ 0.5 m; distance from sprinkler heads ≥ 0.3 m
  • Perforated ceilings must ensure effective detector sensing
  • Detector base securely fastened; after wiring, twist detector into base and confirm proper contact

9.3.3 Audible and Visual Alarm Installation

  • Install one unit inside and one outside the protected zone; wall-mounted with bottom edge at 2.2–2.5 m above floor
  • Mount in conspicuous locations; sound pressure level ≥ 60 dB; in high ambient noise areas, must exceed background noise by 15 dB
  • Secure wiring; test audible and visual function after installation

9.3.4 Gas Discharge Indicator Light Installation

  • Mount above the outside of the protected zone entrance door; 0.2 m from door frame; bottom edge at 2.0–2.2 m above floor
  • Indicator face oriented toward the entrance direction; clear and conspicuous
  • Securely fixed; wiring correct

9.3.5 Emergency Start/Stop Button and Auto/Manual Switch Installation

  • Mount at easily operable positions outside the protected zone door; bottom edge at 1.3–1.5 m above floor
  • Emergency start/stop button shall have a protective cover to prevent accidental operation
  • Auto/manual switch shall have clear “AUTO” and “MANUAL” markings with status indication
  • Securely mounted; wiring terminals correspond correctly

9.4 Conduit and Cable Installation

9.4.1 Conduit Installation Requirements

  • All control and signal circuits must be routed through hot-dipped galvanized steel conduit; PVC plastic conduit is prohibited
  • Conduit wall thickness ≥ 1.5 mm; conduit size selected per cable quantity; total cable cross-sectional area ≤ 40% of conduit internal cross-sectional area
  • Conduit joints shall use threaded connections; apply conductive compound at joints to ensure electrical continuity
  • Conduit bend radius ≥ 6 times the conduit diameter; no creases or dents at bends
  • Conduit secured with pipe clamps at 1.5 m intervals; additional clamps at bends and both ends of junction boxes
  • Where conduit passes through walls or floors, install sleeves; fill gaps with fire-stop sealing material
  • Conduit in ceiling voids must be independently supported; not resting on ceiling framework
  • All metal conduit and junction boxes must be reliably grounded, forming a continuous electrical path

9.4.2 Cable Selection and Installation

  • Signal bus: Flame-retardant twisted pair ZR-RVS-2×1.5 mm², used for detector, audible/visual alarm, and module communications
  • Power circuits: Flame-retardant solid wire ZR-BV-2×2.5 mm², used for DC 24 V power supply and startup output
  • Interlock circuits: ZR-BV-2×1.5 mm², used for fire dampers, fans, and other interlock control
  • Grounding circuit: BV-1×4 mm² yellow-green dual-color wire, reliably grounded
  • Cables of different voltage levels and different circuits shall be routed in separate conduits; sharing is prohibited
  • Conduct continuity and insulation tests on cables before installation; insulation resistance ≥ 20 MΩ
  • No intermediate splices along cable runs; all splices must be made in junction boxes or terminal enclosures
  • Reserve 10–20 cm of cable slack at both ends; apply permanent labels indicating circuit number and purpose
  • Use pulling wire when threading cables through conduit; never force-drag cables to prevent insulation damage
  • In strong electromagnetic interference environments, use shielded cable with the shield grounded at one end

9.5 Suspended Extinguishing Unit Installation Points

  • Position confirmation: Suspend from the protected zone ceiling; nozzle facing vertically downward; no obstructions within the protected coverage area
  • Bracket installation: Use angle steel brackets anchored to the concrete ceiling with expansion bolts; minimum 4 anchor points; load capacity ≥ 5 times the unit weight
  • Cylinder suspension: Mount the unit smoothly onto the bracket; lock fixing bolts; confirm secure suspension
  • Plumb adjustment: Use a plumb bob to calibrate cylinder verticality; deviation ≤ 2‰
  • Solenoid actuator and wiring: Same as cabinet-type units; route wiring down through conduit; provide water protection
  • Heat-sensitive (fusible) type units: Heat-sensitive glass bulb facing downward; avoid external impact; do not paint over or obstruct

9.6 Installation Quality Inspection

After installation, perform item-by-item self-inspection of installation quality:

  • Cabinet installed securely; verticality compliant; door opens smoothly
  • Cylinder assembly reliably secured; no loosening or tilting
  • All piping connections tight; no leakage traces; high-pressure hose free of twisting
  • Nozzle direction correct; orifices unobstructed
  • Pressure gauge indication normal, within green operating range
  • Detector points comply with design; securely installed
  • Conduit routing straight and level; securely fastened; labels clear
  • All exposed ports protected; no foreign matter ingress
  • Grounding reliable; grounding resistance compliant
  • Site cleaned up; equipment surfaces free of stains and damage

10.1 General Wiring Rules

  • All wiring operations must be performed with power disconnected; energized wiring is strictly prohibited
  • Wiring personnel must hold valid qualifications and be familiar with fire alarm electrical wiring codes
  • Verify cable labels against terminal definitions before wiring to prevent incorrect connections
  • Cable stripping length 5–8 mm; copper conductors free of loose strands; use cold-pressed terminals for termination — direct wire wrapping is prohibited
  • Terminal connections must be secure with good contact; no loose connections, shorts, or grounding hazards
  • After wiring, dress and bundle cables neatly; apply wire number labels
  • After all wiring is complete, perform insulation resistance and continuity tests; only then may power be applied

10.2 Controller Terminal Descriptions

Typical single-zone gas extinguishing controller terminal layout and function definitions (models may vary slightly; refer to the product wiring diagram for the specific model):

10.2.1 Power Terminals

Terminal Function
L, N, G Main power input, AC 220 V; L = live, N = neutral, G = protective earth
+24V, GND Backup power output, DC 24 V, external power supply
BAT+, BAT- Backup battery connection terminals

10.2.2 Detection Loop Terminals

Terminal Function
Z1, Z2 Two-wire bus loop terminals, non-polarized, connecting all addressable detectors and modules
— End-of-line resistor at loop end, typically 4.7 kΩ

10.2.3 Extinguishing Control Terminals

Terminal Function
QD+, QD- Extinguishing startup output terminals, DC 24 V/3 A, connecting the solenoid actuator
FK+, FK- Feedback input terminals, dry contact, connecting to pressure switch normally-open contacts

10.2.4 Interlock Output Terminals

Terminal Function
LD1+, LD1- First interlock output group, DC 24 V/1 A, for shutting down air conditioning, fire dampers, etc.
LD2+, LD2- Second interlock output group, DC 24 V/1 A, for cutting non-fire power, etc.

10.2.5 Field Device Terminals

Terminal Function
S+, S- Audible/visual alarm control output
STOP+, STOP- Emergency stop button input
START+, START- Emergency start button input
AUTO, MAN Auto/manual transfer switch input

10.3 Detailed Wiring Methods

10.3.1 Main Power and Backup Power Wiring

  • Connect AC 220 V mains to controller terminals L and N, ensuring correct live/neutral orientation
  • Connect protective earth to terminal G; ensure reliable grounding
  • Connect backup battery to BAT+ and BAT- terminals observing polarity; red positive, black negative; reverse connection is strictly prohibited
  • After wiring, verify voltage is normal with no short circuit

10.3.2 Detection Loop Wiring

  • Route the two-wire bus from controller terminals Z1 and Z2
  • Connect all smoke detectors and heat detectors in series along the loop; detector bus terminals are non-polarized
  • Connect an end-of-line resistor across the last detector terminals at the loop end
  • Multiple detectors shall be connected in a daisy-chain (hand-to-hand) configuration; star connection is strictly prohibited
  • After wiring, measure loop resistance to confirm normal; no short or open circuit

10.3.3 Extinguishing Startup Circuit Wiring

  • Route startup cable from controller terminals QD+ and QD-
  • Install through conduit to the cabinet unit; connect to the two solenoid actuator lead wires
  • For multiple coordinated units, all solenoid actuators are connected in parallel to the startup circuit
  • Observe polarity; reverse connection prevents operation (except for non-polarized actuators on some models)
  • Measure resistance at the circuit end to confirm continuity

10.3.4 Pressure Feedback Circuit Wiring

  • Route feedback cable from controller terminals FK+ and FK-
  • Connect to the pressure switch normally-open contact terminals
  • Multiple units may share the feedback circuit; pressure switch contacts connected in parallel
  • After wiring, manually trigger the pressure switch; the controller should receive the feedback signal

10.3.5 Emergency Start/Stop Button Wiring

  • Emergency start button: connect normally-open contact terminals to controller START+ and START-
  • Emergency stop button: connect normally-open contact terminals to controller STOP+ and STOP-
  • For buttons with indicator lamps, connect lamps to the corresponding power terminals
  • After wiring, test button functions; the controller should respond accordingly when pressed

10.3.6 Auto/Manual Transfer Switch Wiring

  • Connect transfer switch common terminal to the COM terminal
  • Connect auto position to the AUTO terminal; manual position to the MAN terminal
  • Connect status indicator lamps to corresponding power supply
  • Toggle the switch; the controller should correctly display the operating mode

10.3.7 Audible/Visual Alarm Wiring

  • Connect inside and outside audible/visual alarms in parallel to terminals S+ and S-
  • Observe polarity; reverse connection results in no lamp illumination or no sound
  • Test after wiring; alarms should activate simultaneously during alarm conditions

10.3.8 Gas Discharge Indicator Light Wiring

  • Connect the discharge indicator light power terminals in parallel to the startup output terminals, or to dedicated discharge indicator terminals
  • Alternatively, use the pressure switch contacts to energize a 24 V supply to illuminate the indicator
  • Test after wiring; simulate discharge to verify indicator illumination

10.3.9 Interlock Device Wiring

  • Interlock devices such as fire dampers and air conditioning fans connect to the bus through control modules
  • Or connect directly to interlock output terminals; device operating current ≤ 1 A
  • High-current devices require adding intermediate relays for capacity expansion
  • Test interlock actions after wiring; devices should close/cut off correctly during alarm conditions

10.4 Wiring Workmanship Requirements

  • Terminal connections: Maximum 2 wires per terminal; stranded wires must be terminated with ferrules/crimped terminals
  • Wire number labels: Install number sleeves on both cable ends indicating loop number and terminal number; markings clear and fade-resistant
  • Cable bundling: Dress cables neatly in the cabinet with cable ties; straight and level; no crossed or tangled wires
  • Shielding: Connect the shield of shielded cables to the controller grounding terminal at one end only
  • Waterproofing: Seal junction boxes with waterproofing treatment in outdoor and damp locations
  • Fire stopping: Seal conduit pass-throughs at walls and floors with fire-stop putty
  • Cable slack: Coil and secure reserved cable neatly in vacant cabinet space

10.5 Post-Wiring Inspection and Testing

  • Visual inspection: All wiring correct and secure; no wrong or missed connections
  • Insulation test: Measure insulation resistance of each circuit to ground and between circuits using a 500 V megohmmeter; ≥ 20 MΩ
  • Continuity test: Measure each circuit with a multimeter; confirm normal continuity with no open circuits
  • Short circuit test: Confirm no short circuits in any circuit and no grounding faults
  • Polarity check: Verify DC equipment polarity is correct; no reverse connections
  • Grounding check: Protective and functional grounding reliable; grounding resistance ≤ 4 Ω
  • System commissioning may proceed only after all inspections and tests pass.

After system installation and wiring are complete, comprehensive commissioning must be performed to verify system functions comply with design and code requirements, ensuring reliable operation after handover. Commissioning shall be conducted by qualified professional technical personnel, strictly following the commissioning procedures to ensure personnel and equipment safety.

11.1 Pre-Commissioning Preparation

11.1.1 Documentation Preparation

  • System design drawings and design specifications
  • Product manuals, wiring diagrams, certificates of quality
  • Installation records and concealed work acceptance records
  • Commissioning record forms for item-by-item completion

11.1.2 On-Site Inspection

  • Confirm all equipment installed and securely fixed
  • Confirm all wiring correct and clearly labeled
  • Confirm protected zone doors/windows, pressure relief openings, and ventilation facilities comply with requirements
  • Confirm no unauthorized personnel in the protected zone; evacuation routes clear
  • Confirm no flammable/explosive materials or obstacles affecting commissioning
  • Confirm main and backup power supplies normal with correct voltage

11.1.3 Safety Measures

  • Notify relevant parties prior to commissioning; post warning signs; prohibit unauthorized entry
  • Commissioning personnel familiar with operating procedures and emergency response methods
  • Remove solenoid actuator safety pins or disconnect the startup circuit before commissioning to prevent accidental agent discharge
  • Prepare two-way communication equipment for constant contact between inside and outside
  • Provide necessary protective equipment and fire extinguishing apparatus

11.2 Controller Standalone Commissioning

11.2.1 Pre-Power-On Inspection

  • Disconnect all external circuits; check under no-load conditions
  • Verify power terminal voltage is normal; no short circuits
  • Verify fuse ratings are correct and intact
  • Confirm no foreign matter in the enclosure and no loose wiring

11.2.2 Power-On Self-Test

  • Connect main power; controller starts and enters self-test routine
  • Observe LCD display, indicator lamps, and buzzer for normal operation
  • Check for any fault alarms after self-test completes
  • Disconnect main power; test backup power auto-transfer; verify normal operation on backup power
  • Controller must not lock up or reboot during main/backup power transfer
  • Record self-test results; resolve any faults before continuing

11.2.3 Parameter Configuration

  • Enter system settings menu; set correct date and time
  • Configure detector addresses, types, and location descriptions
  • Set extinguishing delay time; default 30 seconds; adjustable as required
  • Configure interlock logic: single-alarm action, dual-alarm action logic
  • Set auto/manual modes, password permissions, and other parameters
  • Save settings; reboot to confirm parameter activation

11.3 Detection and Alarm Function Commissioning

11.3.1 Smoke Detector Testing

  • Use a dedicated smoke tester to apply smoke to the smoke detector
  • Observe whether the detector fire alarm confirmation LED illuminates
  • Observe whether the controller receives the fire alarm signal and displays the corresponding address and location
  • Verify audible/visual alarms activate simultaneously
  • Record alarm response time; should be ≤ 10 seconds
  • Test all smoke detectors individually until all pass
  • After testing, reset the controller; detectors return to normal monitoring

11.3.2 Heat Detector Testing

  • Use a dedicated heat tester to apply heat to the heat detector
  • Observe detector fire alarm confirmation LED illumination
  • Controller receives fire alarm signal normally with correct location display
  • Test all heat detectors individually
  • Reset the system after testing

11.3.3 Fault Alarm Testing

  • Remove one detector; the controller should issue a fault alarm within 100 seconds displaying the fault address
  • Simulate a loop short circuit; the controller should issue a fault alarm
  • Disconnect main power; the controller should issue a main power fault alarm
  • Disconnect the backup battery; the controller should issue a backup power fault alarm
  • Disconnect the startup circuit; the controller should issue a startup circuit fault alarm
  • Under all fault conditions, fault audible/visual indications function normally with accurate information display
  • Controller should automatically return to normal after fault rectification

11.4 Manual Control Function Commissioning

11.4.1 Emergency Start Test

  • System in manual mode; disconnect solenoid actuator wiring (connect a simulated load)
  • Press the emergency start button outside the protected zone
  • Controller should enter delay countdown displaying remaining delay time
  • After delay expires, startup output terminals should provide DC 24 V output
  • Audible/visual alarms and interlock devices activate simultaneously
  • Record delay time error ≤ ±1 second

11.4.2 Emergency Stop Test

  • Initiate the emergency start program; during the delay period
  • Press the emergency stop button
  • Controller should immediately terminate delay and startup program while maintaining alarm state
  • No voltage output at startup terminals; no extinguishing discharge triggered
  • Test 3 times; each stop action must be reliably executed

11.4.3 Auto/Manual Transfer Test

  • Toggle the auto/manual transfer switch to manual
  • Controller displays manual mode; neither single nor dual alarm initiates automatic extinguishing
  • Toggle to auto mode
  • Controller displays auto mode; dual alarm triggers automatic delay sequence
  • Status display matches switch position; transfer is reliable

11.5 Automatic Interlock Function Commissioning

11.5.1 Single Alarm Interlock Test

  • System in auto mode
  • Trigger any single smoke detector (single alarm)
  • Controller issues level 1 fire alarm signal; audible/visual alarms activate
  • Extinguishing delay is not initiated; no startup output
  • Verify single-alarm non-trigger logic is correct

11.5.2 Dual Alarm Interlock Test

  • System in auto mode; disconnect actual extinguishing agent startup circuit; connect simulated load
  • Simultaneously trigger one smoke detector and one heat detector
  • Controller confirms dual alarm and issues level 2 fire alarm signal
  • Immediately enters 30-second delay countdown; LCD displays remaining time
  • During delay, interlock outputs activate: close fire dampers, shut down air conditioning, cut non-fire power
  • Audible/visual alarms inside and outside the protected zone operate continuously
  • After delay expires, startup output terminals provide DC 24 V output
  • Simulate pressure feedback signal; controller displays discharge state; gas discharge indicator illuminates
  • Fire control room host receives fire alarm, discharge, and interlock feedback signals
  • Repeat test 2–3 times; each cycle must show correct logic and reliable operation

11.5.3 Multiple-Unit Synchronization Testing

  • With multiple coordinated units, measure start signal output timing differences between units
  • Response time difference should be ≤ 2 seconds
  • All pressure switches report feedback normally

11.6 Simulated Discharge Test

Per GB 50263-2007 code requirements, system commissioning shall include a simulated discharge test to verify overall system performance.

11.6.1 Test Preparation

  • Select one protected zone for the simulated discharge test; use nitrogen as the simulated medium
  • Nitrogen cylinder specifications and quantity identical to the agent cylinders; charging pressure not less than design storage pressure
  • Remove the agent cylinders; install nitrogen test cylinders; connect piping and startup devices
  • Confirm personnel evacuated from the protected zone; doors and windows closed
  • Test personnel operate from outside the protected zone; record observations

11.6.2 Auto Mode Discharge Test

  • Set system to auto mode
  • Manually trigger dual fire alarm (smoke + heat)
  • System enters delay; automatic startup after 30 seconds
  • Observe smooth nitrogen discharge; nozzle atomization good and distribution uniform
  • Pressure switch actuates; feedback signal normal; discharge indicator illuminates
  • Interlock equipment operates normally
  • Record discharge time, pressure changes, and action sequence
  • No abnormal noise, piping leakage, or component damage during the test

11.6.3 Manual Mode Discharge Test

  • Set system to manual mode
  • Press emergency start button
  • System discharges after delay
  • Verify all components operate normally

11.6.4 Mechanical Emergency Startup Test

  • Disconnect power to the electrical control system
  • Manually operate the mechanical emergency handle
  • Nitrogen cylinder opens and discharges smoothly
  • Mechanical mechanism operates freely without binding
  • Verify emergency startup function is reliable

11.6.5 Post-Test Restoration

  • After testing, ventilate the protected zone to purge nitrogen
  • Remove nitrogen test cylinders; reinstall agent cylinder assemblies
  • Check all components are reset to normal with correct pressure
  • Clean up the site; restore system to normal monitoring status
  • Complete the simulated discharge test record form

11.7 Overall Performance Testing

  • Continuously run for 72 hours without faults; stable performance
  • All functions tested 3 or more times; each test passes reliably
  • All performance indicators meet design and code requirements
  • Status indication accurate; audible/visual signals clear
  • Event records complete with accurate timestamps
  • Communication with the fire control room host normal; signal upload accurate

11.8 Commissioning Records and Acceptance

After commissioning is complete, compile comprehensive commissioning records including:

  • Commissioning date, personnel, and environmental conditions
  • Equipment models, quantities, and serial numbers
  • Test results for each functional item
  • Simulated discharge test data
  • Identified issues and rectification status
  • Commissioning conclusions

After commissioning passes, issue a commissioning report as the basis for completion acceptance.

12.1 Transportation and Storage Precautions

  • Extinguishing agent cylinders are pressure vessels; transport shall comply with dangerous goods regulations; handle gently; collision, throwing, and rolling are strictly prohibited
  • Cylinders must remain upright during transport, securely fastened to prevent tipping; horizontal stacking layers not exceeding specified limits
  • Storage environment temperature 0–50 °C; keep away from heat sources and open flames; avoid direct sunlight
  • Storage area dry and ventilated; free of corrosive gases; away from flammable and explosive materials
  • Solenoid actuators, detectors, controllers, and other electronic equipment must be protected from moisture, dust, and static electricity
  • For storage exceeding six months, check cylinder pressure is normal
  • Products should remain in original factory packaging to prevent component loss or damage

12.2 Installation and Construction Precautions

  • Construction personnel must be professionally trained and familiar with product structure and installation requirements
  • Confirm the protected zone design complies with GB 50370 code requirements; enclosure, pressure relief opening, and door/window airtightness meet standards
  • Electrical wiring work in rainy or humid conditions is strictly prohibited
  • During installation, keep sealing caps on cylinder head valves, nozzles, and other ports to prevent foreign matter ingress into piping
  • Solenoid actuator safety pins must not be removed before commissioning to prevent accidental actuation
  • High-pressure hose installation must avoid twisting and kinking; bend radius not less than 5 times the hose diameter
  • All threaded connections shall use PTFE tape or sealing gaskets to ensure reliable sealing without leakage
  • Electrical wiring strictly per drawings; verify repeatedly after wiring to prevent misconnection and short circuits
  • Wear safety harnesses when working at height; implement proper safety protection
  • Clean up the site after construction; properly dispose of offcuts and packaging materials

12.3 Commissioning Precautions

  • Commissioning must be performed by professional technical personnel; unauthorized personnel must evacuate the protected zone
  • Before commissioning, verify solenoid actuator safety pins are in place or the startup circuit is disconnected to prevent accidental agent discharge
  • Personnel are strictly prohibited from remaining in the protected zone during simulated discharge tests; high-pressure gas can cause injury
  • During mechanical emergency operation testing, personnel shall stand to the side, away from the nozzle discharge direction
  • Observe electrical safety during live testing to prevent electric shock
  • If any abnormality occurs during commissioning, cut power immediately and investigate before continuing
  • Never arbitrarily modify internal controller parameters, particularly delay time and startup logic
  • After commissioning, restore the system to normal operating state; set auto/manual mode as required
  • Commissioning records must be completed truthfully; falsification is prohibited

12.4 Operation and Usage Precautions

  • The system should be set to automatic mode for daily operation; duty personnel shall not arbitrarily switch to manual
  • Personnel entering the protected zone must first switch the system to manual mode; restore to auto after exit
  • Never arbitrarily touch emergency start/stop buttons or the auto/manual switch; protective covers must not be opened casually
  • Never block or cover detectors, nozzles, audible/visual alarms, or discharge indicator lights
  • Never store large quantities of flammable materials in the protected zone; never privately alter the protected zone structure
  • Protected zone doors and windows should remain closed; pay attention to airtightness when air conditioning and ventilation systems are operating
  • Never privately disassemble or modify system components; never strike cylinders or valves
  • On system alarm, evacuate personnel per the emergency plan; confirm the fire condition before deciding whether to discharge
  • After agent discharge, the protected zone must be ventilated; entry only after gas has been fully purged
  • After system discharge, contact professional personnel promptly for refilling and reset; do not handle independently

12.5 Safety Protection Precautions

  • Heptafluoropropane is low in toxicity, but high concentrations can cause dizziness and asphyxiation; do not enter immediately after discharge
  • After extinguishing, activate mechanical exhaust ventilation in the protected zone; ventilation time not less than 30 minutes
  • Contact with liquid agent may cause frostbite; wear protective gloves when handling
  • Cylinders are pressure vessels; keep away from high temperatures and open flames; never expose to direct sunlight
  • Never perform welding, drilling, impact, or other destructive operations on cylinders
  • If cylinder pressure rises abnormally, evacuate personnel immediately; handle only after pressure relief
  • Regularly inspect the safety relief device; never block the relief port
  • After a fire discharge, measure oxygen concentration and agent concentration in the protected zone before re-entry; enter only when safe

12.6 Operation and Maintenance Precautions

  • Maintenance must be performed by qualified professional personnel
  • Before maintenance, switch the system to manual mode, disconnect the startup circuit, and remove solenoid actuator safety pins
  • Before removing pressure gauges or valve components, confirm cylinder pressure has been released
  • Never disassemble any pressure-bearing component under pressure
  • Replacement seals and diaphragms must be original factory genuine parts
  • Electrical maintenance shall be performed with power disconnected and warning signs posted
  • Annually check cylinder service life; expired cylinders are strictly prohibited from use
  • Keep maintenance records and establish equipment files

12.7 Environmental Usage Limitations

  • Operating ambient temperature 0–50 °C; temperature control measures required outside this range
  • Relative humidity ≤ 95%, non-condensing; moisture protection required in damp areas
  • Air free of corrosive and explosive gases; dust content within limits
  • No strong vibration or impact; no strong electromagnetic interference
  • Altitude ≤ 2000 m; derating design required for high-altitude areas
  • Avoid installation in locations with direct sunlight, rain exposure, or heavy oil contamination

To ensure long-term stable and reliable operation of the pipeline-less gas fire suppression system, a comprehensive maintenance system must be established, with regular inspection, testing, and maintenance to promptly identify and eliminate hazards and ensure the system remains in good working order.

13.1 Maintenance Cycle Overview

Maintenance Level Cycle Main Contents Responsible Party
Daily Inspection Daily Visual inspection, status check Duty personnel
Monthly Inspection Monthly Pressure check, surface cleaning, basic function check Operation & maintenance personnel
Quarterly Inspection Quarterly Detector testing, interlock function testing Professional maintenance personnel
Annual Inspection Annually Comprehensive inspection, simulated startup test, cylinder weighing Professional fire inspection organization
Periodic Inspection Every 3/5 years Cylinder hydrostatic test, valve calibration Special equipment inspection organization

13.2 Daily Inspection (Daily)

Duty personnel shall perform daily patrol inspections of the system, including:

  • Controller main/backup power operation normal; no fault alarms or fire alarms
  • Controller displayed auto/manual status matches actual state
  • Discharge indicator light at protected zone entrance is off; emergency button protective covers intact
  • Cabinet exterior intact; no damage or obstruction by foreign materials
  • Protected zone doors/windows closed normally; no unauthorized modifications
  • Detectors and nozzles unobstructed; no dust accumulation
  • No new flammable or explosive materials in the vicinity
  • Complete duty patrol records; report anomalies promptly

13.3 Monthly Inspection and Maintenance

Professional operation and maintenance personnel shall perform monthly inspection and maintenance as follows:

13.3.1 Cylinder and Unit Inspection

  • Check extinguishing agent cylinder pressure; gauge pointer in green normal range; pressure loss ≤ 5%
  • Check cylinder exterior for corrosion, deformation, or impact marks
  • Check cylinder head valve, high-pressure hose, and nozzle for leakage or damage
  • Check pressure switch and solenoid actuator exterior; wiring secure
  • Check cabinet fixing; door lock intact; interior clean and free of debris
  • Check safety relief device; unobstructed and free of corrosion
  • Check nameplates and labels are clear and complete

13.3.2 Control Equipment Inspection

  • Clean dust from controller surface; check display normal and keys responsive
  • Check main/backup power transfer function normal; battery voltage normal
  • Check all indicator lamps and display components normal
  • Check terminal blocks for loosening or oxidation
  • Check grounding reliability; grounding resistance compliant
  • Check event records normal; clock accurate

13.3.3 Detector and Field Device Inspection

  • Clean dust from detector surfaces; ensure detection sensitivity
  • Check detector bases secure; wiring not loose
  • Check audible/visual alarms and discharge indicator lights for visual integrity
  • Check emergency start/stop buttons and auto/manual switches intact
  • Check all conduit secure; no damage or detachment

13.3.4 Protected Zone Inspection

  • Check protective zone enclosure structure intact; no unauthorized openings or wall modifications
  • Check pressure relief opening intact; unobstructed and uncovered
  • Check doors/windows and fire dampers for good airtightness
  • Check evacuation routes clear; emergency lighting functional
  • Check ventilation/air conditioning system normal; interlock function intact

13.3.5 Cleaning and Tidy-Up

  • Wipe dust from cabinet, controller, and detector surfaces
  • Neatly dress and bundle cabinet wiring
  • Clear protected zone debris; maintain a clean environment
  • Complete monthly maintenance records

13.4 Quarterly Inspection and Maintenance

Quarterly functional testing shall be performed to deeply verify system reliability:

13.4.1 Alarm Function Testing

  • Apply smoke test to each smoke detector individually; confirm normal alarm function
  • Apply heat test to each heat detector individually; confirm normal alarm function
  • Test audible/visual alarm volume and brightness meet requirements
  • Test fault alarm function by simulating open and short circuit faults
  • Test event recording function; records accurate and complete

13.4.2 Manual Function Testing

  • Test emergency start button function normal (startup circuit disconnected)
  • Test emergency stop button function reliable
  • Test auto/manual transfer switch; smooth operation and correct status display
  • Test delay function; delay time accurate

13.4.3 Interlock Function Testing

  • Simulate dual alarm; test fire dampers, air conditioning, and fans close/interlock correctly
  • Test non-fire power cutoff interlock normal
  • Test emergency lighting interlock activation normal
  • Test communication with fire control room host; signal upload accurate

13.4.4 Circuit Inspection

  • Measure insulation resistance of each circuit; verify compliance
  • Check terminal blocks for oxidation or loosening; re-tighten
  • Check metal conduit grounding continuity
  • Check cables for aging or damage

13.5 Annual Comprehensive Inspection

An annual comprehensive inspection shall be conducted by a qualified fire inspection organization, with a formal inspection report issued:

13.5.1 Cylinder and Extinguishing Agent Inspection

  • Weigh each extinguishing agent storage cylinder to check for agent leakage
  • If leakage exceeds 5% of the filling quantity, the cylinder must be refilled
  • Check the pressure of the nitrogen starting cylinders; replenish nitrogen if insufficient
  • Check cylinder inspection validity period; arrange inspection in advance for cylinders nearing expiry

13.5.2 Simulated Start Test

  • Disconnect the actual extinguishing agent cylinders, connect simulated loads
  • Conduct automatic mode simulated start test, verifying the entire process logic
  • Conduct manual mode simulated start test
  • Conduct mechanical emergency start function test
  • Test the reliability of the emergency stop function
  • Test multi-unit linkage synchronization

13.5.3 Simulated Discharge Test

According to code requirements, conduct periodic sampling simulated discharge tests to verify overall system performance:

  • Use nitrogen or compressed air
  • Verify pipeline unobstructed flow, nozzle atomization effect
  • Verify pressure switch feedback accuracy
  • Verify system response time and discharge time meet requirements

13.5.4 Component Calibration and Replacement

  • Verify safety valve calibration to ensure accurate relief pressure
  • Calibrate pressure gauges, error within permissible range
  • Inspect seal components for aging; replace if necessary
  • Check battery capacity; replace if less than 3 years of service life remains
  • Clean or replace detector filter screens

13.5.5 Protected Area Safety Inspection

  • Inspect protected area airtightness to ensure extinguishing agent retention rate meets requirements
  • Check relief vent area and position comply with codes
  • Check evacuation routes and emergency exits meet requirements
  • Check warning signs and operating procedures are posted completely

13.6 Mandatory Periodic Inspection (Special Equipment Requirements)

Per the “Gas Cylinder Safety Technical Regulation” TSG 23-2021:

  • Heptafluoropropane extinguishing agent cylinders: hydrostatic strength test every 5 years
  • High-pressure nitrogen starting cylinders: hydrostatic test every 3 years
  • Cylinders that have been in service for 20 years must be mandatorily scrapped and shall not continue in use
  • Inspections must be conducted by organizations qualified for gas cylinder inspection, with inspection reports issued
  • Qualified cylinders shall be stamped with inspection marks and affixed with inspection labels
  • Cylinders that fail inspection or are overdue for inspection are strictly prohibited from being filled and used

13.7 Common Maintenance Items

13.7.1 Extinguishing Agent Refilling

  • When agent leakage exceeds limits or after discharge, refilling shall be performed by specialized manufacturers
  • Cylinders must be inspected before refilling; filling is only permitted after passing inspection
  • Filling purity of extinguishing agent ≥ 99.9%, filling tolerance ≤ ±2%
  • Airtightness test shall be conducted after refilling; no leakage permitted
  • Complete filling records and update cylinder body labels

13.7.2 Valve Repair

  • Cylinder head valve leakage: disassemble and clean, replace seals, reassemble and pressure test
  • Solenoid actuator failure: replace coil or replace unit entirely
  • Pressure switch malfunction: calibrate actuation pressure or replace with new unit
  • Safety valve abnormal relief: replace rupture disc, calibrate actuation pressure

13.7.3 Electrical Repair

  • Detector failure: clean, calibrate; replace if unrepairable
  • Controller failure: troubleshoot power supply, main board, loop board faults; replace faulty boards
  • Wiring faults: locate break points and short circuits; repair or replace cables
  • Sounder/strobe, indicator light faults: replace bulb or entire device

13.7.4 Structural Repair

  • Cabinet deformation, corrosion: repair and reshape, touch up paint
  • Loose brackets: re-tighten, reinforce by welding
  • Nozzle blockage: disassemble and clean, clear spray orifices

13.8 Maintenance Safety Regulations

  • All maintenance operations must be carried out by two or more persons, with safety supervision in place
  • Before operations, switch to manual mode, disconnect the start circuit, remove safety pins, and post warning signs
  • Pressurized components must never be disassembled while under pressure; pressure must be released before disassembly
  • Electrical repairs require power-off operation and voltage verification
  • Entry into protected areas requires two persons with one person remaining outside as sentinel
  • Filling and pressure-testing operations shall be performed by certified personnel
  • Replacement parts shall prioritize original manufacturer genuine products to ensure compatibility and reliability
  • Functional testing shall be conducted after maintenance; the system shall only be restored to operation after passing
  • All maintenance records shall be filed in equipment archives and retained for no less than 5 years

14.1 System Alarm Faults

14.1.1 Controller Reports Main Power Fault

Possible causes:

  • Mains power outage or abnormal voltage
  • Main power fuse blown
  • Main power circuit open circuit or poor contact
  • Controller power module failure

Solutions:

  • Check whether the mains power supply is normal and whether the distribution box breaker has tripped
  • Check the controller power fuse; if blown, replace with same specification fuse
  • Check main power terminal connections; re-tighten loose wiring
  • Measure power input voltage; if normal, determine power module failure and contact the manufacturer for repair
  • The backup battery automatically supplies power during main power fault; restore main power promptly to avoid battery depletion

14.1.2 Controller Reports Backup Battery Fault

Possible causes:

  • Battery aging, insufficient capacity
  • Loose battery wiring, poor contact
  • Charging circuit failure; battery not charging
  • Battery damaged or leaking

Solutions:

  • Check battery terminals; tighten loose connections
  • Measure battery voltage; if below 80% of rated value, replace
  • Check charging output voltage; repair charging circuit if abnormal
  • Battery service life is typically 3 to 5 years; replace promptly upon expiry
  • Observe correct polarity when replacing batteries; reverse connection is strictly prohibited

14.1.3 Controller Reports Loop Fault

Possible causes:

  • Detector line short circuit or ground fault
  • Detector line open circuit, loose connector
  • Detector damaged, address conflict
  • Loop board failure
  • End-of-line resistor disconnected or incorrect resistance value

Solutions:

  • Review the fault indication to determine whether it is a short circuit or open circuit
  • Measure line insulation and continuity in sections to locate the fault point
  • Check detector base wiring; re-crimp loose wire ends
  • Replace faulty detector; re-program address
  • Check end-of-line resistor at loop end; install if missing
  • If wiring is normal and fault persists, replace the loop board

14.1.4 Detector False Alarm

Possible causes:

  • Excessive dust accumulation on detector, sensitivity drift
  • Large amounts of smoke, moisture vapor, or dust in the environment
  • Insects or debris entering the detector
  • Dramatic fluctuations in ambient temperature and humidity
  • Strong electromagnetic interference
  • Detector aging failure

Solutions:

  • Reset the controller and observe whether the alarm repeats
  • Clean detector filter screen and optical chamber to remove dust
  • Investigate site conditions; eliminate smoke, moisture vapor and other interference sources
  • Check the detector insect-proof cover is intact; clean internal debris
  • Adjust detector installation position to avoid interference sources
  • Lower detector sensitivity level
  • Replace detectors that frequently false alarm with new units

14.1.5 Controller Reports Start Circuit Fault

Possible causes:

  • Start circuit open circuit, loose wiring
  • Solenoid actuator coil open circuit
  • Line short circuit or ground fault
  • End-of-line monitoring resistor disconnected

Solutions:

  • Check wiring at both ends of the start circuit; tighten loose terminals
  • Measure solenoid actuator coil resistance; normal is approximately 15–20 Ω; infinite resistance indicates burnout and requires replacement
  • Measure line insulation to eliminate short circuit or ground fault
  • Check line end-of-line resistor; reinstall or replace

14.2 Cylinder Bank and Piping Faults

14.2.1 Storage Cylinder Pressure Drops Too Quickly

Possible causes:

  • Poor cylinder head valve sealing, minor leakage
  • Pressure gauge connection leakage
  • High-pressure hose connector leakage
  • Safety relief diaphragm minor leakage
  • Natural pressure drop due to ambient temperature decrease

Solutions:

  • Observe ambient temperature changes; check whether pressure recovers when temperature rises
  • Apply soapy water to all connection points and look for bubble leakage points
  • Tighten leaking connection fittings; if leakage persists, disassemble and replace seals
  • If pressure loss exceeds 5%, contact the manufacturer for refilling
  • For severe leakage, move the cylinder to a safe area, relieve pressure, then perform maintenance

14.2.2 Cylinder Head Valve Opens but No Discharge

Possible causes:

  • Excessive extinguishing agent fill, liquid phase blocking the outlet
  • Nozzle blocked, spray orifices obstructed by debris
  • High-pressure hose kinked and blocked
  • Cylinder head valve core stuck, not fully opened
  • Extinguishing agent temperature too low, insufficient vapor pressure

Solutions:

  • Immediately evacuate personnel; allow the extinguishing agent to release naturally
  • After the incident, disassemble and inspect the nozzle; clear blockages
  • Inspect the high-pressure hose; straighten kinked sections
  • Disassemble the cylinder head valve, clean the valve core, replace damaged parts
  • Ensure ambient temperature is within the operating range

14.2.3 Piping Leakage During Discharge

Possible causes:

  • Poor fitting sealing, threads not tightened
  • Aged or damaged sealing gaskets
  • High-pressure hose aged and cracked
  • Cracks at pipe weld joints

Solutions:

  • Handle after discharge is complete and pressure is relieved
  • Re-tighten fittings; replace sealing gaskets
  • Replace aged or damaged high-pressure hoses
  • Replace cracked piping or repair by welding, then pressure test

14.2.4 Pressure Switch Does Not Actuate

Possible causes:

  • Actuation pressure set too high
  • Valve core stuck, spring failure
  • Loose wiring, open circuit
  • Oxidized contacts, poor contact
  • Insufficient discharge pressure

Solutions:

  • Calibrate the pressure switch actuation pressure
  • Disassemble and clean the valve core; replace failed spring
  • Check wiring; re-crimp securely
  • Polish contacts to remove oxidation layer
  • Check cylinder bank pressure; refill to rated value

14.3 Start Control Faults

14.3.1 No Start in Automatic Mode

Possible causes:

  • System in manual mode, not switched to automatic
  • Only a single detector alarmed, dual alarm condition not met
  • Emergency stop button pressed and not reset
  • Start circuit open circuit, solenoid actuator damaged
  • Controller start output circuit fault
  • Solenoid actuator safety pin not removed

Solutions:

  • Check manual/automatic status; switch to automatic mode
  • Confirm whether both smoke and heat detectors are alarming simultaneously
  • Check whether the emergency stop button has been reset
  • Measure start output voltage; if no output, troubleshoot the controller
  • Check solenoid actuator wiring and coil; replace if damaged
  • Confirm the safety pin has been removed

14.3.2 Emergency Stop Failure

Possible causes:

  • Stop button wiring loose or open circuit
  • Button contacts oxidized, poor contact
  • Controller program fault
  • Delay period ended, system entered discharge phase

Solutions:

  • Check button wiring; re-tighten
  • Replace faulty button
  • Emergency stop is ineffective after the delay period ends; this is normal logic
  • Return faulty controller to factory for repair

14.3.3 Mechanical Emergency Start Stuck

Possible causes:

  • Handle transmission mechanism rusted or stuck
  • Striker pin bent or binding
  • Cylinder head valve core adhesion
  • Long period without operation, moving parts lack lubrication

Solutions:

  • Clean the transmission mechanism; apply anti-rust lubricating grease
  • Correct the striker pin position; ensure smooth operation
  • Regularly test the emergency mechanism to maintain flexibility
  • Disassemble and repair if severely stuck

14.4 Linkage Peripheral Faults

14.4.1 Fire Damper Does Not Close via Linkage

Possible causes:

  • Linkage output line open circuit
  • Fire damper actuator damaged
  • Control module fault
  • Linkage logic settings incorrect
  • Fire damper mechanical binding

Solutions:

  • Check linkage output voltage; repair line break points
  • Test the fire damper actuator; replace if damaged
  • Check control module address and logic settings
  • Manually test fire damper mechanical action to eliminate binding
  • Re-configure controller linkage logic

14.4.2 Discharge Indicator Light Does Not Illuminate

Possible causes:

  • Indicator bulb burned out
  • Loose wiring, open circuit
  • Pressure switch not actuated
  • Linkage relay fault

Solutions:

  • Replace indicator bulb or entire unit
  • Check wiring; tighten terminals
  • Check whether the pressure switch is operating normally
  • Repair the linkage relay

14.5 Other Common Problems

14.5.1 Accidental System Discharge

Possible causes:

  • Personnel accidentally press the emergency start button
  • Excessive dust or smoke interference on detectors causing dual false alarms
  • Electromagnetic interference causing erroneous controller output
  • Solenoid actuator insulation breakdown causing accidental actuation
  • Failure to remove safety pin during maintenance causing accidental trigger

Solutions:

  • Strengthen management; strictly prohibit unauthorized personnel from touching control buttons
  • Regularly clean detectors to reduce false alarm probability
  • Implement proper line shielding and grounding to improve anti-interference capability
  • Replace solenoid actuators with certified quality products
  • Strictly follow safety procedures during maintenance; safety pins must be removed
  • Ventilate promptly after accidental discharge; contact the manufacturer for refilling and reset

14.5.2 Poor Fire Extinguishing Performance

Possible causes:

  • Protected area doors and windows not closed, poor airtightness, extinguishing agent loss
  • HVAC not linked off, carrying away extinguishing agent
  • Insufficient extinguishing agent fill quantity, concentration too low
  • Nozzle blocked or wrong direction, uneven distribution
  • Protected area volume exceeds design range

Solutions:

  • Ensure all doors and windows are closed before discharge
  • Check linkage functions to ensure air conditioning and fans shut off in a timely manner
  • Weigh and check extinguishing agent; refill if insufficient
  • Clean nozzles; adjust spray direction
  • Add additional extinguishing devices for oversized protected areas

14.5.3 Cabinet Rusting, Paint Peeling

Possible causes:

  • Humid environment, corrosive gases present
  • Coating damage not repaired in a timely manner
  • Use of corrosive cleaning agents during cleaning

Solutions:

  • Remove rust and apply matching color anti-rust paint
  • Improve environment ventilation, reduce humidity
  • Use neutral cleaning agents for cabinet cleaning
  • Choose stainless steel cabinets for coastal or highly corrosive environments

Q1: What is the difference between piping-free gas fire suppression and piped systems, and how should I choose?

A: The core difference lies in the extinguishing agent delivery method. In a piped (centralized) system, storage cylinders are concentrated in a cylinder room and delivered through piping to each protected area — suitable for multiple protected areas and large-volume spaces. In a piping-free (pre-engineered) system, the cylinder assembly is placed directly inside the protected area with no piping required — suitable for a single protected area of small to medium volume.

Selection principles:

  • Choose a piped system for multiple dispersed protected areas with a dedicated cylinder room
  • Choose a piping-free system for a single independent protected area, volume ≤ 1600 m³, with no cylinder room
  • For retrofit projects with short construction periods, piping-free systems are preferred
  • For small-to-medium projects with limited budgets, piping-free systems offer better cost-effectiveness

Q2: Is heptafluoropropane harmful to humans? Can it be used in occupied computer rooms?

A: Heptafluoropropane is safe for humans at design extinguishing concentrations (typically 5%–9%). Its NOAEL (No Observed Adverse Effect Level) is 9%, and most computer room design concentrations are kept within 8%, so brief exposure will not cause harm. However, personnel should evacuate promptly during discharge to avoid dizziness or suffocation from prolonged exposure at high concentrations. It can be used in occupied computer rooms, and it is recommended to configure manual/automatic switching; switch to manual mode when personnel are present.

Q3: Is the 30-second delay mandatory? Can it be shortened?

A: National standards specify that the gas extinguishing system delay time is adjustable from 0 to 30 seconds. The default 30 seconds is to allow personnel evacuation time. If the protected area is unattended and rapid discharge is needed after fire confirmation, the delay may be shortened within code limits. However, setting it directly to 0 seconds is not recommended; at least 10 seconds should be retained, while ensuring linked equipment has sufficient time to actuate. Adjusting the delay must be performed by professional personnel; unauthorized modification is prohibited.

Q4: How often does the extinguishing agent need to be replaced?

A: Heptafluoropropane is chemically stable and will not degrade under normal storage conditions, so periodic replacement is not required. Routine monitoring is performed via the pressure gauge, with weighing every six months. As long as weight loss does not exceed 5% and pressure is normal, the system may continue in service. Refilling is only required in the event of leakage, discharge/use, or when cylinders are due for inspection. Cylinders themselves require hydrostatic testing every 5 years and are scrapped after 20 years of service.

Q5: Can multiple piping-free units be installed in one protected area?

A: Yes. Per GB 50370, when a protected area has a volume not exceeding 1600 m³ and an area not exceeding 500 m², multiple pre-engineered extinguishing units may be installed, up to a maximum of 8 units. All units must be capable of simultaneous actuation, with an action response time difference ≤ 2 seconds. Large-volume protected areas can meet extinguishing agent quantity requirements through multi-unit linkage, synchronously controlled by a single extinguishing controller.

Q6: Is a pressure relief vent mandatory? Where should it be installed?

A: Yes, it is mandatory. The protected area is a relatively airtight enclosure; internal pressure rises after extinguishing agent discharge. Without a relief vent, the building envelope may be damaged, or doors and windows may burst. The relief vent should be installed at a position above 2/3 of the protected area net height, typically at the upper portion of the exterior wall. The relief area is determined by calculation, and the vent pressure rating must match the system. For protected areas without exterior walls, relief devices may be installed venting to a corridor.

Q7: Will the system still work during a power outage?

A: Yes. The gas extinguishing controller contains built-in backup batteries. When main power fails, the system automatically switches to battery power, providing continuous operation for ≥ 4 hours in monitoring state. Alarm, linkage, and start functions all operate normally on battery power. The mechanical emergency start is entirely independent of electrical power. As long as the battery is not completely depleted, short-term power outages do not affect system function.

Q8: What should routine inspections focus on? Can ordinary personnel perform them?

A: Routine inspections mainly check appearance and status: whether the controller has fault alarms, whether pressure gauges are in the green zone, whether buttons and indicator lights are intact, and whether the protected area has any abnormalities. No specialized skills are required; duty personnel can perform these after brief training. However, functional testing, maintenance, and refilling must be performed by certified professionals. Ordinary personnel should not arbitrarily disassemble equipment or test start functions.

Q9: What should I do when the system alarms? Should I press start?

A: After the system alarms, follow these steps:

  • First determine whether it is a single alarm or dual alarm. A single alarm is typically a pre-warning; send personnel to check the fire condition on site
  • Upon confirming a real fire, notify all personnel in the protected area to evacuate immediately
  • After confirming all personnel have evacuated, close doors, windows, air conditioning, and ventilation equipment
  • If the system is in automatic mode, wait for the delay to expire and the automatic discharge to occur
  • If the system is in manual mode or automatic mode has failed, press the emergency start button
  • If it is confirmed to be a false alarm, press emergency stop, reset the system, and investigate the cause

Q10: How long after discharge can personnel enter? What precautions should be taken?

A: After heptafluoropropane discharge, adequate ventilation is required — mechanical exhaust for no less than 30 minutes, or longer for natural ventilation. Before entry, verify internal oxygen concentration ≥ 19.5% and extinguishing agent concentration within safe limits. Enter with two people, carry a respirator, work quickly, and evacuate immediately if dizziness or nausea occurs. Wear appropriate protection when servicing equipment to avoid frostbite from cold components.

Q11: Can I add extinguishing agent or disassemble and repair the system myself?

A: No. Extinguishing agent storage cylinders are pressure vessels. Filling requires professional qualifications and specialized equipment; improper pressure control during unauthorized filling poses an explosion risk. Disassembly and repair of system components requires professional knowledge; improper operation may cause accidental discharge or leakage. All filling, repair, and inspection must be performed by qualified professional organizations and personnel with appropriate certifications.

Q12: Will computer room renovation or remodeling affect the system?

A: Yes, it will. When renovating a protected area, attention must be paid to:

  • Do not arbitrarily demolish or modify walls or expand areas; volume changes will affect extinguishing concentration
  • New openings or enlarged door/window gaps reduce airtightness, causing extinguishing agent loss
  • Ceiling or partition modifications may obstruct nozzles and detectors, affecting performance
  • New large equipment may block extinguishing agent distribution
  • Consult fire protection professionals before renovation; recalculate design parameters and adjust system configuration if necessary

Q13: Are there special requirements for high-altitude areas?

A: In areas above 2,000 meters elevation, due to thinner air, the design extinguishing concentration must be appropriately increased. Electrical component heat dissipation also deteriorates, requiring derating. It is recommended to select equipment one size larger, increase extinguishing agent fill quantity, and strengthen equipment cooling. Design parameters must be recalculated based on the specific altitude.

Q14: Will low winter temperatures affect the system?

A: The heptafluoropropane system has an operating ambient temperature requirement of 0–50 °C. If indoor temperature drops below 0 °C in winter, the extinguishing agent saturated vapor pressure decreases, affecting discharge rate and atomization quality. Heating and insulation measures should be implemented in low-temperature environments to ensure ambient temperature remains above 0 °C. Temperature monitoring is particularly important in unheated computer rooms in northern regions during winter.

Q15: Does the system require annual inspection? What are the consequences of not performing it?

A: Per fire protection regulations, the gas extinguishing system must undergo at least one comprehensive inspection per year, with an inspection report issued by a qualified organization. Failure to conduct required inspections constitutes a fire safety hazard; fire inspection authorities will order rectification, and failure to comply may result in penalties. More importantly, prolonged operation without inspection may leave the system with hidden faults, preventing proper activation during a real fire and causing severe losses.

After installation and commissioning of the piping-free gas fire suppression system is completed, completion acceptance shall be organized per national codes. The system may only be formally put into operation after passing acceptance. Acceptance work is organized by the construction unit, with participation from construction, design, supervision, inspection and testing units, strictly per GB 50263-2007 “Code for Installation and Acceptance of Gas Fire Extinguishing Systems.”

16.1 Acceptance Preconditions

  • All system installation and commissioning completed; construction unit self-inspection passed; commissioning report issued
  • Construction process documentation and concealed works acceptance records complete
  • Third-party fire inspection organization passed inspection; inspection report issued
  • Protected area decoration and supporting facilities fully completed, meeting design requirements
  • Operations personnel trained, mastering basic operation and emergency handling
  • Acceptance plan prepared; acceptance personnel in place

16.2 Acceptance Documentation Review

At acceptance, technical documentation shall first be reviewed. The following documents must be available:

  • System completion acceptance application report
  • Construction drawing design documents, design change records, design descriptions
  • Product factory certificates, 3C certification certificates, inspection reports
  • Gas cylinder factory inspection reports, filling records
  • Main component factory inspection reports
  • Site construction quality management inspection records
  • Construction process inspection records (installation, wiring, pressure testing, etc.)
  • Concealed works acceptance records
  • Commissioning reports, simulated discharge test records
  • Third-party inspection reports
  • Operation and maintenance procedures, management regulations
  • Operations personnel training records

Documentation must be authentic, complete, and properly stamped/signed. Missing items must be submitted within a specified deadline.

16.3 Visual Quality Acceptance

On-site inspection of appearance and installation quality:

  • Cabinet installed securely, plumb, surface smooth, coating intact, labels clear
  • Cylinder banks fixed reliably, no corrosion or damage, pressure gauge readings normal
  • Valves, piping, and nozzles installed squarely, connections secure, no leakage traces
  • Detectors, sounder/strobes, buttons, and indicator lights installed at correct positions and firmly fixed
  • Cable routing level and plumb, securely fixed, clearly labeled, fire-stopping properly implemented
  • Grounding device intact, grounding label clear
  • Protected area building envelope intact, doors and windows airtight, relief vent size and position correct
  • Warning signs and operation instructions posted completely and prominently

16.4 Functional Acceptance Testing

16.4.1 Alarm Function Acceptance

  • Randomly select detectors for smoke injection and heat application tests
  • Detector alarm response normal, controller display accurate
  • Sounder/strobe simultaneously activated, sound pressure level meets requirements
  • Fault alarm function normal, fault display accurate
  • Sampling ratio not less than 20%, and not less than 2 units

16.4.2 Control Function Acceptance

  • Test manual/automatic switching function; status display correct
  • Test emergency start and emergency stop functions; reliable actuation
  • Test delay function; delay time accurate
  • Test dual alarm linkage logic correct; single alarm does not start
  • Simulated start test, start output normal

16.4.3 Linkage Function Acceptance

  • Simulate fire alarm; test fire damper, air conditioning, and fan linked shutdown
  • Test non-fire power supply cut-off function
  • Test discharge indicator light illumination function
  • Test communication with fire control room; signal upload accurate
  • All linkage actions timely and accurate; feedback normal

16.4.4 Simulated Discharge Test Acceptance

  • Each protected area should undergo one simulated discharge test
  • Use nitrogen or compressed air, activated in automatic mode
  • Discharge smooth, nozzle atomization good, distribution uniform
  • Pressure switch actuates, feedback signal correct
  • Linked equipment operates normally
  • No leakage, no component damage during testing

16.4.5 Mechanical Emergency Start Acceptance

  • Disconnect the electrical control system; operate the mechanical emergency handle
  • Valve opening smooth, mechanism flexible without binding
  • Discharge normal, verifying emergency function reliability

16.5 Main Performance Indicator Acceptance

Item Requirement
Extinguishing agent fill quantity deviation ≤ ±2%, verified by weighing
System working pressure Within rated range
Extinguishing agent discharge time ≤ 10 seconds
Delay time error ≤ ±1 second
Multi-unit linkage action time difference ≤ 2 seconds
Insulation resistance ≥ 20 MΩ
Grounding resistance ≤ 4 Ω
Protected area relief vent area Conforms to design requirements

16.6 Acceptance Determination Criteria

16.6.1 Acceptance Pass Criteria

The system acceptance is deemed qualified when all items meet the following conditions:

  • Technical documentation complete and valid
  • Visual quality meets requirements
  • All functional tests passed
  • Simulated discharge test passed
  • Main performance indicators meet standards
  • No major safety hazards present

16.6.2 Veto Items (Serious Non-Conformance)

Acceptance is directly judged as failed if any of the following conditions occur:

  • Single smoke detection used without dual smoke/heat detection, directly triggering extinguishing
  • System lacks mechanical emergency manual start device
  • Protected area has no relief vent, or relief vent severely non-compliant
  • Extinguishing agent fill quantity severely insufficient, fraudulent
  • Gas cylinders without inspection certificates or overdue for inspection
  • Products without 3C certification, not meeting market access requirements
  • Simulated discharge test failed; system cannot start normally
  • Linkage function failed; cannot shut down ventilation and air conditioning

16.6.3 General Non-Conformance Items

General appearance, labeling, and localized installation issues are classified as general non-conformance and may pass after rectification within a deadline and re-inspection.

16.7 Acceptance Rectification and Re-inspection

  • Issues found during acceptance shall be documented in a rectification notice, specifying rectification content and deadlines
  • The construction unit shall rectify accordingly and apply for re-inspection upon completion
  • If re-inspection still fails, continue rectification until qualified
  • Upon full compliance, sign the completion acceptance qualification document

16.8 Acceptance Handover

After acceptance passes, system handover procedures shall be processed:

  • Hand over all technical documentation and spare parts to the user unit
  • Hand over system operation authority and passwords
  • Conduct on-site training for user unit operations personnel
  • Sign handover records, clarifying maintenance responsibilities
  • System formally enters operation

I. Search Keyword Classification

1. Core Primary Keywords

  • Piping-free gas fire suppression
  • Cabinet-type heptafluoropropane fire extinguishing device
  • Pre-engineered gas extinguishing system
  • Computer room gas fire suppression system
  • Heptafluoropropane piping-free extinguishing system

2. High-Conversion Long-Tail Keywords

  • Piping-free gas fire suppression installation wiring commissioning manual
  • Cabinet-type heptafluoropropane fire extinguishing device installation guide
  • Computer room piping-free gas fire suppression system construction plan
  • Heptafluoropropane pre-engineered extinguishing system commissioning code
  • Piping-free gas extinguishing system acceptance standard
  • Small-to-medium computer room gas fire suppression configuration plan
  • Electrical distribution room piping-free heptafluoropropane extinguishing system
  • Archive room gas fire suppression equipment manufacturer quotation

3. Industry Traffic Keywords

  • Gas extinguishing system construction and acceptance code
  • Heptafluoropropane extinguishing system operating principle
  • Difference between piping-free and piped gas extinguishing
  • Best gas for computer room fire suppression
  • How often to replace heptafluoropropane extinguishing agent
  • Gas extinguishing system daily maintenance
  • Pre-engineered extinguishing system design code
  • Cabinet-type gas extinguishing device national standard

4. Brand-Specific Keywords

  • Lain piping-free gas fire suppression
  • Guangdong Lain heptafluoropropane fire extinguishing device
  • Lain computer room gas fire suppression system
  • Guangzhou Lain pre-engineered extinguishing system
  • gdlain.com gas extinguishing equipment

5. Drop-Down / Related Search Keywords

  • Piping-free gas fire suppression installation steps
  • Piping-free gas fire suppression wiring diagram
  • Piping-free gas fire suppression commissioning method
  • Piping-free gas fire suppression precautions
  • Piping-free gas fire suppression common faults
  • Heptafluoropropane cabinet device parameters
  • Computer room gas fire suppression acceptance process
  • Gas extinguishing system repair and maintenance

II. SEO Optimization Tag System

1. Page Core Optimization Tags

Element Content
Page Topic Piping-free gas fire suppression installation wiring commissioning manual
Target Keywords Piping-free gas fire suppression, cabinet-type heptafluoropropane, installation wiring commissioning
Page Type Technical manual / product handbook
Applicable Scenarios Computer room fire protection engineering, equipment procurement, construction commissioning, operation and maintenance

2. Title Tag

Piping-Free Gas Fire Suppression Installation Wiring Commissioning Manual — Cabinet-Type Heptafluoropropane Pre-Engineered Extinguishing System Construction and Acceptance Complete Guide — Guangdong Lain Smart Computer Room

3. Meta Keywords

Piping-free gas fire suppression, cabinet-type heptafluoropropane fire extinguishing device, pre-engineered gas extinguishing system, computer room gas fire suppression installation, heptafluoropropane wiring commissioning, gas extinguishing system acceptance standard, Guangdong Lain Smart Computer Room

4. Meta Description

Guangdong Lain Smart Computer Room professionally provides a complete piping-free gas fire suppression system installation wiring commissioning manual, with detailed explanation of cabinet-type heptafluoropropane pre-engineered extinguishing device product introduction, composition and classification, technical parameters, installation steps, wiring specifications, commissioning methods, acceptance standards, maintenance and fault handling. Applicable to computer rooms, electrical distribution rooms, archive rooms and other locations. Compliant with GB 50263 and GB 50370 national standards.

5. H1 Tag

Piping-Free Gas Fire Suppression Installation Wiring Commissioning Manual (Cabinet-Type Heptafluoropropane Pre-Engineered Extinguishing System)

6. H2 Tags

  • Product Introduction
  • Product Composition
  • Product Classification
  • Product List
  • Product Operating Principle
  • Product Technical Parameters
  • Product Functions and Features
  • Product Application Scenarios
  • Product Installation Specifications
  • Product Wiring Standards
  • Product Commissioning Process
  • Product Precautions
  • Product Repair and Maintenance
  • Product Common Problems and Solutions
  • Product QA
  • Product Acceptance Standards

7. Internal Link Optimization Tags (Natural Anchor Text Placement)

Core Anchor Texts: Piping-free gas fire suppression, cabinet-type heptafluoropropane fire extinguishing device, pre-engineered gas extinguishing system

Long-Tail Anchor Texts: Piping-free gas fire suppression installation method, heptafluoropropane system wiring commissioning, computer room gas fire suppression acceptance code

Related Anchor Texts: Computer room environment monitoring system, micro-module cold aisle, shielded computer room construction, computer room precision air conditioning

Copyright Notice

The copyright of this document is owned by Guangdong Lain Smart Computer Room Equipment Co., Ltd., and is protected by the Copyright Law of the People’s Republic of China. Any organization or individual is prohibited from copying, reproducing, excerpting, modifying, disseminating, commercially using, or creating mirror versions of all or part of this document without the written authorization of the Company.

For reprinting or quoting content from this document, the source must be credited as “Source: Guangdong Lain Smart Computer Room Equipment Co., Ltd., Website: https://gdlain.com,” and the original content must not be distorted or altered. Commercial use is prohibited. Violators of the above statement will be held legally liable by the Company.

The content of this document serves as product technical guidance and may be updated periodically with product technology upgrades without prior notice. The latest version as officially released by the Company shall prevail.